Forwards Dynamic Analysis of Wetwell-to-Drywell Vacuum Breakers & Improved Dynamic Vacuum Response, in Response to Generic Ltr 83-08.Results Demonstrate That as-built 18- Inch A&M Vacuum Breaker Valves Meet ASME Code Criteria
ML17252A577
Person / Time
Site: Dresden, Quad Cities, 05000000
Issue date: 07/12/1983
From: Rybak B
COMMONWEALTH EDISON CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML17194B633 List:
References
6931N, GL-83-08, GL-83-8, NUDOCS 8307190062
Download: ML17252A577 (7)


Text

I: e Commonwealt'artison One First National.FWr" Chicago, Illinois Address Reply to: Post Office Box 767 Chicago, Illinois 60690 July 12~ 1983 Mr. Harold R. Denton, Director Off ice of Nuclear Reactor Regulation u:s. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Dresden Station Units 2 and 3 Quad Cities Station Units 1 and 2 Modification of Vacuum Breakers on Mark I Containment ~ Generic Letter 83-08 NRC Docket* Nos~ 50~237/249i-50*254/265 Beferences a):

NRC Generic Letter 83-08 from D~n:

Eisenhut to all Mark I Utilities~

Same Subject, dated February 2, 1983.

b):

Continuum Dynamics~ Inc: (CDI) Tech:

Dear Mr. Denton:

Note No. 82-31, Mark I Vacuum Breaker Improved Valve Dynamic Model - Model Development a~d Validation~ Revision o1*

September 1982 (submitted to the NRC v a GE letter MFN~l59-82 dated 10-28-82 on beha~f of the *Mark I Owners Group):

The purpose of this submittal is to document the Commonwealth Edison assessment of the subject drywell/wetwell vacuum breakers in response to the NRC generic letter 83-08 (reference 1).

The wetwell/

drywell vacuum breaker valves both at Dresden and Quad Cities~ have been evaluated in accordance with the ASME Boiler and Pressure Vessel Code, Secion III, Subsection NC for Class 2 components~ 1977 edition inqluding the Summer 1977 addenda as required by the Mark I Program Structural Accept~~ce £riteria (NED0-24583-1).

The evaluation results are presented in the ~nclosed certified stress reports (attachments 2 & 3), prepared by NUTECH in 1981.

During the Short Term Program the valves on both Quad Cities and Dresden were modified to have wrought aluminum discs with stainless steel posts.

The old valve had cast aluminum discs~

These changes were incorporated in the above mentioned evaluations:

  • i H.

R~ Denton 2

July 12~ 1983 Based on the results of the analyses (attachment 2) modifica-tions have been made to the 18" Atwood & Morrill (A&M) internally mounted vacuum breaker valves at Quad Cities Units l & 2:

These modifications consisted of replacing the shaft and the weight lever with those made of higher strength components obtained from the valve manufacturer (A&M) during the Fall 1981 outage at Quad Cities Unit 2 and Fall 1982 outage at Quad Cities Unit 1.

The analyses results (attachment 3) demonstrate that the as-built 18" externally mounted A&M vacuum b~eaker valves at Dresden Units *2 & 3 meet the ASME codes criteria~

Hence, no modifications are necessary.

Attachment I provides an overview of the analyses methodology used in the evaluation presented in Attachments 2 & 3~

The wetwell to drywell pressure differential (~P) across the valve pallet (disc) was developed by Containuum Dynamics~ Inc~ (CDI) and used for the structural evaluation of the vacuum breakers.

Subsequent to issuance of the certified stress reports, CDI refined their dynamic model to reduce conservatism in load prediction and also provided plant-unique impact velocities due to the pressure differential (AP) across the valve pallet.

A report documenting the valve dynamic modeling and model validiation is currently under review by the NRC staff (attachment 2)~

The impact velocities for Quad Cities and Dresden vacuum breakers using this approach are presented in the enclosed CDI reports (attachments 5 and 6).

As shown in Attachment I, the impact velocities calculated and used by NUTECH for stress evaluations presented in the certified stress reports (attachments 2 & 3) are more conservative than those calculated by CDI.

Therefore~ it is concluded that the assessment of the subject vacuum breakers is conservative~

In summary, the Dresden and Quad Cities wetwell to drywell vacuum breaker valves have been analyzed in a conservative manner and required modifications have been completed~

The attachments to this letter provide complete documentation for the plant unique calculations which formed the basis for modifications to the Quad Cities vacuum breakers, and justification for the acceptability of the as-built Dresden vacuum breakers.

Therefore, it is hoped that review and acceptance of this transmitttal by the NRC will close this issue for Commonwealth Edison's Dresden and Quad Cities Stations.

If you have any questions concerning this submittal~ please contact this office.

~..

