ML17207A337
| ML17207A337 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie |
| Issue date: | 06/19/1979 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | |
| Shared Package | |
| ML17207A334 | List: |
| References | |
| 50-389-79-08, 50-389-79-8, NUDOCS 7909040061 | |
| Download: ML17207A337 (2) | |
Text
APPENDIX A NOTICE OF VIOLATION Florida Power and Light Company St. Lucie, Unit 2 License No.
CPPR-144 Based on the NRC inspection May 30 to June 1, 1979, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below.
These items have been categorized as described in correspondence to you dated December 31, 1974.
,"(
)
As required by Criterion V of Appendix B to 10 CFR 50, and as implemented by Florida Power and Light Company PSAR Section 17.1A.5, activities affecting quality are prescribed and to be accomplished in accordance with documented procedures.
Procedure
(}I 10.71 and Specification FLO-2998-473 specify that concrete test cylinders will be cured in accordance with ASTM C-31 and ASTM C-511.
ASTM C-31 requires the temperature adjacent to field cured test cylinders be maintained in the range of 60 to 80 degrees Fahrenheit.
ASTM C-511 requires that laboratory cured test cylinders be moist cured in a room having a minimum relative humidity of 95 percent.
Moist curing is defined in ASTM C-31 as meaning that the test specimens shall have free water maintained on the entire surface area at all times.
Contrary to the above, on May 31,
- 1979, temperatures adjacent to field cured test cylinder set numbers 6147 and 6149 were 90 degrees and 86 degrees Fahrenheit respectively.
In the laboratory curing room free water was not visable on test specimens stored along the right wall and no documentation was available to support the 95 percent relative humidity requirement.
This is an infraction.
A similar item was brought to your attention in our letter dated December 14, 1977.
1 cg" '+[~