FLORIDA POWER & LIGHT COMPANY ST.
LUCIE NUCLEAR POWER STATION UNIT No. 1 REACTOR CONTAINMENT BUILDING INTEGRATED LEAK RATE TEST
SUMMARY
TECHNICAL REPORT Prepared for:
Florida Power & Light Company Prepared by:
Ebasco Services Incorporated Plant Operations
& Betterment Dept.
July 10, 1979 Zg 08~00470
TABLE OF CONTENTS I.
INTRODUCTION...................
~
~
~ 1 UMMARY ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
S
~
~ 2 III.
TEST DISCUSSION A.
Description of Containment...
B.
Description of Instrumentation....
~
~
~
~
~
~ 3 1.
Tempera ture Instrumenta tion.
2.
Humidity Instrumentation....
3.
Pressure Instrumentation.
4.
Numa tron (Digital Voltme ter) 5.
Flow Instrumentation........
~ ~
~
~
~
~
~
~
~
~
~
~
~ 4
~
~
~ 4
..4
~
~
~ 4
~ ~
~ 4 C.
Description of Computer Program.
D.
Error Analysis..................
E.
Description of Test..
~
~
~ 5
~
~
~ 6
~
~ ~ 7 RESULTS AND VERIFICATION.............,...,,
~
~
~
~ 10 V. CONCLUSIONS...,,...,....,,..........................:......11 VI.
F IGURES ~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~ 1 2 VII.
APPENDICES ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~ 16 A.
Computer -'enerated Report 1".
Controlled Leak Rate Test B.
Type B and C Test Results
'P
I.
INTRODUCTION A periodic Type "A",Integrated Leakage Rate Test was performed on the containment structure of the Florida Power 6 Light Company St.
Lucie Nuclear Power Station - Unit No.l pressurized water reactor in May of 1979 utilizing the "Absolute Method" of testing.
The test was performed at the reduced test pressure (Pt) of 19.8 psig as specified in the Technical Specifications.
The purpose of this test was to verify that the measured leakage rate (Ltm) was less than the maximum allowable operational rate of 0.24%/day by weight at the reduced test pressure (Pt).
This report describes and presents the results of this periodic.
Type "A" Leakage Rate Test including the supplemental method utilized for verification.
C
II.
SUMMARY
Type B and C tests were previously performed by Florida Power 6
Light Company station personnel with repairs and corrections made where necessary.
At the start of the Type A test, all valves were to be in their normal position for accident conditions.
Exceptions to this valve line-up were noted during this test and are listed in the official copy of the test procedure which is on file at the St. Lucie station.
The first order least squares fit of the measured total-time data yielded a leakage rate of 0.052%/day with a calculated upper 95% confidence limit leakage rate of 0.057%/day.
The first order least squares fit of the data using the mass point method yielded a
leakage rate of 0.044%/day.
The supplementary Controlled Leak Rate Test (CLRT) results (simple total-time method) verified the measured leakage with'in the allowable acceptance band.
>>2-
III. TEST DISCUSSION A.
Descri tion of Containment The free standing containment vessel is 140' 232' 3/4" high with a cylindrical steel shell 1.903" thick, a 0.95" thick hemispherical dome with a 1.903" thick ellipsoidal bottom and a 2g" thick knuckle.
The vessel is constructed of ASME SA 516 GR 70 carbon steel plate and has a calculated free air volume of 2,500,000 cubic feet.
The structure includes one personnel airlock, one emergency escape lock, one fuel transfer
- tube, one maintenance hatch,and one 28'quipment hatch.
A circular polar crane runway girder and crane rail were designed integrally with the vessel wall.
I The vessel was designed and constructed in accordance with the rules of Section III of ASME symbol for a design internal containment pressure of 39.6 psig at a temperature of 264F..
B.
Descri tion of Instrumentation The containment system was equipped with instrumentation to permit leakage rate determination by the "Absolute Method".
Utilizing this method, the actual mass of dry air within the containment is calculated.
The leakage rate becomes the time rate of change of this value.
The mass of air (Q) is calculated according to the Perfect Gas Law as follows:
~PV = ~P~P)
Pa
= air partial pressure free volume gas constant temperature Pt = total pressure, psia P
= water vapor pressure, psia wv The parameters required are temperature, humidity and pressure.
The temperature and humidity with the exception of temperature sensor 23 were automatically output at 15 minute intervals via a data logger and printer.
The location of the instrumentation is shown in Figures 1 6 2. The pressure readings were recorded every 15 minutes by the da ta acqu isition team.
1.
Te erature Instrumentation The containment was equipped with 40 precision RTD's.
The accuracy of these detectors is within + 0.2 F over the specified 200 F span and + 0.5 F over the remainder.
2.
Humidit Instrumentation, The containment was equipped with 10 RHD's.
The accuracy of these detectors is + 2.5% relative humidity for a 0-100% relative humidity excursion.
3.
Pressure Instrumentation The containment was equipped with 2 precision readout units (1 primary and 1 spare) with a calibration accuracy of 0.15% reading, resolution of 0.002% of full scale and readout of 100,000 counts
= full scale.
The absolute pressure capsule has a range of 0-50 psia.
The computed maximum probable pressure loop error is equivalent to 0.001 psia.
In addition a 120 inch large bore U tube servomanometer was connected to the same sensing line as the two precision readout units as an alternate back-up.
The accuracy of this instrument is + 0.005 inches of mercury.
4.
Numatron Di ital Voltmeter A L6N digital voltmeter (Numatron) was utilized to obtain direct readout of temperature sensor 23.
This instrument has an accuracy of + 0.01 millivolt. In the case of temperature, due to utilization of a resistance bridge circuit, the voltmeter error contributes an additional
+ O.l F.
Consequently, this temperature loop error is equivalent to 0.3 F.
5.
Flow Instrumentation One Wallace and Tiernan rotameter with a range of 0 to 11 scfm and an accuracy of +
1% full scale was used during the supplemental test.
0 J
C.
Descri tion of the Com uter Pro ram The Ebasco ILRT computer program is an interactive Fortran IV program written specifically for fast easy utilization during all phases of the ILRT and CLRT.
Data entry and modifications, if necessary, are readily accomplished by the data acquisition team.
In addition to extensive data verification
- routines, the program calculates on demand, point-to-point, total-time or mass-point leak rates.
The required first order linear regressions corresponding to the last two types of leak rate calculations are also provided as well as the total-time at the upper 95% confidence limit.
Data rejection based on the Chauvenet criterion may be utilized in the analysis.
Both a priori and posteriori instrument error contribution to the leak rate are computed using the standard error approach.
A priori error is based on nominal pretest conditions whereas a posteriori error is based on actual"test conditions.
Data storage and retrieval are enhanced by the flexible display of either sensor values or various computed variables in tabular or graphical form on the computer terminal.
Data are recorded on magnetic tape to prevent loss during the testing.
All data are stored on the computer systems in use with retrieval capability to any desired data base throughout the testing.
Temperature, pressure and humidity data are entered interactively via the computer terminal at 15-minute intervals.
-Care is taken to record correctly and in a timely manner both on the data sheets and within the file system utilized by the program.
Each set of data is verified by the data acquisition team; modifications are promptly made when errors are detected.
Prior to issuance of this report, further extensive data verifi-cation has been performed.
0
The computer-generated reports based on verified data substantiate for both the ILRT and CLRT that a successful test has been completed in accordance with 10 CFR 50, Appendix J.
D.
Error Anal sis Three types of error analyses are performed using the ILRT computer program.
These types are a priori instrument loop error, a posteriori instrument loop error and a statistical confidence interval.
The priori instrument loop error is based on the standard error approach in which individual contributions of the various sensors and display equipment are added to provide the worst p robable error.
The error is computed to a 95% confidence.
Prior to the test, this a priori loop error determines whether the instrumentation system is capable of measuring the required leakage sufficiently accurately such that the error and nominal leakage do not exceed the maximum permissible.
The a posteriori instrument loop error also is based on the standard error approach and is computed to a 95% confidence.
No simplifying assumptions other than constant containment free volume are made in the derivative calculations for parameter sensitivity in the standard error formula.
Instrument loop errors are computed from containment conditions once variable bias has been compensated.
This leakage error due to instrumentation is then reported for both the ILRT and CLRT as the maximum probable instrument loop error.
A statistical confidence interval is generated for the total-time first order regression line of the simple total-time leak rates.
The interval provides a hyperbolic region symmetrically centered about the slope of the mean of the regression line.
The significance of this interval is that further observations of the leak rate should lie within this region 95% of the time.
E.
Descri tion of Tests Interpretation of the final analysis of test data show results well within the specified limits for this containment as delineated in Section V (Conclusions) of this report.
The containment was made ready for the Integrated Leak Rate Test with final inspection and closure completed at 1830 hours0.0212 days <br />0.508 hours <br />0.00303 weeks <br />6.96315e-4 months <br /> on 5/23/79 and pressurization commencing at 1839.
Pressurization was accomplished by utilizing up to ten mobile air compressors with a total capacity of approximately 10,000 scfm.
These units were connected to the containment as shown in Figure 3.
At 1954 on 5/23/79 a gasket for a handhole on No.l chiller dryer started leaking.
The chiller dryer was removed from service along with five of the compressors, reducing the pressurization rate by approximately 50% until 2030, at which time the handhole gasket was replaced and all pressurization equipment was returned to service.
Pressurization of containment was secured at 0255 on 5/24/79 with 21.6 psig pressure in the containment vessel, After an appropriate stabilization period, the apparent leak rate was determine to be
.31%/day or about one and one third times the allowable.
At 1300 the leak survey team detected leakage past check valve I-V07217 on containment spray header "B" and the system was realigned.
At 1410 on 5/24/79 the rotameter pressure gage for P-52 was reading 10 psig.
Investigation by FP&L personnel revealed that its manual containment isolation valve was partially open.
The isolation valve was re-turned to its normally closed position.
While collecting the pressure data samples from 1330 on it was noticed that the pressure decay rate had suddenly increased, investigation by FP&L personnel revealed that an operator had been instructed to close valve V00144 rather than controlled leak rate isolation valve V00143.
The closure of V00144 had isolated the pressure sensors from the containment atmosphere.
This valve had remained close for approximately 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and 20 minutes.
At 1530 on 5/24/79 the valves were placed in their proper configuration, with the official start of the 24-hour ILRT initiated at 1615 hours0.0187 days <br />0.449 hours <br />0.00267 weeks <br />6.145075e-4 months <br /> on 5/24/79.
Trending and analysis of raw data indicated that temperature sensors 5,17 and 30 as well as humidity sensors 1,5,6 and 7 were reading erratic.
These sensors were deleted and the effected sensor volume fractions were updated by the computer such that all calculations did not incorporate the deleted sensor inputs.
The ILRT was successfully completed at 1615 hours0.0187 days <br />0.449 hours <br />0.00267 weeks <br />6.145075e-4 months <br /> on 5/25/79 with a calculated total-time leakage rate of 0.052%/day.
Health Physics sampled the containment air volume prior to initiation of the Controlled Leak Rate Test (CLRT).
The rotameter was adjusted to approximately 9.51 scfm bleedoff flow.
This flow is equal to approximately
.235%/day.
The CLRT commenced at 2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> on 5/25/79 with stable conditions in containment and was satisfactorily completed at 0045 on 5/26/79.
Depressuri-zation of the containment commenced at 0145 on 5/26/79.
The discharge was monitored with"'no gaseous or particulate activity observed.
Following a satisfactory containment air sample, an internal containment inspection was performed at 0840 with the containment at approximately 0.20 psig.
During the containment inspection no anomalies were noted.
Prior to performance of the ILRT, Local Leakage Rate Tests (LLRT) were performed by FP&L personnel'o verify containment integrity.
These Type B and Type C tests were performed on containment electrical penetrations, mechanical penetrations, piping system I
isolation valves which become part of the containment boundary under accident conditions, fuel transfer tube, personnel access lock, emergency lock and equipment hatch.
The acceptance criteria for the LLRT is that the total leakage from these tests shall not exceed 0.60 (La).
The total leakage from these tests was within these limits and the tabulated results are presented in Appendix B.
IV ~
RESULTS AND VERIFICATION The Type A Integrated Leakage Rate Test was conducted for a period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> starting at 35.943 psia with a total of 97 samples or data sets taken.
The results of a computed least squares statistical fit of all data revealed a leakage rate of 0.052%/day with an upper 95/ confidence limit of 0.057/,/day (Total-Time Method),
0.040%%u/day (Total-Time Simple) and 0.044%/day (Mass-Point Method).
The maximum probable instrument loop error for the ILRT was 0.003//day within a computed confidence of 95/..
S ince the least squares statistical fit of the measured data is a function-of test duration, the regression errors during the CLRT are high.
For the purpose of verificaMon of this test, the total-time simple leakage rate shall be utilized due to the CLRT data which are of much shorter duration as compared to the ILRT data.
Following satisfactory completion of the ILRT, a 4'5 hour5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> CLRT was performed.
This test was conducted by superimposing a known leakage rate of approximately 9.5 scfm at 35.827 psia which corresponds to a leakage rate of approximately
.235/ /day.
The measured Simple Total-Time Leak Rate for the CLRT was 0.284%/day. It should be noted that no data samples were rejected in computing the results for the ILRT as well as the CLRT.
10-
V.
CONCLUSIONS The Integrated Leakage Rate Test at Pt (34.5 psia) provided acceptable results as evidenced by the computer printout and graphs in Appendix A of this report.
The measured leak rate is well within the specified limits.
The acceptance criteria for the ILRT is as follows:
1.
The maximum allowable operational leak rate shall not exceed 75% of Lt 0.240%/day at 'a pressure of not less than 34.5 psia.
As reported in Section IV, the measured leakage rate for the containment was 0.052%/day, with an upper 95%
confidence limit of 0.057%/day (Total-Time Method).
The maximum probable instrument loop error is 0.003%/day at a
95% statistical regression confidence interval.
2.
The accuracy of the ILRT shall be verified by a supplemental test where the difference between the containment leakage rate measured during the CLRT and the ILRT is within 0.25 Lt.
As reported in Section IV, the measured verification leakage rate was 0.284%/day (Simple Total-Time), which is well within the acceptance band.
