ML17250A679

From kanterella
Jump to navigation Jump to search
Forwards LER 80-008/03L-0
Date released: 04/30/2018 Download: ML17250A679


LER 80-008/03L-0:on 800910,during PT-12.2 Test for B Emergency Generator,Bus 16 Breaker Did Not Close.Caused by Guide Pin Split End Opening & Binding Control Relay Antipump Release Lever.Split End Closed
ML17309A102
Person / Time
Site: Ginna 
Issue date: 10/07/1980
From: Edgar C
ROCHESTER GAS & ELECTRIC CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML17309A102 (2)
Forwards LER 80-008/03L-0
ML17250A678
Person / Time
Site: Ginna 
Issue date: 10/07/1980
From: White L
ROCHESTER GAS & ELECTRIC CORP.
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References