--_

      • .** l

¥ Docket No. 50-237 Commonwealth Edison Company ATTN:

Mr. Cordell Reed Vice President

  • Post Office Box 767 Chicago, IL 60690 DEC 6 rns3

SUBJECT:

DRESDEN NUCLEAR POWER STATION, UNIT 2 CONTAINMENT INTEGRATED LEAK RATE TEST FREQUENCY

References:

1.

Letter dated June 13, 1979, from B. B. Stephenson to H. R. Denton 2.. Letter dated July 7, 1983, from D. J. Scott to H. R. Denton Gentlemen:

We have reviewed the resul.ts of the Type A, B and. C leak rate tests submitted by References 1 and 2.

Our review indicates that the last two consecutive Type A tests at Dresden Unit 2 were failures and, pursua*nt to 10 CFR 50, Appendix J, Section III.A.6.(b), a Type A test should be performed during each plant shutdown for refueling.until two consecutive Type A tests 111eet the acceptance criteria of Appendix J.

Accordingly, unless you request and are granted an exemption from this requirement by NRR, we expect you to conduct a Type A tes.t during your upcoming refueling outage.

We will* gladly.discuss any questions you have concerning t.his matter.

Sincerely, r>

~~~=~*Q r:a:31212o~i75-e31206 PDR ADOCK 0500023.7 P

PDR

,.--~

.1 I

R. L. Spessard, Director Division of Engineering

  • cc:

D. L. -Farrar,* Director

.:.of Nuclear Licensing D~ J. Scott, Station Superintendent DMB/Document Control Desk *,(RIDS)

Resident Inspector, Rill Phyllis Dunton, Attorney General's Office, Environmental Control Division Robert A. Gilbert, NRR Francis Jape, RI!

Walter R. Butler, NRR

~

  • c==*--,_"='o-c~-=--"--~-~-~-, _ _,__

RIII 6?.$.a!

R~J..l;o RI~

lreYes/ld


~==-Walke.r. _

S~eter Spessard 12 / s/ 83 12 / ;J /B'f ~= -"

0 -=tcZ t.0,/ 8~ -~~ ____ 1:~ ~3=~-

0

-~ J~