VI. FIGURES
0
0 9pO 0
yQ'I 8
2 32 Q3f s7h
,.~
S6 Zfo',L.le.00'o
/
439 IPp i,II I0
~IG If EL.l2.7.0O'L 200.00'LI74.00'EL 27.00'8 A
I 9 ~sf)
S 3I(m I>
lIOS)
I2(n) 39(<o) 32]35) 3P(3q) 9(lo)
I3(I6)
I4(I5)
~I gO I
yS 3
EL20o.oo'I 20+
~$
7 21 26 gL4o.0a'O 5
I 8
3 z('zz) t) zz(zz) zgzs) zs.
I e) zre v
6 I l8p'L.<0.OO PLANS SECT lON 0
RHb (lo)
~p (go)
REACTOR CONTAINMENT t OCaT~ONS OF eTO sC>> a RHD'sl.o)
INSIDE CONTAINMEHT ouTSIDK co&'N'T Pl'0-9 I-YOOI39(I3H,)
P 526 Z sl~-24 j'=yooIW(e2z l OOISI tI323)
YoOISO(I323)
'/g,-lT-29 PI 00.8 YOOI5Z(ITS)
C0NDEMsA7C
'Pof (TYP.)
SERV0.
HANOI METER YPOI53 {825)
% A~S.
J"VDOIAI (I3Ã)
LLR TEST r-vooIe{I325)
P
'h" QAAIH
$ YbS7 VOOl45{I3K3)
J:I" IT.Z5 x.vool43()325 Pl 00-7 Tl i@5 VOOI4e(I323)
~ YOogS(I32S)
I"IT.23 FI OO-I Fl 00-IS YAA@HETER,
~"x/g." RED.
(TV,.)
XVOOI42 (I324)
LI-R TEST SnS<IC CLPSS I VOOHS(I&2,3)
/z. savH QTEsT VOOl47 {1323)
I-IT-z3 FLOW DIAGRAM tLRT PRESSupE SENs~NG E. CGNTR0LLED LEAKAGE lNsT
TEMP.
PERM.
PI VOOIOS(323)
VOOIO7(323)
PI 5FI,OOIOO(1)
VOOIO'2 (SZ)
PERM.
8'IT 19 8"- IT.ZO 8"-IT 5 TEMP.
TO ATMOS.
(-
~8'- lT-17A INSIDE CONTAINMENT I-8'IT-2I i I CQ VOOIOe(SSZ) 8"-IT-14 AIR VOOI06(632.)
2". IT-ZZ VOO Ill(M.1) 4'5N-5A I
8"- 1T-12A C-VOOIOI(SIZ) 900 KN(324)
SEISMIC CLAS5 I Ifl 1
IO I VOO103 (324) 3/4 DRAIN 4.
LEAK TEST TI 00.
3/4" DRAIN BLEAK TEST TO 3" HOSE ~
DISCHARGE CANAL IA 8"- IT-I I@,
tO PI I
I Tl TI I
51 IJ 4800 SCFFI CHIRR DRYER IA I
~ ~
V00IIZ(323)
PI3 V00113 (3zs) ~
Pl 002 (323) 5-3 I
'15 14 3800 SCFM CHILLER ~
DRYER 15 I
I 4"-5'A I
I I
PI I
5.13 2'5.0 gn ~
VO0120(323) I VOOIIB(323) 3" (TYP.)
Cl
~$
38 I
MECK.
IB VOO114(3n) 5'EPARATOR(TYING)
V00116(325)
I I OeuN (nP)
O N N 8a~
88 6m 4 g'3 4.
8"- IT-8A Qu 38~
I MOISTURE.
I 2-5W-74 TYP.
I AFTERCOOLER I8 O'T. 10A I
M01SmR SEP.
I B 6"-SW-V, U
FROi~f HYDRANT FLOW DIAGRAM ILRT PRESSURIZING 8 DEPRESSURIZING STATION COMP RESSORS IA ak gt
)
VII.
APPENDICES
APPENDIX A. 1 FLORIDA POWER & LIGHT COMPANY ST.
LUCIE NUCLEAR POWER STATION UNIT N0.1 COMPUTER - GENERATED REPORT INTEGRATED LEAK RATE TEST
LEAK RATE COMPUTED USING TOTAL TIME METHOD AS RECOMMENDED BY APPENDIX J FOR 10 CFR 50 (REACTOR CONTAINMENT LEAKAGE TESTING FOR WATER COOLED POWER REACTORS)
TEST PERIOD STARTED AT 1615 HOURS ON MAY 24,1979 A LEAST SQUARES FIRST ORDER FIT OF LEAK RATE TO TIME SHOULD YIELD A SLOPE OF ZERO AND AN INTERCEPT EQUAL TO THE LEAK RATE AS COMPUTED AT THE INITIAL START TIME THE EQUATION HAS THE FORM L=ST+R WHERE L CORRELATED LEAK RATE S SLOPE OF CORRELATION T TIME IN HOURS R INTERCEPT LEAK RATE LEAK RATE MEAN 0-001 HOURS +
0.018 PER CENT 0.035 PER CENT INITIALCONTAINMENT AIR WEIGHT =
437052 LBS.
FINAL CONTAINMENT AIR WEIGHT =
436877 LBS.
FITTED MASS POINT LEAK RATE IS 0.044 PER CENT PER DAY FITTED TOTAL TIME LEAK RATE IS 0.052 PER CENT PER DAY SIMPLE TOTAL TIME LEAK RATE IS 0.040 PER CENT PER DAY TOTAL TIME LEAK RATE AT UPPER 95so CONFIDENCE LIMIT IS 0.0579$
PER DAY MAXIMUM NRC LEAK RATE OF 0.240 PER CENT PER DAY GIVEN FOR LOW PRESSURE TEST AT 35.94 PSIA MAXIMUM PROBABLE TEMPERATURE LOOP ERROR IS 0.008 DEGREES F.
MAXIMUM PROBABLE PRESSURE LOOP ERROR IS 0.0005 PSIA.
MAXIMUM PROBABLE HUMIDITY LOOP ERROR IS 0.044 PERCENT."
MAXIMUM PROBABLE INSTRUMENT ERROR IS 0.0030 PERCENT PER DAY WITHIN A COMPUTED CONFIDENCE OF 95.00 PERCENT
'e
17-33
~
65
~
81
~
113.
a.sooo CONPUTEQ LERK RRTES RELRTIVE TO LIMITS 0.8000 0.0000
-0.8000 xxxxxxxxxx x
x STATISTICAL TOTAL LEAK RATE CONTAINMENT DESIGN LEAK RATE NRC TECHNICAL SPECIFICATION LIHIT tNSTRUl'ENT ERROR LIl'IT REDU" ION v
v COMPUTED FIRST ORDER EQUATION CI 5
4 I
~i M
~.
5 CI hl SS lsJ O
CI
-1.6000 xx
=2.4000 0
240 480.
720.
960.
1200.
a44o.
a68o.
TINE IN N I NUTES
EBRSCO SERVICES INCORPORRTED 17'3
~
49 6S
~
81'7'13
'.3400 COMPUTED FIT RELRTIVE TQ CRITICRL LINIT x
x SIMPLE TOTRL TINE LEAK RRTE INSTRUMENT ERROR LIHIT REDUCTION v
v COMPUTED FIRST ORDER EOURTIOH OREEN OCTROON STAT IST I CRL REJECTION 0.2600 0.1800 0.1000 0.0200 x x x
x X~XXX" xx Xx X
x
-0.0600 0
240 480.
720.
960.
1200.
1440.
1680 T INE IN NINUTES
17-33 S
~
81 13.
0.41OO CONPlJTED LERK RATE F IT RELRT I,VE TO LIMNITS CONTRIHHEHT DESIGN LERK RATE NRC TECHNICRL SPECIFICATION LIHIT INSTRUMENT ERROR L It')IT REDUCTION v
COMPUTED FIRST ORDER EQUATION cn 0-CCn 0.3300 0.2600 5
~t Isl a
4 0.1700 Eh IC Ch 0.0900 0.0100 240.
480.
720-960.
1200.
1440.
1680 T I ME IN MINUTES
e
7
~
9
~
7
~
13
~
36.0000 RVERRDE t"ONTRINNENT PRESSURE 35.9600 35
~ 9200 35.8800 35.8400 35.8000 0
240.
480.
720.
960 1200.
1440.
1680.
TINE IN MINUTES
3
~
EBRSCO SERVICES INCORPORRTEO 7
~
9
~
5
~
7
~
13
~
I UJ QJ CL U
I V3 UJ UJ cb LtJ C3 89.6000 89.2000 88.8000 88.4000 VOLUNETRI CRLLY HEI BHTED CONTR INNENT TEHPERRTURE UJ l
CC UJ CL QJI 88.0000 87.6000 0
240.
480.
720 960.
1200.
1440.
1680.
TIME IN MINUTES
EBASCO SERYICES INCDRPORATEO 7
~
3
~
9
~
5
~
7 0
13
~
0.4006 YOLUNETRIL'RLLY NE I DHTED YRPOR PRESSURE 0.4000 0.3996 0 3990 0.3986 W
W X
g gled NP N
NW N
0.3980 0
240.
480.
720.
960.
1200.
1440.
1680.
DESCRIPTION OF VARIABLES AVG.
TEM VOLUMETRICALLYWEIGHTED TEMPERATURE.
AVG.
PRE AVERAGE PRESSURE.
VAP-PRE VOLUMETRICALLYWEIGHTED VAPOUR PRESSURE.
LEAK COM LEAK RATE COMPUTED FROM FIRST ORDER REGRESSION.
LEAK SIM - LEAK RATE BASED ON TOTAL TIME CALCULATIONS.
LEAK MAS LEAK RATE FROM MASS POINT FIRST ORDER REGRESSION.
NOTE FOR TABULAR DATA TABLE VALUES OF ZERO SIGNIFY EITHER 3..
DATA IS NOT APPLICABLE TO THE CALCULATION OR 2.
SENSOR HAS BEEN DELETED FROM THE SCAN.
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 21
. 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 AVG. TEM DEG.
F 89.050 89.025 88.995 88.966 88.933 88.903 88.887 88-864 88.838 88.813 88 '88 88-765 88.749 88.725 88-702 88.676 88-663 88-641 88.622 88-604 88.583 88.565 88.548 88.529 88.510 88.497 88.475 88.464 88-443 88.427 88.417 88.397 88-383 88.370 88.359 88.348 88.330 88.324 88.306 88.292 88.283 88.268 88.254 88.241 88.232 88.218 88.211 88.196 88.193 88.173 PSIA 35.943 35.941 35.939 35.938 35-936 35.934 35.932 35.930 35.928 35.927 35.925 35.923 35.922 35.920 35.918 35.916 35.914 35.914 35.912 35-911 35.909 35.908 35-906 35.905 35.904 35.903 35.902 35-900 35-899 35-898 35-896 35.895 35.895 35-894 35-893 35-891 35.890 35.888 35.888 35.888 35.886 35.885 35.884 35.883 35.882 35.881 35-880 35.879 35-878 35.877 PSIA 0-400 0.400 0.400 0.400 0.399 0.399 0.399 0-399 0.399 0.399 0-399 0.399 0-399 0.399 0-399 0.399 0.399 0.399 0.399 0.399 0.399 0-399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0'98 0-398 0.398 0-398 0.399 0-398 0.399 0.399 0.399 0.399 0-399 0.399 0-398 0.399 0.398 0.399 0.398 0.399 0.399 0.399 0.399 AVG.
PRE VAP.
PRE LEAK COM PER CENT 0-018 0-018 0.019 0.019 0-019 0.020 0-020 0.021 0-021 0.021 0.022 0-022 0.022 0.023 0.023 0-023 0.024 0.024 0-024 0-025 0.025 0.026 0-026 0.026 0 027 0-027 0.027 0.028 0-028 0.028 0-029 0.029 0.030 0.030 0.030 0.031 0.031 0.031 0.032 0.032 0.032 0.033 0-033 0.033 0-034 0.034 0.035 0.035 0.035 0.036 LEAK SIM PER CENT 0.000 0.005 0.001
-0.040 058
-0.048 0.005 0.018 0.032 0.012
- 0. 003
- 0. 010
~ 0-021 0.028 0.034 0.028 0.046 0.041 0.039 0.036 0.037 0.040 0.041 0.039 0-039 0.037 0.032 0.042 0.036 0.033 0.039 0.035 0.034
- 0. 035 0.035 0.041 0.039 0.050 0.039 0.036 0.041 0.039 0.039 0.038 0.040 0.040 0.042 0.043 0.046 0.043 LEAK MAS PER CENT 0.000 0.000 0.001
-0.036
-0.059
-0.058 023 0.002 0.022 0.023 0.019 0.019 0.023 0.028 0.033 0.035 0.042 0.045 0-047 0.047 0.047 0-048 0.049 0-049 0.049 0.049 0.047 0.048 0.047 0.046 0.046 0.045 0.044 0.044 0.043 0.044 0.044 0.046 0.045 0.045 0.045 0.045 0.045 0.045
- 0. 045.
0.045 0.045 0.045 0.046 0.046
VARIABLE TABLE
SUMMARY
(CONTINUED)
SAMPLE NUMBER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 DELTA MINS 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 AVG.
TEM DEG.
F 88.163 88.152 88.141 88.130 88.121 88.108 88.097 88.087 88-077 88.067 88.058 88.047 88.041 88.030 88.022 88.010 88.001 87.992 87.974 87.961 87.952 87.941 87.928 87.917 87.906 87-896 87.884 87-875 87.862 87-851 87-846 87-833 87.809 87-801 87.798 87.783 87.777 87.764 87.750 87.742 87.725 87 '17 87.708 87.700 87.692 87.680 87.670 PSIA PSIA PER CENT 35 '76 35.876 35 '75 35.874 35.873 35.872 35.872 35-871 35 '70 35.869 35.868 35.867 35 '66 35.865 35.864 35.864 35.863 35-862 35-861 35-860 35.859 35-859 35-858 35-857 35 '56 35-856 35.855 35 '54 35.853 35 '53 35.852 35.851 35.850 35.849 35.848 35.848 35-847 35.846 35-845 35;844 35-844 35.843 35.842 35-841 35.840 35.840 35.839 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399
'0. 399 0.399 0.399 0.399 0.399 0-399 0.399 0-399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0.399 0-399 0.399 0.399 0.399
'0. 399 0.036 0.036 0.037 0.037 0.037 0.038 0.038 0.038 0.039 0.039 0.040 0.040 0.040 0.041 0.041 0.041 0.042 0.042 0.042 0.043 0.043 0.043 0.044 0.044 0.045 0.045 0.045 0.046 0.046 0.046 0.047 0.047 0.047 0.048 0.048 0.049 0.049 0.049 0.050 0.050 0.050 0.051 0.051 0.051 0.052 0.052 0.052 AVG-- PRE VAP.
PRE LEAK COM LEAK SIM PER CENT 0.044 0.042 0.043 0.043 0.044 0.044 0.042 0-043 0.043 0-045 0.046 0.046 0.047 0.'047 0.050 0.047 0.048 0-048 0.045 0.035 0.045 0.044 0.043 0.041 0.043 0.043 0.043 0.042 0.042 0.042 0 '44 0.042 0.038 0.039 0.042 0-040 0.042 0.042 0.040 0 '41 0.039 0.040 0 '40 0.040 0.041 0.039 0.040 LEAK MAS PER CENT 0.046 0.046 0.046 0.046 0.047 0-047 0.047 0.047 0.047 0.047 0.047 0 '48 0 '48 0.048 0.049 0.049 0.049 0.049 0.049 0.049 0.049 0.049 0.048 0-048 0-048 0-048 0-048 0-048 0.047 0-047 0.047 0.047 0.047 0.046 0.046 0.046 0.046 0.046 0.045 0.045 0.045 0.045 0.045 0.044 0.044 0.044 0.044 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 21 22 23
'4 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 DELTA MENS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 TEMP 1
DEG.
F 85.061 85.088 85.116 85.061 85-088 85.088, 85.061 85.116 85.088 85.088 85.061 85.034 85.034 85.034 85.034 85.034 85.007 85.007 85.034 85.034 85.007 85.034 85.007 85.007 85.007 85.034 85.007 85.007 85.007 85.007 85.007 85.007 85.007 84.980 84.980 84.980 85.007 84.980 84.980 85.034 84.980 84.980 84.952 84.952 84.980 84.980 84.980 84.952 84.952 84.952 86.395 86.395 86.367 86.367 86.367 86-367 86.367 86.340 86.313 86.286 86.286 86.286 86.259 86.259 86.231 86.231 86.204 86.204 86.231 86.177 86.177 86-177 86.150 86.122 86 '77 86.177 86.122 86.150 86.122 86.095 86.095 86.122 86.095 86.068 86.068 86.095 86.041 86.041 86.041 86.041 86-068 86.041 86.014 86.014 86.014 85.986 85.986
'85.986 85.986 86.014 85.469 85.469 85.469 85.442 85.415 85.442 85.442 85.442 85.415 85.442 85.469 85.442 85.415 85.415 85.415 85.388 85.388 85.361 85-361 85.415 85-388 85.361 85.388 85.361 85-361 85.333 85.361 85.361 85.361 85.333 85.361 85.388 85.333 85.361 85.361 85.361 85.361 85.361 85.333 85.333 85.333 85.306 85-306 85.306 85.306 85.306 85.306 85.306 85.333 85.306 TEMP 2
TEMP 3
DEG.
F DEG.
F 86.041 86.014 86.014 85.959 86.014 86.014 86.014 85.959 85.986 85.959 85.959 85.959 85.986 85.959 85.959 85.959 85.905 85.932 85.932 85.905 85.932 85.905 85.932 85.905 85.905 85.932 85.905 85.905 85.878 85.905 85.905 85.878 85.905 85.878 85.878 85.905 85.878 85.905 85.878 85.878 85.878 85.878 85.878 85.905 85.878 85.905 85.878 85.850 85.850 85.850 0.000 0.000 0-000 0.000 0.000 0.000.
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 F 000 0-000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 TEMP 4
TEMP 5
DEG.
F DEG.
F TEMP 6
DEG.
F 85-007 85.007 85.007 85.034 85.007 84.980 85.007 85-007 84.980 84-980 84.980 85.007 84.980 85 007 84.980 84.925 84-952 84.952 84.952 84.980 84.952 84.925 84-980 84-952 84.925 84-980 84.925 84.952 84.952 84.925 84.925 84.925 84-952 84.898 84-925 84.925 84.952 84.952 84 '25 84-925 84.925 84.925 84.898 84.925 84.898 84.925 84.871 84.898 84.898 84-871
SAMPLE NUMBER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84
'85 86 87 88 89 90 91 92 93 94 95 96 97 DELTA MINS 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 84.952 84.925 84.980 84.925 84.952 84.952 84.952 84.925 84.952 84.952 84.925 84.952 84.871 84.925 84.871 84.925 84.925 84.952 84.925 84.871 84.898 84.925 84.925 84.871 84.871 84.898 84.871 84.871 84.898 84.898 84.898 84.871 84.925 84.898 84.844 84.898 84.898 84.898 84.871 84.871 84.871 84.898 84.871 84.898 84.898 84-871 84.925 85.959 85.986 85.986 85.959 85.986 85.959 85.959 85.932 85.959 85.959 85.878 85.932 85.905 85.905 85.878 85.905 85.905 85.905 85.878 85.850 85.878 85.878 85.905 85.823 85.823 85.850 85.850 85.850 85.823 85-850 85.823 85.823 85-796 85.823 85.823 85-796 85.823 85.823 85.796 85.796 85.769 85.769 85.769 85-796 85.796 85.769 85.769 VARIABLE TEMP 1
TEMP 2
DEG.
F DEG.
F TABLE
SUMMARY
(CONTINUED) 85.306 85-306 85.279 85.279 85.279 85.279 85.306 85.279 85-279 85.279 85.279 85.279 85.306 85.306 85.252 85.252 85.225 85.252 85.252 85.225 85.225 85.252 85.225 85.252 85.225 85.225 85-197 85.225 85.225 85.225 85.225 85.252 85 '25 85.197 85.225 85.197 85.197 85.225 85.225 85.225 85.197 85.225 85.197 85.197 85.225 85.197 85.197 85.850 85.850 85.850 85-850 85.823 85-850 85-850 85.850 85.823 85.823 85.850 85.823 85-850 85.823 85.850 85.823 85-796 85.823 85-823 85.823 85-796 85.796 85.796 85.796 85.769 85-796 85.796 85.769 85-796 85-769 85-769 85.796 85.796 85-769 85-796 85.769 85-769 85.769 85.769 85.796 85.742 85.742 85.796 85.769 85.796 85.769 85.769 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000, 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TEMP 3
TEMP 4
TEMP 5
DEG.
F DEG.
F DEG.
F TEMP 6
DEG ~
F 84.871 84.898 84.844 84-898 84.898 84.898 84.898 84.952 84-925 84.898 84.898 84-898 84.871 84-871 84.871 84.844 84-844 84.816 84-844 84.844 84-871 84.844 84.844 84.844 84.844 84.816 84.871 84.871 84.816 84.844 84.898
'84.898 84.871 84.844 84-844 84.844 84.844 84 844 84-844 84-816 84.844 84-816 84-844 84-816 84-816 84 871 84-816 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE DELTA TEMP 7
TEMP 8
TEMP 9
TEMP 10 TEMP 11 TEMP 12 NUMBER MINS DEG.
F DEG.
F DEG.
F DEG.
F DEG.
F
-DEG.
F 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 85.578 85.605 85.605 85.578 85.605 85.578 85.551 85-578 85-551 85.551 85.578 85-551 85.551 85.524 85-551 85.524 85.524 85.524 85 '24 85.497 85.497 85.524 85.469 85.497 85.497 85.497 85.469 85.497 85.469 85.497 85.469 85.469 85.469 85.497 85.497 85.469 85-469 85 '97 85.497
'85.469 85.469 85.469 85.497 85-469 85-469 85.442 85.469 85.442 85.469 85.442 85.061 85.061 85.061 85.034 85.034 85.007 85.034 85-034 85.007 85.034 85.007 85.007 84-980 84-980 85.007 84.980 84.980 84.952 84.925 84.925 84.952 84.925 84.925 84.898 84.925 84.952 84.898 84-952 84.898 84.898 84.925 84.898 84.925 84.898 84 898 84-898 84.898 84.898 84-871 84.898 84.871 84.898 84.898 84.871 84.871 84.844 84.898 84-844 84.844 84.871 89-616 89.562 89.534 89.479 89.425 89.425 89.370 89.342 89.288 89.288 89.233 89-206 89-151 89.151 89.123 89.096 89-069 89.014 89-014 88-986 88-986 88.932 88.932 88.849 88.849 88-849 88-822 88.822 88.740 88.712 88.712 88.685 88.712 88.685
-88 '58 88.630 88-603 88-603 88.575 88-548 88.548 88.493 88.466 88.466 88-466 88.493 88.438 88.438 88.411 88-356 89.260
>> 89.178 89.123 89.123 89.069 89.041 89.014 88.986
'88.959 88.932 88.877 88.849 88.795 88.795 88.767 88.712 88.685 88.685 88.630 88.603 88.603 88.575 88.548 88-521 88.521 88.466 88.438 88.411 88.384 88.384 88.329 88.329 88.301 88-274 88.274 88.247 88.247 88.247 88.219 88.192 88.164 88.137 88.110 88.110 88.082 88.055 88.082 88.055 88-027 88.000 89.260 89.178 89.178 89.123 89-096 89.041 89.041 88-986 88.959 88.932 88.904 88.877 88-877 88.795 88.740 88.767 88,-740 88.712 88.685 88.685 88.658 88.603 88-603 88.548 88.521 88.493 88-466 88.438 88-'438 88.438 88.384 88-356 88.329 88-356 88.329 88-301 88-301 88.274 88.247 88.219 88.219 88;192 88.219 88.192 88.137 88.137 88.110 88.137 88-110 88.082 89 '07 89.452 89.452 89.342 89.342 89.288 89.288 89.260 89.233 89.178 89.151 89.096 89.096 89.041 89.041 88.986 88-959 88.904 88.932 88.877 88.849 88.822 88.795 88.795 88-767 88-740 88.712 88.712 88.712 88.630 88.630 88.603 88.575 88-548 88.548 88.575 88-521 88.548 88.493 88-466 88.438 88.438 88.411 88.384 88.356 88.356 88-356 88.329 88.301 88-301
VARIABLE TABLE
SUMMARY
(CONTINUED) 51 52" 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88.
89 90 91 92 93 94 95 96 97 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 SAMPLE DELTA NUMBER MINS TEMP 7
DEG.
F 85.469 85.469 85.415 85.442 85-415 85.442 85.415 85.415 85.415 85.415 85.415 85.415 85.415 85-415 85.388 85-361 85-388 85-388 85.388 85.388 85-361 85.361 85.361 85.361 85.361 85.388 85.361 85.361 85.388 85.361 85.333 85.388 85.333 85.361 85.333 85.361 85.361 85.333 85.333 85.361 85.361 85.333 85.361 85.361 85.361 85.333 85-333 84.871 84.871 84.844 84 '44 84.844 84.816 84.816 84.816 84-816 84-816 84-844 84.816 84.816 84.816 84.789 84-816 84.789 84.789 84-789 84.789 84.789 84.789 84-816 84-789 84.789 84-816 84-789 84-789
- 84. 762 84.762 84.789 84.816 84.735 84.762 84.762 84.762 84.762 84.762 84.762 84.789 84.762 84-762 84.762 84.762 84.762 84.762 84-789 88.356 88.329 88.301 88.301 88.301 88-274 88.274 88.247 88.247 88.192 88-219 88.164 88.137 88.164 88.137 88.137 88-110 88.082 88-082 88-082 88-027 88-055 88-027 88-000 88-000 87-973 87-973 87-946 87-946 87.964 87-891 87.891 87-891 87-864 87.837 87.837 87-782 87.782 87.755 87.755 87.728 87.728 87.701 87 '01 87.674 87-646 87.646.
TEMP 8
TEMP 9
DEG.
F DEG.
F TEMP 10 DEG.
F 88-000 87.973 87-973 87.918 87.891 87-891 87.891 87.891 87.864 87 '64 87.864 87.837 87.810 87-810 87-782 87-755 87-755 87.701 87.701 87.701 87-701 87.674 87.619 87.619 87-592 87.619 87.592 87.565 87.565 87.537 87.510 87.510 87.483 87.456 87.456 87.456 87.429 87-401 87.401 87.401 87.374 87.347 87.347 87.293 87-320 87.320 87.293 TEMP 11 DEG.
F 88-082 88.055 88.000 88.000 88.000 88.000 87.946 87.946 87.946 87.946 87.918 87.891 87.864 87.864 87.864 87.810 87-810 87.810 87.810 87-755 87.755 87.755 87.728 87.701 87.701 87.674 87.646 87.619 87.619 87.619 87.619 87.592 87.592 87.592 87.565 87.537 87.510 87.510 87.483 87.456 87.456 87.429 87.401 87.401 87.401 87-401 87.374 TEMP 12 DEG.
F 88.274 88.274 88.247 88.219 88.219 88.192 88.164 88.164 88.137 88.164 88.137 88.082 88.110 88.055 88.027
'8.027 88.000 88.000 88.000 88.000 87.973 87.946 87.973 87.946 87.918 87 '46 87.891 87.891 87.864 87.864 87.837 87.810 87.810 87.782 87.810 87.782 87.755 87.728 87.701 87.701 87.674 87.646 87.646 87.674 87 '92 87.619 87.592 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER DELTA TEMP 13 MINS DEG ~
F TEMP 14 DEG.
F TEMP 15 DEG.
F TEMP 16 DEG.
F TEMP 17 TEMP 18 DEG.
F DEG.