H. R: Denton 3 -

July 12, 1983 One signed original and sixty (60) copies of this transmittal are provided for your use:

Due to the nature and size of the reports only two, ( 2) copies of Attachments 2 through 5 are provided~

Very truly yours; s;~frt-Nuclear Licensing Administrator lm ):

Overview of the Analyses Methodology 6931N 2):

NUTECH Report COM-08-023; Dynamic Analysis of Wetwell-to-Drywell Vacuum Breakers for Quad Cities Station Units l & 2~ Rev~ O~

September l98L 3):

NUTECH Report COM-28-026, Dynamic Analysis of Wetwell-to-Drywell Vacuum Breakers for Dresden Nuclear Station Units 2 & 3; Rev: O, December 1981~

4):

CDI Tech. Note No. 82-7; Improved Dynamic Vacuum Breaker Valve Response for Quad Cities l & 2, Revision 1, September 1982.

5):

CDI Tech~ Note No. 82-4, Improved Dynamic Vacuum Breaker Valve Response for Dresden 2 & 3~ Revision O, September 1982.

9Page 1 of 3 ATTACHMENT I WETWELL/DRYWELL VACUUM BREAKER VALVES DRESDEN UNITS 2 & 3, AND QUAD CITIES UNITS 1 & 2 OVERVIEW OF THE ANALYSES METHODOLOGY A.

ANALYSES SEQUENCE:

1.

CDI provided NUTECH with pressure differential

(~P) across the Vacuum Breaker Disc (pallet) in May 1980 for QC 1&2 and October 1981 for D 2&3.

2.

NUTECH calculated the pallet impact velocity using NUTECH's proprietary computer program DISCO (rigid body dynamics).

3.

Based on the impact velocities calculated in step.2, NUTECH performed a structural evaluation of the valve components using AN SYS. finite element code and issued certified stress reports in September 1981 for QC 1&2 and December 1981 for D 2&3 (references 2 & 3).

4.

Based on the results of the analyses in step 3, CECo replaced the shaft and weight lever for internally mounted vacuum.breakers at QC 1&2.

However, no modifi-cations are needed for the externally mounted vacuum breakers at D 2&3.

5.

CDI refined the dynamic model and reduced conservatism in load prediction as well as impact velocity calcu-lations and came up with much lower impact velocities, in September of 1982 (References 4, 5 and 6).

Page 2 of 3 B.

Comparison of NUTECH calculated impact velocities vs. CDI calculated impact velocities due to design loading during chugging:

r

\\

Parameter Valve Type Maximum Valve Opening (radians)

NU TECH CDI f No Flow Effects

{Flow Effects Maximum Impact( 5 )

Velocity (radians/sec)

NU TECH CDI jNo Flow Effects

{Flow Effects Quad Cities Units 1 & 2 18" A&M Internal 0.13(l) 0.060}

( 3) 0.046 4.63l(l)

3. 09 )

l ( 3)

2. 45 J Dresden Units 2 & 3 18" A&M External 0.01 (2 )

0.0} ( 4) o~o 0.8224( 2 )

0.0} (4) 0.0 i;b--______________

__.__ __________ __.8 (1)

Group 1 Forcing Function applies to Browns Ferry 1,2,3, Monticello, Pilgrim, and Quad Cities 1&2, transmitted by GE letter MI-G-64 dated May 15,--..~980 from D. L.. Butcher to K.

B~ Ramsden (CECo); Results presented are from NUTECH

_.l:'~E?.:l:"_"l: ~OM-_Q8_:023L Re~~---Q ~~ dat~~ 8~12._"t:.e~-~~-- ~.~~~J~nc~_osed). __ _

(2)

Plant Unique Design Forcing Function transmitted by GE l~tter MI-G-72 of October 19, 1981 from D. L. Butcher to R. H. Mirochna; Results presented are from NUTECH report COM-28-026 1 Rev. 0, dated December 1981 (enclosed).

(3)

CDI Tech. Note No~ 82-7, Improved Dynamic Vacuum Breaker Valve Response for Quad Cities 1&2, Rev. 1, September 1982 (enclose9).

Page 3 of 3 (4)

CDI Tech. Note No. 82-4, Improved Dynamic Vacuum Breaker Valve Response for Dresden 2&3, Rev. 0, September 1982 (enclosed).

(5)

Only closing impacts (i.e. between the pallet and the valve seat) occurred.

There were no opening impacts (i.e. between the pallet and the valve body).

C.

CONCLUSION Since NUTECH's stress analyses are based on higher impact velocities and the stresses in valve components are propor-tional to impact velocity, it can be concluded that the stress evaluation is conservative.

  • July 7, 1983

Subject:

Modification of WW/OW Vacuum Breakers Mark I Containment Program Dresden, Units 2 and 3 Quad Cities; Units l and 2 Mr~ B. Rybak:

Attached is a draft of a letter that we propose be sent to the NRC in response to NRC generic letter 83~08.

This letter requested information on the subject modifications.

If there are any questions on the information presented please contact us.

RHM/mct 33200 Attachment cc:

W.L. Eck D.L. Sanderson Approved by: