ML17207A820
| ML17207A820 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie |
| Issue date: | 02/11/1980 |
| From: | Robert E. Uhrig FLORIDA POWER & LIGHT CO. |
| To: | Harold Denton Office of Nuclear Reactor Regulation |
| References | |
| L-80-50, NUDOCS 8002190606 | |
| Download: ML17207A820 (5) | |
Text
REGULATOR NFORMATION DISTRIBUTION TEM (BIDS)
ACCESSION NBR!800219060b DOC,DATE: 80/02/11 NOTARIZED; NO FACIAL:50 335 St. Lucie Pl anti Unit 1g Florida Power 8
I ight Co, "AOTH~ NAME AUTHOR AFFILIATION UHRIGg R ~ E ~
Florida Power 8 Light Co.
RECIP ~ NAME
'ECIPIENT AFFILIATION DENTON<H,R.
Office of Nuclear Reactor Regulation
SUBJECT:
Submits addi info in suport of util 800222 response to 800102 order to show cause why facility should continue operation until 800315 refueling outage. Observer in control room on
?0 n basis for monitoring valves.
DOCKET 05000335 DISTRIBUTION CODE:
AOAES COPIES RECEIYEO:LTR g ENCL Q
SIZE:
TITLE: Resp to Lesson Learn Task Force Comb Eng 8
50 267 4Q ~~ SOW&~wwWw%woe &W&W&WW&&&&age &%HO WW~ $%w&tOOw~~&wWWww~ww~wwposs WOO~ %W&0%&~w RECIPIENT ID CODE/NAME ACTION!
8 BC QQB A Q INTERNAL>>
REG FIL RF BR 2
NRC PDR 21 PLANT SYS BR 23 EFLT TRT SYS NSIC 6
C ANDERSON G
IMBRO OEI. D EXTERNAL: 20 ACRS COPIES LITTR ENCL 7
7'6 1
RECIPIENT ID CODF/NAME 15 I 8
E 19 ENG BR 20 REAC SFTY BR 22 EEB LPDR 5
C NELSON 7
G CATALINA J>>T>>
TELFORD g ~~AJ COPIES LTTR ENCl E
j 0
TOTAL NUMBER OF COPIES REQUIRED'TTR 43 ENCL
J n
~
M e
e ll I
lt
'h l
Il P
~
l4 p'
. BOX 529100, MIAMI,FL 33152
@Qlhy iir FLORIDA POWER & LIGHTCOMPANY February ll, 1980 L-80-50 Office of Nuclear Reactor Regulation Attention:
Mr. Harold R. Denton, Director U. S. Nuclear Regulatory Commission Washington, D.
C.
20555
Dear Mr. Denton:
Re:
St. Lucie Unit 1
Docket No. 50-335 Show Cause Order In response to Section V of the Show Cause Order for St. Lucie Unit 1 issued by your office on January 2, 1980, Florida Power 8 Light Company (FPL) provided a response showing cause why St. Lucie Unit 1 should be permitted to continue operation until the scheduled March 15, 1980 refueling outage.
This information was submitted by FPL letter L-80-29 dated January 22, 1980.
The purpose of this letter is to provide additional information in support of continued operation of St. Lucie Unit 1 until March 15, 1980.
In our January 22, 1980 submittal, FPL committed to meeting the requirements of the Order by February 15, 1980 with the exception of valve position monitoring of the power operated relief valves (PORV) and the pressurizer safety valves.
Our submittal committed to the installation of a valve position monitoring system during the March refueling.
We also provided technical justification in support of our position that a one month delay in the installation of the monitoring system would not adversely affect the public health and safety.
We continue to maintain that the currently installed redundant and diverse instrumentation described in our earlier response is adequate in detecting and
. providing indication of a leaking or open PORV or pressurizer safety valve.
However, in order to provide additional assurance, FPL will station, for the
- interim, a dedicated, qualified observer in the control room on a 24 hour-per-day basis until March 15, 1980.
In this regard, we propose to station the qualified observer in the control room during operation to monitor PORV and pressurizer safety valve performance under transient or accident conditions and assuring proper response to any valve malfunction.
This observer wi 11 have received special instructions as to his actions in the event of such a transient or accident.
He will immediately monitor RCS
- pressure, Pressurizer Relief Tank level and temperature,'PORV position indicating lights, and tail pipe temperatures.
If there are indications that a
PORV or safety valve has lifted and not reclosed as it should have, the PEOPLE... SERVING PEOPLE
Office of Nuclear Reactor Regulation Page 2
observer will immediately inform the Shift Supervisor or licensed operators so that the proper actions can be taken immediately.
We believe that this additional
- measure, in conjunction with the information contained in our earlier responses, clearly justifies the continued operation of St. Lucie Unit 1 until the scheduled March refueling outage.
Very truly yours, Robert E. Uhrig Vice President Advanced Systems 5 Technology REU/DKJ/cph cc:
Mr. J.
P. O'Reilly, Region II Harold F. Reis, Esquire
4 K%~
1