F 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 r18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600
- 615, 630 645 660 675 690 705 720 735 89.479 89.452 89.397 89.397 89.370 89.342 89.288 89.260 89.206 89.178 89.151 89-096 89.123 89-096 89.069 89.014 88.959 88-986 88-904 88.877 88-849 88.849 88-849 88.822 88.767 88.740 88-740 88.712 88.685 88.658 88.658 88.603 88.603 88-548 88 '75 88-575 88-521 88.493 88.493 88-466 88-438 88-438 88-466 88.411 88.411 88.384 88.384 88.356 88.356 88.301 89-726 89.671 89.616 89.589 89.589 89.562 89.534 89.452 89.452 89.425 89.397 89.370 89.342 89.342 89.288 89-233 89.260 89.233 89.178 89-123 89.123 89.096 89.096 89.096 89.014 89.014 88.959 88.959 88.932 88.959 88.932 88.904 88.877 88.849 88 849 88.849 88.822 88-795 88-795 88.740 88-767 88-740 88.712 88.685 88.685 88.658 88 630 88-630 88.603 88.603 89.425 89.342 89.315 89.260 89.233 89.178 89.178 89.151 89.069 89.041 88.986 88.986 88.932 88.877 88.877 88.849 88.822 88.795 88.767 88.767 88.712 88.685 88.685 88.630 88.603 88-575 88-575 88.548 88-521 88.521 88.466 88.466 88.411 88.438 88-384 88.384 88.356 88.356 88.329 88.301 88.274 88-274 88.274 88.219 88.219 88.219 88-219 88-164 88.164 88.137 91-233 91.178 91.178 91.151 91.069 91.041 91.014 90.986 90.932 90.904 90.877 90.822 90.795 90.795 90-767 90.740 90.740 90.740 90.712 90.658 90.603 90.603 90-603 90-548 90-548 90-521 90.493 90.438 90.438 90.411 90.438 90.356 90.356 90.329 90.329 90.301 90.274 90.247 90.274 90.247 90.247 90.192 90.164 90.164 90.137 90-110 90.110 90-082 90.082 90.055 0.000'.000 0.000 0.000 0.000 0.000 0 F 000 0.000 0.000 0-000 0.000 0-000 0.000 0-000 0.000 0.000 0.000 0.000 0-000 0.000 0-000 0.000 0-000 0-000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0 F 000 0.000 0.000 0.000 0-000 0-000 0-000 0.000 0-000 0-000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0-000 0.000 89.644 89.589 89.589 89.562 89.479 89.479 89.425 89.397 89.397 89.342 89 '42 89.288 89.233 89.206 89.178 89.151 89.123 89.096 89.069 89.069 89.041 89.014 88.959 88.986 88.959 88.932 88.877 88.904 88.849 88.822 88.795 88-822 88.767 88.767 88.740 88.712 88.685 88.685 88.630 88.630 88.630 88.603 88.575 88.575 88.575 88.548 88.521 88.521 88.521 88.493
VARIABLE SAMPLE DELTA TEMP
'13 TEMP 14 NUMBER MINS 'EG.
F DEG.
F TABLE
SUMMARY
(CONTINUED)
TEMP 15 DEG.'
TEMP 16 DEG.
F TEMP 17 TEMP 18 DEG.
F DEG.
F 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 88.301 88.329 88.247 88.247 88.219 88.219 88.192 88.219 88.192 88.164 88.164 88.164 88.137 88.110 88.082 88.055 88.055 88-055 88.027 88-027 88.027 88.000 87.946 87.973 87.973 87.973 87.918 87.946 87.891 87.864 87.891 87.864 87.837 87.837 87.810 87.782 87.810 87.782 87.782 87.782 87.728 87.728 87.701 87..674 87.674 87.646 87.619 88.603 88.548 88.548 88.575 88.521 88-521 88.466 88.466 88.493 88.466 88.438 88.411 88.438 88.384 88.356 88.356 88-356 88-356 88-329 88.301 88.301 88.301 88-274 88 247 88-247 88-247 88.219 88.192 88.192 88.164 88.164 88.110 88.082 88.082 88.082 88.027 88.027 87.973 88.000 87.973 87.973 87-973 87.946 87-946 87.946 87.946 87.891 88.110 88.110 88.110 88.055 88.055 88-055 88.027 88.000 87.973 87.973 87.946 87-946 87-918 87-918 87.918 87-864 87-891 87-837 87-810 87-810 87.810 87.755 87.782 87-782 87.755 87-728 87-701 87.701 87.674 87.646 87.674 87.619 87.592 87.619 87.592 87.565 87.592 87.537 87.510 87-510 87.510 87-483 87.456 87.456 87-401 87.401 87.401 90.027 90.000 90.027 90.000 89.973 89.973 89.918 89.918 89.918 89.890 89.890 89.863 89.863 89.836 89.836 89.808 89.808 89.808 89-753 89.753 89-753 89.726 89-699 89.699 89 '26 89.671 89-671 89.644 89.644 89-616 89-616 89.589 89.562 89.507 89.534 89.507 89.507 89.479 89.479 89.425 89.452 89.425 89.397 89.370 89.397 89.342 89.370 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 "0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 88.438 88.411 88.411 88.411 88.411 88.356 88.356 88.356 88.301 88.329 88.301 88.301 88.274 88.247 88.247 88.219 88.192 88.192 88.164 88.164 88.164 88.164 88.137 88.110 88.082 88.082 88.055 88.027 88.027 88.027 87.973 87.973 87.973 87.946 87.973 87.946 87.891 87.891 87.891 87.864 87.864 87.837 87.810 87.810 87.782 87.755 87.755 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER DELTA TEMP 19 TEMP 20 TEMP 21 MINS DEG.
F DEG.
F DEG.
F TEMP '22 DEG.
F TEMP 23 DEG.
F TEMP 24 DEG.
F 1
2 3
5 6
7 8
9 10ll 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390'05 420 435 45'0 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 89.452 89.370 89.370 89.370 89.288 89.260 89.260 89.206 89.178 89.178 89.123 89.096 89.069 89.041 89.041 89.014 88.986 88.986 88.959 88.932 88.877 88.849 88.822 88.822 88.795 88.795 88.767 88.740 88.740 88-685 88-685 88.658 88-630 88.658 88.603 88.603 88.603 88,575 88.575 88.521 88.521 88.493 88-466 88.466 88.438 88.438 88.438 88.411 88.411 88.356 89.206 89.178 89.151 89-178 89-069 89.041 89.041 88.986 88.986 88.932 88.959 88.904 88.877 88.822 88.822 88.822 88.795 88.795 88.740 88.740 88.712 88.658 88.630 88.658 88-658 88-630 88.575 88.548 88.521 88.521 88.493 88.493 88.521 88.466 88-466 88.438 88.411 88.384 88.384 88.356'8.329 88.329 88.301 88.274 88.301 88.274 88.219 88.247 88.247 88.247 87.565 87.565 87.537 87.483 87.456 87.401 87.374 87.320 87.320 87'.320 87.293 87.265 87.211 87.184 87.157 87.102 87.102 87.075 87.048 87.020 86.966 86.939 86.939 86.912 86-884 86.857 86.857 86-803 86.776 86.748 86.748 86.721 86.694 86-667 86.667 86.639 86.639 86.585 86.558 86.558 86.585 86.531 86.476 86.503 86-449 86.449 86.476 86.449 86.422 86.367 87.891 87.837 87.782 87.755 87.728 87.701 87.701 87.674 87.592 87.565 87.537 87.483 87.483 87-456 87.429 87.401 87.374 87.320
'87.320 87.293 87.238 87.211
,87.184 87.184 87.157 87.129 87.102 87.075 87.048 87.020 86.993 86.993 86.966 86.939 86.884 86.884 86.857 86.857 86.830 86-776 86.748 86.776 86.748 86 '94 86.694 86.667 86.639 86-612 86.639 86.585 87.810 87.728 87.728 87.701 87.701 87.619 87.619 87 '19 87.592 87.537 87.565 87.456 87.456 87.456 87.401 87.374 87.347 87.293 87.293 87 '93 87.238 87.211 87.184 87.184 87.184 87.102 87.102 87-075 87.048 87.020 87.020 86.993 86.993 86.939 86.939 86.912 86.884 86.884 86-830 86.830 86.803 86.776
- 86. 748 86.776 86.748 86.748 86-694 86.694 86-667 86.639 88.384 88.329 88.301 88.274 88.247 88.219 88.192 88.164 88.164 88.110 88.082 88.055 88.082 88.000 87.973 87.973 87.946 87.918 87.891 87.864 87.837 87.837 87.782 87.782 87.728
- 87.728 87.674 87.674 87.646 87.592 87.592 87.592 87.537 87.537 87.537 87.483 87.456 87.456 87.429 87.401 87.374 87.374 87.347 87.320 87.320 87.293 87.265 87.265 87.238 87.211
VARIABLE TABLE
SUMMARY
(CONTINUED)
SAMPLE NUMBER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 DELTA MINS 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050.
1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 88.356 88.356 88.329 88.329 88.301 88.301 88.247 88.274 88.219 88.219 88.219 88.192 88.164 88.164 88.164 88.164 88.137 88.110 88.110 88.110 88.082 88.082 88.055 88.055 88.027 88.000 88.027 87.973 88.000 87.973 87.946 87 '46 87.918 87.918 87.891 87.918 87.891 87-864 87.837 87.837 87.837 87.810 87.782 87.782 87.782 87.728 87.728 88.192 88.164 88.164 88.137 88.137, 88.137 88.110 88.082 88.055 88.055 88.000 88.000 88.000 87.946 87.973 87.946 87.918 87.891 87.891 87.918 87.864 87.891 87.864 87-837 87.837 87.782 87.810 87.782 87.810 87.755 87.755 87.755 87.728 87.701 87.701 87.701 87.701 87-674 87-646 87.646 87.646 87.619 87.619 87.592 87.592 87.592 87.565 86.367 86.340 86.340 86-340 86.313 86.259 86.286 86.259 86.204 86.204 86.204 86.204 86.204 86.150 86.150 86.095 86.095 86.068 86.095 86.041 86-068 85.986 86.014 86.014 85.959 85.986 85.959 85.959 85.932 85.905 85.905 85.850 85-850 85.850 85.823 85.796 85-796 85-769 85.742 85-742 85.714 85-714 85.687 85.687 85.660 85.633 85.633 END OF TABLE TEMP 19 TEMP 20 TEMP 21 DEG.
F DEG.
F DEG.
F TEMP 22 DEG.
F 86.558 86.558 86-558 86.531 86;503
- 86. 449
- 86. 449
- 86. 449
- 86. 449
- 86. 422
- 86. 422 86.395 86.367 86.340 86.313 86.313 86.259 86.259 86.259 86.204 86.204 86"-204 86.177 86.150 86.122 86.122 86.095 86.095 86-068 86.041 86.068 85-986 85.959 85.959 85.932 85.905 85.905 85.878 85.850 85-850 85.796 85.823 85-796 85.742 85-769 85.742 85.687 TEMP 23 DEG.
F 86.639 86.612 86.585 86-585 86.585 86.531 86.531 86.503 86.503 86.476 86.476 86-449 86.449 86-395 86.395 86-367 86.367 86.340 86.313 86.313 86.286 86.259 86-231 86.231 86.204 86-204 86.204 86-204 86.150 86-150
'86-150 86.095 86.095 86-068 86.068 86.041 86 '68 86.014 85.986 85.986 85.959 85.932 85.932 85-905 85.905 85.878 85.878 TEMP 24 DEG.
F 87.211 87.184 87.184 87.157 87.129 87.102 87.102 87.075 87.020 87.020 87.020 86.993 86.966 86.966 86.966 86.939 86.939 86-912 86.857 86-857 86.830 86.830 86.776 86.721 86.748 86.776 86.721 86.667 86.667 86.639 86.667 86.612 86.558 86.531 86.531 86-503 86.476 86.476 86 '49 86.449 86.422 86.395 86.367 86.367 86.340 86.340 86-286
VARIABLE TABLE
SUMMARY
SAMPLE DELTA TEMP 25 TEMP 26 TEMP 27 NUMBER MINS DEG.
F DEG.
F DEG.
F TEMP 28 DEG.
F TEMP 29 DEG.
F TEMP 30 DEG.
F 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44.
45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 89.490 89.460 89.420 89.400 89.360 89.330 89.330 89.280 89.250 89.220 89.190 89.160 89.130 89.110 89.080 89.050 89.020 89.000 88.980 88.950 88.930 88.900'8.880 88-860 88-840 88-810 88.800 88-780 88.760 88.740 88.720 88.700 88.680 88.660 88.650 88.640 88.620 88.600 88.590 88-580 88.560 88.550 88.530 88.520 88.500 88.480 88-470 88-460 88.450 88.430 89.452 89.452 89.370 89.342 89.288 89.260 89.233 89.178 89.178 89.178 89.096 89.096 89.069 89.069 88.986 88.986 88.986 88.959 88.904 88.904 88.904 88.877 88.822 88.822 88.767 88.712 88.712 88-685 88.685 88.685 88-658 88.575 88.603 88-603 88.521 88.548 88.493 88.521 88.466 88.466 88.466 88.438 88.411 88.411 88.384 88.356 88.384 88.384 88.329 88.329 89.452 89.507 89.425 89.425 89.370 89.288 89.260 89.288 89-206 89-206 89 178 89.151 89.151 89-096 89.069 89.041 89.069 89.041 88.959 88.986 88.959 88.959 88.904 88.877 88.822 88.822 88.767 88.767 88.767 88.712 88.712 88-685 88.658 88.658 88.630 88-603 88.575 88-603 88-548 88.521 88-521 88-493 88.493 88.493 88-466 88.411 88.438 88.384 88.438 88.438 89.342 89.370 89.288 89.288 89-206 89.206 89.151 89.123 89.123 89.123 89.014 89-041 89.014 89.014 88.959 88.932 88.932 88.932 88.877 88.849 88.877 88.822 88.822 88.795 88.712 88.740 88.712 88.685 88-658 88-630 88.603 88-603 88.575 88.548 88-521 88.493 88.493 88.493 88.466 88.438 88.438 88.411.88-411 88.384 88.384 88.384 88.384 88.329 88.356 88.329 90.027 90.000 89.945 89.890 89.808 89.726 89.753 89.699 89.671 89.616 89.562 89.562 89.562 89.534 89.479 89.425 89.397 89.425 89.370 89.342 89.315 89.288 89.233 89.233 89-178 89.178 89.151 89;123 89-096 89.096 89 041 89.041 88.986 88.986 88.932 88.932 88.904 88.877 88.877 88-877 88.849 88-822 88.795 88.795 88.767 88-740 88-740 88.740 88.712 88.712 0-000 0-000 0-000 0.000 0.000 0-000 0.000 0.000 0-000 0 000 0.000 0-000 0.000 0-000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 0-000 0.000 0-000 0-000 0.000 0-000 0-000 0-000 0-000 0-000 0-000 0.000 0.000 0-000 0-000 0.000 0.000 0-000 0-000 0.000 0-000 0-000 0-000 0.000
VARIABLE TABLE
SUMMARY
(CONTINUED) 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 750 765 780 795
~
810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 SAMPLE DELTA NUMBER MINS TEMP 25 DEG.
F 88'.440 88.430 88.420 88.390 88 '70 88.360 88.350 88.340 88.330 88.320 88-310 88.300 88.280 88.260 88-260 88-240 88.230 88.220 88.220 88.200 88.180 88.180 88.170 88-160 88.150 88.130 88-120 88.110 88.100 88.080 88.060 88.050 88.040 88.040 88-030 88.010 87.990 87.980 87.970 87.950 87.930 87.920 87.920 87.900 87-890 87.880 87.860 TEMP 26 DEG.
F 88.329 88.301 88.301 88.274 88,.274 88.274 "88.247 88.247 88-247 88.219 88.219 88-219 88.192 88.247 88.247 88.247 88.219 88.219 88.164 88.164 88-082 88.082 88.055 88.082 88.027 88.055 88.000 87.973 87.973 87.946 87.973 87.918 87.891 87-891 87.918 87.864 87.864 87.837 87.837 87.810 87 810 87.810 87-782 87.782 87.728 87.782 87.755 88.384 88-384 88-356 88.329 88.329 88.301 88.274 88.301 88.274 88-274 88-247 88-274 88.274 88.301 88.247 88.274 88.247 88.219 88.192 88.164 88-110 88.110 88-082 88-082 88-055 88-055 88-055 88-000 87.973 87.946 87.946 87-918 87.891 87-918 87.891 87-864 87.864 87-864 87-837 87.837 87.782 87-810 87-782 87.782 87.728 87.755 88.301 88.274 88.274 88.247 88-219 88.219 88.192 88.219 88.192 88.176 88.164 88.192 88.192 88.164 88.219 88.192 88.192 88.110 88.082 88-082 88-082 88-027 88.000 88.000 88-000 87.973 87.946 87.946 87.918 87.891 87-864 87.837 87-864 87.810 87-837 87.810 87.810 87.782 87.755 87.728 87-728 87.728 87.701 87.728 87.701 87.728 TEMP 27 TEMP 28 DEG.
F DEG.
F.
88.384 88.301 88.685 88.685 88.658 88.658 88.630 88.575 88.575 88.548 88-548 88.575 88.493 88-521 88-548 88.521 88-575 88.575 88.548 88.521 88.466 88.411 88.384 88.356 88.329 88 '56 88-301 88.247 88-274 88-219 88.219 88.192 88.192 88.164 88.137 88.082 88.110 88.082 88.055 88.055 88-027 88.027 88.000 88.000 88.000 87-946 87.946 87.918 87.891 0.000 0.000 0-000 0-000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0-000 0.000 0 F 000 0-000 0.000 0-000 0-000 0.000 0.000 0.000 0.000 0-000 0-000 0.000 0-000 0-000 0.000 0-000 0-000 0.000 0-000 0-000 0.000 0.000 0-000 0.000 0-000 0.000 0.000 0-000 0 F 000 0.000 0-000 0.000 0.000 0-000 TEMP 29 TEMP 30 DEG.
F DEG.
F END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE DELTA TEMP 31 TEMP 32 TEMP 33 NUMBER MINS DEG.,
F DEG.
F DEG.
F TEMP 34 DEG.
F TEMP 35 DEG.
F TEMP 36 DEG.
1 2
3 4
5 6
7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 89.425 89.397 89-397 89.315 89.288 89.233 89.206 89.233 89.151 89-096 89 '69 89.096 89.069 89-014 88.932 88.932 88.932 88.904 88-877 88.849 88.822 88 '95 88.795 88.740 88.740 88.740 88-685 88-658 88-685 88.603 88.603 88 F 548 88-548 88-521 88.548 88.521 88-493 88-493 88-438 88-466 88.411 88-384 88.384 88.384 88-356 88.301 88.301 88.301 88-301 88.247 89.260 89.233 89.178 89-151 89.123 89-096 89.069 89.041 88.986 88.959 88.904 88.904 88-877 88.822 88-849 88.795 88-740 88-712 88.740 88.685 88-630 88.658 88-630 88-575 88-575 88.548 88.493 88.493 88-493 88-438 88.411 88-411 88-384 88.356 88-384 88-356 88.329 88-301 88.301 88.247 88 247 88.219 88.219 88-192 88-164 88.164 88.110 88-110 88.110 88-082 89.616 89-562 89-507 89.479 89-452 89.425 89.370 89.315 89.315 89.315 89.233 89-206 89.178 89-151 89.096 89-096 89.123 89.069 89.014 88-986 88.932 88.932 88.932 88.904 88.877 88-849 88.849 88.822 88.767 88.767 88.767 88.767 88.712 88-685 88.685 88.658 88.630 88.575 88 603 88-575 88.575 88-548 88.521 88.493 88.466 88.466 88.438 88.411 88-411 88.384 89.425 89.397 89-342 89.315 89-288 89.233 89-206 89.178 89.151 89-069 89.096 89-096
'89-014 88.986 88.959 88.932 88.932 88-849 88-849 88-822 88.795 88.822 88.740 88.712 88.685 88.685 88.658 88-658 88.603 88.603 88.603 88.548 88-521 88.521 88.493 88-466 88.466 88-466 88.466 88.411 88-411 88-411 88-356 88.301 88-329 88.301 88.301 88.247 88-274 88.247 89.288 89.288 89.206 89-151 89.123 89.096 89-096 89.041 89.041 88.959 88.932 88.904 88.904 88-904 88.849 88.795 88.795 88.740 88 '40 88.712 88.658 88.630 88.603 88.603 88.575 88.548 88.521 88.493 88.466 88.466 88.438 88.384 88.384 88.384 88.356 88.356 88.329 88-329 88.301 88.274 88.247 88.247 88.219 88.192 88.192 88.192 88.137 88.137 88.137 88.110 88.356 88.329 88-274 88.219 88.164 88.082 88-082 88-000 88.000 87.946 87.891 87-864 87.864 87.810 87.782 87.728 87 '01 87 '46 87.619 87-619 87.565 87-537 87-510 87-456 87-456 87-401 87-401 87-374 87.320 87-320 87-293 87.211 87.184 87.184 87.157 87.129 87-102 87.075 87-075 87.020 87.048 86-993 86.966 86.939 86.912 86-884 86-884 86.857 86.803 86.803
SAMPLE NUMBER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70'1 72 73 74 75 76 77 78 79 80 81 82 83 84 85
'86 87 88 89 90 91 92 93 94 95 96 97 DELTA MINS 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 88.247 88.247 88.247 88.219 88.164 88.192 88-164 88-164 88.137 88.137 88.110 88.055 88.082 88-055 88.000 88.027 88.000 87.973 87.946 87.918 87.946 87.918 87.918 87.891 87.891 87-837 87-810 87.837 87-782 87 '82 87.782 87.782 87 '28 87-728 87.728 87.728 87.728 87.674 87.619 87-619 87.619 87-592 87-592 87.537 87-537 87-510 87.510 88.055 88.055 88.055 88.027 88.027 88.000 87.973 87.973 87.946 87.918'7.918 87.918 87.864 87.891 87-864 87.810 87.837 87.837 87.782 87.782 87.782 87-755 87 '28 87.728 87-674 87-646 87-674 87-674 87.619 87.619 87-592 87.619 87.565 87.537 87.565 87.537 87.510 87.483 87.483 87-456 87.456 87-401 87-401 87.374 87.401 87.347 87.347 88.356 88.356 88.329 88.301 88-301 88.274 88.274 88-247 88.247 88-219 88.219 88.192 88.219 88-192 88-137 88-110 88.110 88.110 88.110 88.082 88 '27 88.000 88-000 88.000 87.973 87.973 87.946 87.918 87-891 87-891 87-918 87-864 87-837 87.837 87.837 87.810 87.782 87.755 87.755 87.728 87.728 87-701 87-728 87-674 87.646 87-646 87.646 88.247 88-219 88.247 88.192 88-164 88.192 88.137 88.110 88.110 88.082 88.082 88.082 88.082 88.055 88.027 88.027 88-000 87-946 87-946 87-946 87.946 87-918 87-891 87-891 87-864 87-837 87-837 87-810 87-837 87.755 87-782 87-782 87.728 87.701 87.701 87.646 87.646 87 '01 87-619 87-619 87.592 87-565 87-565 87.592 87-510 87-510 87.456 88.082 88.082 88.027 88.027 88.027 88.000 88.000 88.027 87.946 87.918 87.918 87-891 87.864 87-864 87-837 87.837 87.837 87.810 87.782 87.755 87.755 87.728 87.728 87.728 87.728 87.646 87-674 87.646 87.619 87.619 87.619 87.592 87.537 87.537 87.537 87.510 87.537 87.510 87.483 87.483 87.401 87.429 87.401 87.401 87.374 87.374 87.347 86.776 86.748 86.748 86.721 86.721 86.694 86.667 86.612 86.612 86.585
'86.558 86.531 86.503 86.503 86.476 86.476 86.449 86.422 86.367 86.367 86.367 86.340 86-286 86.286 86.259 86.204 86.177 86.177 86-150 86.150 86.095 86.095 86.041 86.014 86.014 85.959 85.986 85.932 85.905 85.850 85.823 85.823 85-769.
85.769 85.742 85.714 85.714 END OF TABLE VARIABLE TABLE
SUMMARY
(CONTINUED)
TEMP 31 TEMP 32 TEMP 33 TEMP 34 TEMP 35 TEMP 36 DEG.
F DEG.
F DEG.
F DEG.
F DEG.
F DEG.
F
SAMPLE NUMBER 1
2 3
5 6
7 8
9 10ll 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 TEMP 37 DEG-F 88.411 88.411 88.356 88-301 88-219 88.192 88.137 88.137 88.082 88.000 88.000 87.946 87.891 87.864 87.837 87.810 87.782 87.755 87.701 87 '74 87.646 87.592 87.565 87.537 87.510 87.483 87.456 87.429 87.401 87.374 87-347 87.293 87.293 87.265 87.265 87-211 87-184 87-157 87.129 87.102 87.075 87.048 87.048 87.020 86.993 86-966 86.966 86.939 86.912 86-884 DEG.
F DEG-F DEG.
F 95.699 95.699 95 '26 95 '26 95 '26 95.699 95-753 95-726 95.753 95-726 95.726 95.726 95.781 95.753 95.781 95.781 95.781 95.753 95-781 95.808 95.836 95.808 95.836 95 '36 95.836 95-863 95-890 95.918 95-918 95-973 95.945 95.945 95.945 95.973 95.973 96.027 96.000 96-027 96.027 96-082 96.110 96.110 96.137 96.137 96-192 96.192 96.219 96-219 96.247 96.247 93.699 93.726 93-671 93.644 93.616 93.616 93.589 93.616 93.589 93.589 93-562 93-534 93.562 93.534 93.507 93.507 93.534 93.507 93.507 93.452 93.480 93.480 93.452 93.452 93.452 93.425 93.480 93.452 93.452 93.425 93 '80 93.425 93-452 93-452 93.452 93.425 93.452 93.452 93.452 93.480 93.480 93.480 93.452 93.452 93.480 93.452 93 '80 93.452 93.480 93.480 97.836 97-836 97.808 97.836 97-808 97.808 97.781 97.863 97-836 97-890 97-890 97.890 97.918 97.945 97.945 97.918 97.945 97.945 98.000 98.000 98-027 98.055 98.082 98.110 98.110 98-110 98.137 98.164 98.164 98.192 98-247 98.274 98.274 98-301 98.329 98.356 98-356 98-411 98.384 98.438 98.438 98.493 98.521 98.521 98.548 98.575 98.603 98-630 98.658 98.658 PSIA 35.943 35.941 35.939 35.938 35.936
~ 35.934 35.932 35.930 35.928 35.927 35-925 35.923 35.922 35.920 35.918 35.916 35.914 35.914 35.912 35.911 35.909 35.908 35.906 35.905 35.904 35.903 35.902 35.900 35.899 35.898 35.896 35-895 35.895 35.894 35.893 35.891 35.890 35.888 35.888 35.888 35.886 35.885 35.884 35.883 35.882 35-881 35.880 35.879 35.878 35.877 VARIABLE TABLE
SUMMARY
TEMP 38 TEMP 39 TEMP 40 PRES 1
HUM 1
FRACTION 0.000 0-000 0.000 0.000 0'000 0.000 0.000 0.000 0.000 0.000
-0. 000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000.
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000
SAMPLE NUMBER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 DELTA MINS 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 86.884 86.830 86.830 86.776 86.776 86.776 86.748 86.694 86.694 86.639 86.639 86.585 86.612 86.558 86.585 86.558 86.503 86.476 86.476 86.422 86.422 86.395 86.367 86.340 86.313 86.286 86.259 86-259 86.231 86.204 86.150 86.150 86.095 86.095 86-068 86.014 86.014 86.014 85.932 85.932 85.905 85.878 85.796 85.850 85.823 85.823 85.769 96.274 96.274 96.301 96.329 96.356 96.384 96.411 96.411 96.411 96.438 96.493 96.493 96.493 96 '48 96.584 96.603 96.630 96.658 96.658 96.658 96.630 96.712 96.685 96.712 96.767 96.767 96.795 96.822 96.822 96.877 96.849 96.877 96.904 96.932 96.932 96.959 96.986 96.986 97.041 97-069 97.041 97-123 97.123 97.150 97.151 97-206 97.206 VARIABLE TEMP 37 TEMP 38 DEG.
F DEG.
F TABLE
SUMMARY
(CONTINUED)
TEMP 39 DEG.
F 93.452 93 '52 93.452 93.480 93.534
'3.480 93.507 93.507 93.507 93.507 93.507 93.534 93.534 93.507 93.562 93.534 93.534 93.562 93.534 93.562 93.562 93.534 93.562 93.562 93.562 93.562 93.534 93.589 93.534 93-562
'3.562 93.562 93.562 93.589 93.534 93.562 93.562 93.589 93-616 93.562 93.562 93.589 93.589 93.589 93.589 93.589 93.589 DEG.
F 98.712 98.712 98.740 98.767 98.795 98.795 98.849 98.849 98.904 98.932 98.932 98.986 99.041 99.041 99.069 99.096 99.123 99.151 99.151 99.206 99.233 99.233 99.288 99.288 99 '43 99.343 99.370 99.397 99.425 99.452 99.507 99.507 99.507 99.534 99.589 99.644 99.617 99.671 99.699 99.726 99.726 99.753 99.808 99.836 99.863 99.863 99.918 PSIA 35.876 35.876 35.875 35.874 35.873 35.872 35.872 35.871 35.870 35.869 35.868 35.867 35.866 35.865 35.864 35.864 35.863 35.862 35.861 35-860 35.859 35.859 35-858 35.857 35.856 35-856 35-855 35.854 35-853 35.853 35.852 35.851 35.850 35.849 35.848 35.848 35.847 35.846 35.845 35.844 35-844 35.843 35.842 35.841 35.840 35-840 35.839 TEMP 40 PRES 1
HUM 1
FRACTION 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE DELTA NUMBER MINS HUM 2
HUM 3
HUM 4
HUM 5
HUM 6
HUM 7
FRACTION FRACTION FRACTION FRACTION FRACTION FRACTION 1
2 3
4 5
6 7
8 9
10ll 12, 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630
,645 660 675 690 705 720 735 0.667 0.664 0.664 0.665 0.666 0.666 0.667 0.667 0.667 0.668 0.668 0.669 0.669 0.670 0.671 0.672 0.671 0.674 0.673 0.673 0.673 0.673 0-675 0.674 0.675 0.674 0.675 0.675 0.674 0.675 0.674 0.675 0.675 0.675 0.675 0.676 0.676 0.676 0.676 0.676 0.676 0.677 0.677 0.677 0.677 0.678 0-677 0.678 0-678
- 0. 678 0.639 0.640 0.641 0.642 0-643 0.644 0-644 0.645 0-646 0.646 0.646 0.646 0.647 0-647 0.647 0.649 0.649 0.650 0.651 0.651 0.652 0.652 0.653 0.654 0.654 D.655 0.655 0.656 0.656 0.656 0-657 0-657 0-657 0-658 0-658 0.659 0.659 0-660 0.660 0.660 0.661 0 '61 0.661 0.662 0.662 0.663 0.663 0.663 0.663 0.663 0.577 0.578 0.578 0.579 0.578 0.579 0.579 0.579 0.579 0.580 0.580 0.580 0.581 0.581 0.581 0.581 0.582 0.583 0.583 0.582 0.583 0.583 0.584 0-585 0.584 0.584 0.585 0.585 0.585 0.585 0.585 0.586 0.586 0.586 0.586 0.586 0.587 0.587 0.587 0.587 0.588 0.587 0.588 0.588 0.588 0.589 0.589 0.589 0.590 0.590 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0:000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Oi000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0-000 0.000 0-000 0-000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0-000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0-000 0.000 0.000 0.000 0-000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
VARIABLE TABLE
SUMMARY
(CONTINUED)
SAMPLE NUMBER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 DELTA MINS 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 0.678 0.678 0.678 0.679 0.678 0.679 0-679 0.679 0.679 0.679 0.679 0.679 0.680 0.680 0.682 0.681 0.681 0.680 0.680 0.680 0.680 0.680 0.680 0.681 0.681 0.681 0.681 0.681 0.682 0.681 0.682 0.682 0.682 0.681 0.681 0.681 0.682 0.682 0.684 0.683 0.683 0.683 0.683 0.683 0.683 0.683 0-683 0.664 0.664 0.664 0.664 0-665 0.665 0.665 0.665 0.665 0.666 0.666 0.666 0.666 0.667 0.667 0.667 0.667 0.667 0.667 0.667 0.667 0.668 0.668 0-667 0.668 0-668 0-668 0-668 0.668 0.668 0.669 0-669 0.669 0.669 0.669 0.669 0-669 0-669 0.669 0-670 0.670 0.670 0.670 0.670 0.670 0-670 0.670 0-590 0-590 0-591 0;591 0.591 0.591 0.592 0.591 0.592 0.592 0.593 0.593 0.593 0.594 0.595 0.594 0.595 0-594 0.595 0.595 0-595 0.596 0-595 0.595 0-596 0.596 0-597 0-597 0.597 0-598 0.599 0-598 0-598 0-598 0.599 0.599 0-600 0-601 0-601 0-601 0-601 0.602 0-602 0-602 0-603 0.603 0-602 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 "0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0-000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 0-000 0.000 0-000 0.000
,0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000
~0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 0.000 0-000 0-000 0.000 0-000 0.000 0.000 0'. 000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0-000 0-000 0-000 0-000 0-000 0.000 0-000 0.000 0-000 0-000 0.000 0-000 0.000 0-000 0.000 0.000 0.000 0.000 0-000 0-000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0-000 0.000 0.000 0-000 0.000 0-000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 0-000 0-000 HUM 2
HUM 3
HUM 4
HUM 5
HUM 6
HUM 7
FRACTION FRACTION FRACTION FRACTION FRACTION FRACTION END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER DELTA MINS HUM 8
HUM 9
HUM io FRACTION FRACTION FRACTION 1
2 3
5 6
7 8
9 10ll 12 13 14 15 16 17 18 19 20
.21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 45 46 47 48 49 50 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 300 315 330 345 360 375 390 405 420 435 450 465 480 495 510 525 540 555 570 585 600 615 630 645 660 675 690 705 720 735 0.563 0.563 0.564 0-564 0-564 0.565 0.565 0-565 0.565 0.566 0-566
'.567 0.567 0.567 0.568 0.568 0.569 0-569 0.569 0.569 0.569 0.570 0.570 0.571 0.571 0.571 0.572 0.572 0.572 0.572 0.573 0.573 0.573 0.574 0.574 0.574 0.574 0.575 0.575 0.575 0-576 0.576 0.576 0.577 0.577
'0.577 0.577 0-578 0.578 0.578 0.528 0.528 0.529 0-528 0.528 0-530 0.530 0.529 0.530 0.530 0.531 0.530 0-530 0.531 0.532 0.531, 0.532 0.532 0.532 0.531 0.533 0.534 0.532 0.533 0-533 0.533 0.534 0.533 0.534 0.535 0.534 0.535 0.534 0.535 0.535 0.536 0.537 0-536 0.537 0.537 0.537 0.537 0.538 0.536 0.538 0.537 0.537 0.538 0.538 0-539 0-567 0-568 0-568 0.569 0-569 0.569 0-569 0.570 0-569 0.570 0.570 0.570 0.571 0.571 0.571 0.571 0.572 0-572 0.572 0-572 0.572 0.573 0-573 0.573 0.574 0-574 0.574 0.574 0.575 0.574 0.575 0.576 0.575 0.576 0.576 0.576 0.577 0.577 0.577 0-578 0.577 0-578 0-578 0-578 0.579 0-578 0.579 0.579 0.579 0-580
VARIABLE TABLE
SUMMARY
(CONTINUED)
SAMPLE DELTA NUMBER MINS HUM 8
HUM 9
HUM 10 FRACTION FRACTION FRACTION 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 750 765 780 795 810 825 840 855 870 885 900 915 930 945 960 975 990 1005 1020 1035 1050 1065 1080 1095 1110 1125 1140 1155 1170 1185 1200 1215 1230 1245 1260 1275 1290 1305 1320 1335 1350 1365 1380 1395 1410 1425 1440 0.578 0.579 0.579 0.579 0.580 0.580 0-580 0.580 0.581 0.581 0.581 0.582 0.582 0.582 0.582 0.583 0.583 0.583 0.584 0-584 0.584 0-585 0-585 0.585 0.586 0-586 0.586 0.586 0-587 0.587 0-587 0.588 0-588 0.588 0-588 0.589 0.589 0.589 0.590 0.590 0-591 0.591 0.591 0.592 0.592 0-592 0.592 0-539 0.538 0-539 0.540 0-540 0.540 0.540 0-541 0.541 0-541 0.541 0-541 0.542 0-541 0.542 0-542 0-542 0.543 0-543 0.543 0.544 0.544 0.543 0-544 0.545 0.544 0.544 0.545 0.544 0-546 0 '46 0.546 0.546 0.547 0.547 0-548 0.547 0-548 0-548 0-548 0.549 0.549 0 550 0-550 0.549 0.550 0-550 0.581 0.581 0.581 0-581 0-581 0.581 0-582 0.582 0-582 0.582 0.582 0-583 0.583 0-583 0-583 0-584 0.584 0-585 0-585 0.585 0.585 0-585 0-586 0-586 0.586 0.586 0-587 0.587 0-587 0.588 0-588 0.588 0.589 0.588 0-590 0.589 0.590 0.590 0-591 0.591 0.590 0-591 0.591 0.592 0.592 0-593 0.593 END OF TABLE
END OF REPORT ON CONTAINMENT LEAK RATE TEST TO NRC
APPENDIX A.2 FLORIDA POWER & LIGHT COMPANY ST.
LUCIE NUCLEAR POWER STATION UNIT N0.1 COMPUTER
-, GENERATED REPORT CONTROLLED LFAK RATE TEST,
Iy
LEAK RATE COMPUTED USING TOTAL TIME METHOD AS RECOMMENDED BY APPENDIX J FOR 10 CFR 50 (REACTOR CONTAINMENT LEAKAGE TESTING FOR WATER COOLED POWER REACTORS)
TEST PERIOD STARTED AT 2000 HOURS ON MAY 25,1979 A LEAST SQUARES FIRST ORDER FIT OF LEAK RATE TO TIME SHOULD YIELD A SLOPE OF ZERO AND AN INTERCEPT EQUAL TO THE LEAK RATE AS COMPUTED AT THE INITIALSTART TIME THE EQUATION HAS THE FORM - L=ST+R WHERE L CORRELATED LEAK RATE S SLOPE OF CORRELATION T TIME IN HOURS R INTERCEPT LEAK RATE LEAK RATE MEAN
= -0.001 HOURS +
0.295 PER CENT 0.292 PER CENT INITIALCONTAINMENT AIR WEIGHT =
436835 LBS.
FINAL CONTAINMENT AIR WEIGHT =
436589 LBS.
FITTED MASS POINT LEAK RATE IS 0.291 PER CENT PER DAY FITTED TOTAL TIME LEAK RATE IS 0-289 PER CENT PER DAY SIMPLE TOTAL TIME LEAK RATE IS 0.284 PER CENT PER DAY MAXIMUM NRC LEAK RATE OF 0.240 PER CENT PER DAY GIVEN FOR LOW PRESSURE TEST AT 35.83 PSIA LEAKAGE OF.240
~
PER DAY AT 34.496 PSIA IS EQUIVALENT TO 9.34 SCFM.
SUPPLEMENTAL TEST (CLRT)
DATA AND PREVIOUS ILRT RESULTS PLUS INJECTED LEAKAGE MUST BE WITHIN 25+o OF LA
(
3'1 SCFM)
FOR VERIFICATION MAXIMUM PROBABLE TEMPERATURE LOOP ERROR IS 0.008 DEGREES F.
MAXIMUM PROBABLE PRESSURE LOOP ERROR IS 0.0005 PSIA.
MAXIMUM PROBABLE HUMIDITY LOOP ERROR IS 0.044 PERCENT.
MAXIMUM PROBABLE INSTRUMENT ERROR IS 0.0030 PERCENT PER DAY <*
WITHIN A COMPUTED CONFIDENCE OF 95.00 PERCENT
E8RSCO SERVICES INCORPORRTED-
/
17 9 LLJ 0 4000 0.3600 CONPUTEQ FIT RELRTIVE TO CRITICAL LIMIT x
x
=
SIMPLE TOTAL TINE LEAK RATE IHSTRUt',EHT ERROR L IHIT RF DUCT ION Y
Y COMPUTED FIRST ORDER EQUATION GREEN OCTAGON STATISTICAL RE JE,CT ION 0-C3 0 3200 0.2800 Y
Y Y
Y Y
Y Y
Y Y
0 Y
x x
x x
x x
0.2400 0.2000 60
~
120
~
180.
240
~
300.
360
~
420.
TIME IN N
NUTES
'i J
5'DRRTED 9 ~
i..
17
~
0 4000 t ONPUTED LERK RRTE FIT RELRTIVE TO LIMITS CONTRINNENT DESIGN LERK RRTE NRC TECHNICRL SPECIFICRTION LIt1IT
'NSTRUMENT ERROR LIMNI~
REDUCTION COMPUTED FIRST ORDER EQURTION 0.3600 0.3200 Y
Y Y
Y y
y y
Y Y
Y Y
Y Y
Y Y
Y Y
Y Y
0.2800 0.2400 0 2000 0
60
~
120 180.
240
~
300.
360 TIME IN MINUTES
9 ~
1 17
~
9
~
12.0000 8.0000 COMPUTED LERK RRTES RELRTIVE TO LIMITS x
x STRTISTICRL TOTRL LEAK RATE COHTRINf1ENT DESIGN LERK RRTE NRC TECHNICRL SPECIFICRTION LIMIT INSTRUMENT ERROR L IHIT REDUCTION COMPUTED FIRST ORDER EQURTIOH 4 0000 0-0000 x
x
-4 0000
-8.0000 4
60
~
120.
180.
240.
300.
360.
420.
TINE IN MINUTES
J
EBRSCO SERVICES INCURVURHIEU 3
~
7 ~
5
~
9 ~
35.8380 RVERRDE CONTRINNENT PRE55URE 35.8300 35.8220 35-8140 35-8060 35.7980 0
60
~
120 180.
240.
300.
360.
420.
T I ME IN MINUTES
EBRSCO SERVICES INCURPuRHTEU 7
~
9
~
VOLUNETRI CALLY WEIGHTED CONTR INNENT TENPERRTVRE 87.5400 87.5000 87.4600 87.4200 87.3800 0
60'20.
180.
240.
300.
360.
420.
TIME IN MINUTES
EBHSCU SERVICES INCURVURRTED 3 ~
7
~
9
~
0 4032 VOLUMETRICALLY WEIGHTED VAPOR PRESSURE 0.4024 0.4016 0.4008 0.4000 0 3992 60'20.
180.
240.
300.
360.
420.
TIME IN MINUTES
DESCRIPTION OF VARIABLES AVG. TEM VOLUMETRICALLYWEIGHTED TEMPERATURE.
AVG. PRE AVERAGE PRESSURE-VAP.
PRE VOLUMETRICALLYWEIGHTED VAPOUR PRESSURE.
LEAK COM LEAK RATE COMPUTED FROM FIRST ORDER REGRESSION-LEAK SIM LEAK RATE BASED ON TOTAL TIME CALCULATIONS.
LEAK MAS LEAK RATE FROM MASS POINT FIRST ORDER REGRESSION.
NOTE FOR TABULAR DATA TABLE VALUES OF ZERO SIGNIFY EITHER 1.
DATA IS NOT APPLICABLE TO THE CALCULATION OR 2.
SENSOR HAS BEEN DELETED FROM THE SCAN.
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 AVG. TEM DEG.
F 87.530 87.522 87-506 87.501 87.495 87.488 87.476 87.473 87.460 87.457 87.449 87.440 87.435 87.425 87.423 87.410 87.402 87.403 87.388 87.386 AVG. PRE PSIA 35-827 35.825 35.823
~
35.822 35.820 35.819 35.817 35-816 35.814 35.813 35.812 35-810 35-809 35.807 35-806 35.804 35.803 35.801 35.800 35.798 VAP.
PRE PSIA 0.399 0.399 0.400 0.400 0.400 0.400 0-400 0.400 0.400 0.400 0-400 0.400 0.401 0.402 0.401 0.401 0.401 0.401 0.401 0.400 LEAK COM PER CENT 0.295 0.295 0.295 0.294 0.294 0.294 0.293 0.293 0.293 0.292 0.292 0.292 0.291 0.291 0.291 0.290 0.290 0-289 0.289 0-289 LEAK SIM PER CENT 0.000 0.354 0-267 0-275 0.299 0.288 0.270 0.285 0.281 0.288 0.294 0.288 0.307 0-311 0.303 0.291 0-286 0-292 0.282 0-284 LEAK MAS PER CENT 0-000 0-000 0.267 0-266 0.287 0-287 0.275 0.278 0.279 0.282 0-287 0.288 0.295 0-302 0-304 0.301 0-298 0 296 0.293 0 '91 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE-NUMBER 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270
'285 TEMP 1
DEG.
F 84.898 84.871 84.871 84.898 84.898 84.898 84-871 84.871 84-898 84.898 84-871 84.871 84-871 84.898 84-871 84.844 84.871 84.844 84.898 84-871 TEMP 2
DEG.
F 85.714 85.714 85.714 85.687 85-742 85.714 85.714 85.714 85.687 85.714 85.687 85.714 85.687 85-714 85.714 85-687 85.714 85.714 85-687 85.687 TEMP 3
DEG.
F 85."225 85.225 85.170 85-225 85.197 85.197 85.197 85.225 85.197 85.225 85.197 85.197 85.197 85-170 85.197 85.225 85-225 85-225 85.170 85-170 TEMP 4
DEG.
F 85.742 85.796 85.796 85.796 85-796 85-742 85.742 85.796 85.769 85.796 85.796 85.769 85.796 85.796 85.796 85.769 85.742 85.796 85.769 85.769 TEMP 5
DEG.
F 0.000 0.000 0-000 0-000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0-000 TEMP 6
DEG.
F 84.898 84.898 84-871 84.898 84.898 84.898 84.898 84.898 84.844 84.871 84.898 84.898 84.898 84.871 84.844 84.871 84.844 84.898 84.871 84.871 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 TEMP 7
DEG.
F 85.388 85.388 85.361 85 '61 85.361 85.361 85-361 85.388 85.333 85.361 85.333 85.361 85-361 85.361 85.361 85.333 85-361 85-333 85.333 85.333 TEMP 8
DEG.
F 84.789 84.789 84.789 84.762 84.816 84.816 84.789 84.789 84.789 84.762 84.762 84.789 84-789 84-789 84.789 84-762 84.762 84.762 84.735 84.735 TEMP 9
DEG.
F 87.429 87.429 87.401 87.374 87.401 87.347 87.374 87.320 87-320 87-265 87.320 87.265 87-265 87.265 87-265 87.238 87-265 87.211 87.211 87.211 TEMP 10 DEG.
F 87.075 87.048 87.048 87.020 87.020 86.993 87.020 86.993 86.939 86.966 86.993 86.912 86.912 86.912 86 '84 86.884 86.857 86.857 86.830 86.830 TEMP 11 DEG-F 87.184 87.157 87.102 87.129 87.102 87.075 87.075 87 '48 87.048 87.020 87.020 86.993 86.993 86.993 86.993 86.993 86.939 86-966 86.939 86.939 TEMP 12 DEG.
F 87.401 87.429 87.347 87.347 87 '20 87.347 87 '20 87.293 87.293 87.293 87.265 87.265 87.265 87.211 87-211 87.238 87-211 87.184 87.184 87.184 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2, 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 i 135 150 165 180 195 210 225 240 255 270 285 TEMP 13 DEG.
F 87.429 87.401 87.401 87.374 87.374 87.374 87.374 87.347 87.293 87.320 87.293 87.293 87.293 87.293 87.265 87.211 87-293 87.211 87.211 87.211 TEMP 14 DEG.
F 87-674 87.701 87.646 87.619 87.592 87.619 87.592 87.619 87.619 87.565 87.592 87.537 87.565 87.510 87.510 87.510 87.483 87.456 87.456 87.483 TEMP 15 DEG.
F 87.184 87.129 87.157 87.129 87.102 87.102 87.075 87.048 87.075 87.048 87.048 87.048 86.993 86.993 86.993 86.993 86.939 86.966 86.939 86.912 TEMP 16 DEG.
F 89.123 89.123 89.123 89.096 89.069 89.069 89.041 89.096 89.041 89.014 89.014 88.986 88.959 88.986 88.959 88.932 88.932 88.932 88.932 88.932 TEMP 17 DEG.
F 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 TEMP 18 DEG.
F 87.537 87.510 87.510 87.483 87.483 87.456 87.429 87.429 87.401 87.429 87.429 87.401 87.401 87.374 87.374 87.347 87.347 87.347 87.320 87.320 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 DELTA MENS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 TEMP 19 DEG.
F 87.537 87.483 87.483 87.456 87.483 87.483 87.429 87.429 87.429 87.429 87.401 87.374 87.374 87.374 87.374 87.347 87.320 87.347 87 '20 87.320 TEMP 20 DEG.
F 87 '01 87.347'7.374 87.347 87.347 87.320 87.347 87.320 87.320 87.320 87.293 87.265 87.265 87.238 87.265 87.238 87.211 87.238 87.211 87.184 TEMP 21 DEG.
F 85.361 85.333 85.306 85.333 85.306 85.279 85.279 85.279 85.252 85.225 85.225 85.225 85.197 85.170 85.197 85.143 85.143 85.143 85.088 85.088 TEMP 22 DEG.
F
'85.415 85.415 85.388 85.388 85.361 85.333 85.306 85.279 85.252 85.252 85-225 85.225 85.197 85.197 85.197 85.143 85.143 85.116
'5.116 85.088 TEMP 23 DEG.
F 85.633 85.605 85-578 85.551 85.551 85.524 85.524 85.524 85-497 85.469 85.442 85.415
,85.415 85.415 85.388 85.415 85.361 85.333 85.333 85-306 TEMP 24 DEG.
F 85.986 85.986 85.959 85.932 85.932 85-905 85.823 85.905 85.823 85.823 85.823 85.823 85.742 85.769 85.742 85.742 85.714 85-687 85-633 85.660 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 TEMP 25 DEG.
F 87.660 87.650 87.640 87.620 87.620 87.600 87.590 87.580 87.570 87.550 87.540 87.500 87.510 87.500 87.490 87.490 87 '70 87.460 87.450 87.440 TEMP 26 DEG.
F 87.565 87.565 87.537 87.537 87.483 87.483 87.483 87.483 87.456 87.483 87.456 87.429 87.429 87.401 87.374 87.401 87.374 87.374 87.347 87.347 TEMP 27 DEG.
F 87.565 87.537 87.510 87.510 87.483 87.456 87.456 87.456 87-456 87.456 87.401 87.401 87.401 87.374 87.374
,87.374 87.347 87.374 87.347 87.320 TEMP 28 DEG.
F 87.510 87.483 87.456 87.456 87.456 87.456 87.401 87.429 87.401 87.401 87.401 87.401 87.401 87.374 87.347 87.347 87.293 87.347 87.293 87.320 TEMP 29 DEG.
F 87.674 87.619 87.619 87.646 87.619 87.646 87.619 87.592 87.619 87.592 87.537 87.537 87.565 87.537 87.537 87.510 87.483 87.483 87 '83 87.483 TEMP 30 DEG.
F 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
5 6
7 8
9 10ll 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 TEMP 31 DEG.
F 87.293 87 293 87.238 87.265 87.265 87.238 87.238 87.211 87.211 87.211 87.184 87.184 87.184 87.157 87.157 87.129 87.157 87.129 87.102 87.129 TEMP 32 DEG.
87.102 87.129 87.102 87.102 87.048 87.048 87.048 87.048 87.020 87.020 87.020 86.993 86.966 86.966 86.993 86.966 86.966 86.912 86.912 86.912 TEMP 33 DEG.
F 87.429 87.429 87.429 87-401 87.374 87.374 87.347 87-347 87.347 87.320 87.320 87 '20 87.347 87-265 87.265 87.265 87.265 87.238 87.238 87.238 TEMP 34 DEG.
F 87-265 87 265 87-238 87.238 87.211 87.238 87 265 87-157 87.184 87.157 87.157 87.157 87.129 87.075 87.129 87.100 87.075 87-075 87.075 87.048 TEMP 35 DEG.
F 87.102 87.102 87.102 87.075 87.075 87.075 87.020 87.020 86.993 87.020 86.993 86.993 86.966 86.966 86.939 86.939 86.939 86-966 86.912 86.912 TEMP 36 DEG.
F 85-388 85.361 85-306 85-306
'85.279 85-279 85.252 85.225 85-170 85.197 85-170 85.143 85.088 85.116 85-116 85-034 85-034 85.061 85-007 85.007 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 TEMP 37 DEG.
F 85.388 85.361 85 '61 85.333 85.333 85.306 85-279 85.279 85.252 85.197 85.170 85.197 85.170 85.170 85.116 85-116 85-061
~
85-116 85.088 85.034 TEMP 38 DEG.
F 97.589 97 '17 97-644 97.671 97.726 97.753 97.781 97.781 97-808 97.808 97.890 97:890 97 '45 97.945 98.000 97.973 98.027 98.055 98.082 98.110 TEMP 39 DEG.
F 93.671 93.699 93.671 93-671 93.699 93.726 93.699 93.699 93.753 93.753 93.753 93.753 93-781 93.781 93-781 93-781 93-781 93.808 93.836 93.836 TEMP 40 DEG.
F 100.381 100.435 100.463 100.490 100.490 100.544 100.571 100.599 100.653 100-680 100-708 100-762 100.789 100-816 100.844 100-898 100.925 100.952 100.980 101.034 PRES 1
PSIA 35.827 35.825 35.823 35.822 35.820 35.819 35.817 35.816 35.814 35-813 35-812 35.810 35-809 35.807 35-806 35.804 35.803 35.801 35-800 35-798 HUM 1
FRACTION 0-000 0-000 0.000 0.000 0.000 0.000 0-000 0 000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
4 5
6 7
8 9
10ll 12 13 14 15 16 17 18 19 20 DELTA MINS' 15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 HUM 2
FRACTION 0.683 0-683 0-683 0-683 0.684 0-683 0-684 0.683 0.684 0-685 0-687 0-687 0-688 0-693 0-689 0.689 0.687 0.687 0-687 0.686 HUM 3
FRACTION 0.670 0-670 0-670 0-671 0.671 0.671 0.671 0-671 0-671 0-671 0.672 0-672 0.673 0-674 0.673 0-673 0'73 0.673 0-673 0-673 HUM 4
FRACTION 0.608 0-608 0-609 0-610 0.610 0-610 0.610 0.610 0-610 0.612 0.613 0.613 0.616 0.615 0.614 0 ~
614'.614 0-614 0.614 0.614 HUM 5
FRACTION 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0-000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 HUM 6
FRACTION 0-000 0-000 0.000 0.000 0-000 0.000 0.000 0-000 0.000 0-000 0.000 0.000 0-000 0-000 0.000 0-000 0.000 0.000 0.000 0.000 HUM 7
FRACTION 0-000 0.000 0-000 0.000 0.000 0-000 0.000 0.000
, 0-000 0.000 0-000 0.000 0 F 000 0.000 0.000 0-000 0-000 0.000 0.000 0.000 END OF TABLE
VARIABLE TABLE
SUMMARY
SAMPLE NUMBER 1
2 3
5 6
7 8
9 10ll 12 13 14 15 16 17 18 19 20 DELTA MINS 0
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285 HUM 8
FRACTION 0.597 0.597 0.598 0.598 0.599 0.598 0.599 0.599 0.599 0-600 0.601 0.601 0.601 0.602 0.602 0.602 0.602 0.603 0-603 0.602 HUM 9
FRACTION 0-555 0,.555 0-555 0-555 0-556 0-556 0-556 0-557 0-556 0-556 0.557 0.556 0.557 0.558 0.558 0.558 0-559 0.558 0-558 0.559 HUM 10 FRACTION 0.597 0.597 0.598 0.598 0.599 0.599 0.599 0.599 0.599 0-600 0.600 0.601 0.602 0.602 0.602 0.602 0.602 0.601 0.603 0.602 END OF TABLE END OF REPORT ON CONTAINMENT LEAK RATE TEST TO NRC
APPENDIX B FLORIDA POWER 6 LIGHT COMPANY ST.
LUCIE NUCLEAR POWER STATION UNIT N0.1 TYPE B 6 C RESULTS
APPENDIX B Testing conducted between August, 1975 and October, 1976.
Date As Found As Left Reason Escape Lock Inner Door Seal Escape Lock Outer Door Seal 3-22-76 1
3-26-76 0
3-22-76 1.7 3-26-76 0
1.7 0
Retest following door opening Retest following door opening Retest following door opening Retest following door opening Maintenance Hatch Gasket Interspace 7-23-76 1050 1050 Retest following hatch closure Periodic Local Pene tra tion 25 Leak Rate Testing conducted October Valve Date Tested 10-28-76 10-28-76 10-28-76 10-28-76 10-23-76 thru November; 1976.
As Found As Left I-V-15328 I-MV-15-1 10-14-76 11-3-76 10-19-76 1620
- 14. 2 0
- 14. 2 I-V-18794 I-V-18796 I-V-18195 I-MV-18-1 10-22-76 10- 19-76 10-19-76 209 24.6 18.1 209 24.6 18.1 10 14 I-FCV-25-4 I-FCV-25-5 I-FCV-25-2 I-FCV-25-3 V-6779 V-6741 11-15-76 10-23-76 11-3-76 10-22-76 10-22-76 19.8 98, 724 12.8 0
19.8 820 12.8 0
- Note; All units expressed in sccm.
1 of ll e
Penetration 23 24 26 29A 29B 31 41 42 43 44 46 47 48C Valve I-HCV-14-1 I-HCV-14-7 I-HCV-14-2 I-HCV-14-6 V-2515 V-2516 V-5200 V-5203 V-5201 V-5204 V-5202 V-5205 V-6554 V-6555 I-V-07009 V-3463 I-LCV-07-11K I-LCV-07-11B V-6301 V-6302 I-SE-01-1 V-2505 I-V-07189 I-V-07206 I-V-.07188 I-V-07170
'I-FSE-27-1 I-FSE-27-2 I-FSE-27-3 I-FSE-27-4 I-FSE-27-8 I-V-27101 I-FSE-27-11 I-V-27102 I-FSE-27-10 Date Tested 10-22-76 10-22-76 10-13-76 10-13-76 10-5-76 10-5-76 10-5-76 10-5-76 10-5-76 10-5-76 10-5-76 10-5-76 10-22-76 10-22-76 10-22-76 10-13-76 10-13-76 10-13-76 10-13-76 11-15-76 11-15-76 10-13-76 10-13-76 10-13-76 10-14-76 As Found 3.4 8.9 0
1.5 7.2 0
39 40.6 4.8 87, 117. 2 104 81 29.1 25.5 50
- 15. 1 65.1 As Left 3.4 8.9 0
1.5 7.2 0
39 40.6 4.8 87 117.2 104 81 29.1 25.5 50 15.1 65.1 2 of 11
Penetration 51C 52A Ve 1ve I-FSE-27-5 I-FSE-27-6 I-FSE-27-7 I-FSE-27-9 I-FCV-26-1 I-FCV-26-2 Date Tested 10-14-76 11-3-76 10-14-76 10-14-76 10-14-76 11-3-76 As Found 118 4.2 1587 As Left 42.2 4.2 743 52B 52C 52D 52E I-FCV-26-3 I-FCV-26-4 I-FCV-26-5 I-FCV-26-6 I-V-OO14O I-V-00143 I-V-00139 I-V-00144 10-14-76 10-14-76 11-3-76 10-22-76 10-22-76 10-14-76 10-14-76 2.1 570 1190 19.8 6.2 3.2 2.1 352 1190
- 19. 8 6.2 3.2 54 56 Blind Flange I-V-25-11 I-V-25-12 11-3-76 10-19-76 250 250 I-V-25-13 I-V-25~14 10-19-76 301 301 67 68 I-V-25-15 I-V-25-16 I-V-25-20 I-FCV-25-7 I-V-25-21 I-FCV-25-8 10-19-76 11-5-76 11-5-76 11-7-76 11-7-76 1105 1575 8
9 21 1105 1575 8
9 21 All Electrical Penetrations Fuel Transfer Tube Blind Flange Maintenance Hatch Gasket Interspace 10-28-76 11-24-76 11-29-76 1.7 420 1.7 420 Escape Lock Inner Door Gasket 11-4-76 11-24-76 3 of ll
C
Penetration Valve Date Tested As Found As Left Escape Lock Outer Door Gasket 11-4-76 11-24-76 11-30-76 0
0 2.3 0
0 2.3 Escape Airlock Personnel Lock Inner Door Gasket Personnel Lock Outer Door Gasket Personnel Airlock 11-4-76 11>>29-76 11>>29-76 11-29-76 1.2 4.2 1.2 4.2 Testing conducted between
- December, 1976 and February, 1978.
Date As Found As Left Reason Escape Lock Inner Door Seal 12-1-76 3-11-77 3-11-77 4-6-77 9-26-77 10-8-77 3.2
>2000 3.2 Retest following door opening Retest following door opening Replaced seals Periodic surveillance Periodic surveillance Retest following door opening Escape Lock Outer Door Seal 12-1-76 3-11-77 3-11>>77 4-6-77 9-26-77 10-8-77 525 0
0 0
0 470 525 0
0 0
0 470 Retest following door opening Retest following door opening Retest following door opening Periodic surveillance Periodic surveillance Retest following door opening Escape Airlock 4-6-77 0
9-26-77 0
Periodic surveillance Periodic surveillance Personnel Lock Inner Door 4-8-77 1.8 10-11-77 12.3 1.8 12.3 Periodic surveillance Periodic surveillance Personnel Lock Outer Door 4-8-77 1.2 10-11-77 16.5 1.2 16.5 Periodic surveillance Periodic surveillance Personnel Airlock 4-8-77 440 10-11-77 2780 440 2780 Periodic surveillance Periodic surveillance Maintenance Hatch Gasket Interspace 4-25-77 15 10-8-77 430 15
'30 Retest following hatch closure Retest following hatch closure 4of 11
Penetra tion 9
Valve Date I-V-18195 4-25-77 As Found, As Left Reason Relocation of valve 51C I-FSE-27-1 I-FSE-27-2 I-FSE-27-3 I-FSE-27-4 I-FSE-27-5 I-FSE-27-6 I-FSE-27-7 10 77 742 10-8-77 812 10-8-77 561 10-8-77 394 10-8-77 430 10-8-77 485 10-8-77 515 742 812 561 394 430 485 515 Valve replacement Valve replacement Valve replacement Valve replacement Valve replacement Valve replacement Valve replacement 54 I-V-00101 10-8-77 630 630 Installation of valve Periodic Local.Leak Rate Testing conducted March thru May, 1978.
Penetration Valve I-V-15328 I-MV-15-1 I-V-18794 I-V-18796 Date Tested 3-31-78 3-31-78 3-31-78 3-31-78 4-10-78 5-4-78 5-4-78 3-28-78 As Found 87 0
10.8 As Left 87 0
10.8 10 V-18797 V-18798 I-V-18195 I-MV-18-1 I-FCV-25-4 I-FCV-25-5 3-28-78 3-28-78 4-17-78 4-29-78 4-17-78 4-11-78 1.2 0.7 9550 0
3310 1.2 0.7 383 0
3310 I-FCV-25-2 I-FCV-25-3 4-iS-78 5-13-78 455,904 38,511
Penetration 14 23 24 Valve V-6779 V-6741 I-HCV-14-1 I-HCV-14-7 I-HCV-14-2 I-HCV-14-6 Date Tested 4-10-78 4-10-78 4-15-78 4-15-78 As Found As Left 0
26 28A V-2515 V-2516 V-5200 V-5203 4-24-78 4-24-78 4-7-78 4-7-78 700 525 139 125 700 525 139 125 29A 29B 31 41 V-5201 V-5204 V-5202 V-5205 V-6554 V-6555 I-V-07009 V-3463 4-7-78 4-7-78 4-7-78 4-7-78 4-18-78 4-18-78 4/14/78 0
400 0
0 400 42 43 44 46 47 48A 48C I-LCV-07-11A I-LCV-07-llB V-6301 V-6302 I-SE-01-1 V-2505 I-V-07189 I-V"07206 I-V-07188 I-V"07170 I-FSE-27-1 I-FSE-27-2 I-FSE-27-3 I-FSE-27-4 I-FSE-27-8 I-V-27101 I-FSE-27-11 4-14-78 4-26-78 4-26-78 4-25-78 4-25-78 4-10-78 4-10-78 3-29-78 3-29-78 3-29-78 3-29-78 3-29-78 3-29-78 3-29-78 18 22 6
5130 0
0 0
382 30 0
0 18 22 6
5130 0
0 0
382 30 6 of 11
Penetration Valve I-V-27102 I-FSE-27-10 Date Tested 3-29-78 3-29-78 As Found As Left 51C 52B I-FSE-27-5 I-FSE 27-6 I-FSE-27-7 I-FSE-27-9 I-FCV-26-1 I-FCV-26-2 I-FCV-26-3 I-FCV-26-4 3-29-78 3-29-78 3-29-78 3-29-78 4-14-78 4-14-78 4-14-78 4-14-78 67 675 350 0
67 675 350 0
52C 52D I-FCV-26-5 I-FCV-26-6 I-V-00140 I-V-00143 5-2-78 5-2-78 4-4-78 34 2240 34 2240 52E I-V-00139 I-V-00144 4-4-78 54 I-V-00101 4-4-78 550 550 57 58 67 68 I-V-25-11 I-V-25-12 I-V-25-13 I-V-25-14 I-V-25-15 I-V-25-16 I-V"25-20 I-FCV-25-7 I-V-25-21 I-FCV-25-8 4-3-78 4-3-78 4-3-78 4-20-78 5-2-78 4-20-78 4-19-78 4-19-78 185 225 1150 325,000 105 13 456 185 225 1150 27 105 13 456 All Electrical Penetrations Fuel Transfer Tube Blind Flange 3-30-78 5-20-78 Maintenance Hatch Gasket Interspace 5-23-78 Escape Lock Inner Door Gasket
'-20-78 Escape Lock Outer Door Gasket 5-20-78 7of ll
Pene tration Escape Airlock Valve Personnel Lock Inner Door Gasket Personnel Lock Outer Door Gasket Personnel Airlock Date Tested 5-6-78 5-21-78 5-21-78 5-21-78 As Found
- 16. 7 As Left 34 16.7 Testing conducted between June, 1978 and March, 1979.
Date As Found As Left Reason Escape Lock Inner Door Seal 11-8-78 Periodic surveillance Escape Lock Outer Door Seal 11-8-78 Periodic surveillance Escape Airlock 11-8-78.
6350 6350 Periodic surveillance Personnel Lock Inner Door Seal 11-8-78 1.4 1.4 Periodic surveillance Personnel Lock 11-8-78 Outer Door Seal.
10 10 Periodic surveillance Personnel Airlock 11-8-78 75 75 Periodic surveillance Maintenance Hatch 11-7-78 Gasket Interspace 1-27-79 444 135 444 135 Retest following hatch closure Retest following hatch closure Penetration Valve Date As Found As Left Reason 29A V-5204 10-30-78 0
Valve repair (packing)
Periodic Local Leak Rate Testing conducted April thru May 1979.
Penetration Valve Date Tested 4-5-79 4-5-79 4-5-79 4-5-79 4-5-79 As Found 552 589 521 711 28 As Left 552 589 521 711 28 8 of ll
Penetration 10 Valve I-V-15328 I-MV-15-1 I-V-18794 I-V-18796 V-18797 V-18798 I-V-18195 I-N-18-1 I-FCV-25-4 I-FCV-25-5 I-FCV-25-2 I-FCV-25-3 Date Tested 4-9-78 4-20-79 4-17-79 4-17-79 4-17-79 4-13-79 4-13~79 4-12-79 5-13-79 4-3-79 As Found 205 76.1 70 87.7 5.7 2912 249 35,275 As Left 205 76.1 70 87.7 5.7 2912 249 977 14 23 24 V-6779 V-6741 I-HCV-14-1 I-HCV-14-7 I-HCV~14-2 I-HCV-14-6 4-19-79 4-19-79 4-14-79 4-14-79 8.2 12.1 9.9 9.6 8.2 12.1 9.9 9.6 26 29A 29B 31 41 V-2515 V-2516 V-5200 V-5203 V-5201 V-5204 V-5202 V-5205 V-6554 V-6555 I-V-07009 V-3463 4-20-79 4-20-79 4-20-79 4-20-79 4-18-79 4-18-79 4-20-79 4-20-79 4-13-79'-13-79 4-17-79 6186 761 174 188 3.2 5.7 11.4 565 0.8 5.9 263 6186 761 174 188 3.2 5 7, 11.4 565 0.8 5.9 263 42 I-LCV-07-11A 4-16-79 I-LCV-07-llB 893 893 43 V-6301 V-6302 4-18-79 4-18-79 406 523 406 523 9 of 11
Penetration 44 46 47 48A 48C 51C 52B Valve I-SE-01-1 V-2505 I-V-07189 I-V-07206 I-V-07188 I-V-07170 I-FSE-27-1 I-FSE-27-2 I-FSE-27-3 I-FSE-27-4 I-FSE-27-8 I-V-27101 I-FSE-27-11 I-V-27102 I-FSE-27-10 I-FSE-27~5 I-FSE-27-6 I-FSE-27-7 I-FSE-27-9 I-FCV-26-1 I-FCV-26-2 I-FCV-26-3 I-FCV-26-4 Date Tested 4-16-79 4-16-79 4-16-79 4-16-79 4-7-79 4-7-79 4-7-79 4-7-79 4-7-79 4-7-79 4-7-79 4-6-79 4-6-79 4-6-79 4-6-79 4-6-79 4-6-79 4-11-79 4-11-79 4-11-79 4-11-79 As Found 332 12 237 10.9 11.6 11.0 10.9 11.7 10.9 11.5 11.7 12.3 8.8 9.7 9.4 10.1 9.3 11.0 798 14.5 732 As Left 332 12 237 10.9 11.6 11.0 10.9 11.7 10.9 11.5 11.7 12.3 8.8 9.7 9.4 10.1 9.3 11.0 798
- 14. 5 732 52C 52D 52E 54 56 57 58 67 I-FCV-26-5 I-FCV-26-6 I-V-00140 I-V-00143 I-V-00139 I-V-00144 I-V-00101 I-V-25-11 I-V-25-12 I-V-25-13 I-V-25-14 I-V-25-15 I-V-25-16 I-V-25-20 I-FCV-25-7 4-12-79 4-12-79 4-10-79 4-10-79 4-7-79 4-11-79 4-10-79 4-11-79 4-6-79 4-6-79 42.2 2859 24.4 14.3 451 216 1132 586 260 698 42.2 2859 24.4 14.3 451 216 1132 586 260 698 10 of ll
Valve Date Tested As Found As Left 68 I-V-25-21 I-FCV-25-8 4-9-79 4-9-79
'19. 5 16.2 19.5 16.2 All Electrical Penetrations Fuel Transfer Tube Blind Flange 4-3-79 5>>21-79, 7.5 7.5 intenance Hatch Gasket Interspace 5-23-79 7.3 7.3 Escape Lock Inner Door Gasket Escape Lock Outer Door Gasket Escape Airlock Personnel Lock Inner Door Gasket Personnel Lock Outer Door Gasket Personnel Airlock 5-16-79 5-16-79 5-4-79 5-18-79 5-18-79 5-17-79 14, 893 12.4 94.9 882 8.4 12.4 94.9 882 The current (as of May 26, 1979) As left totals for Type B, Type C"and By-Pass Containment leakage is as follows:
Type "B" testing Type "C" testing By-Pass leakage testing Acceptance limits:
.60 La By-Pass 3,406 scc/min 2,111 scc/min 21,109 scc/min 544,786 scc/min 108,957 scc/min
0 v
v 1,
1
(