Confirms 811119 Discussion Re Action Taken on Diesel Generator Cooling Water Pump Operability
ML17194A276
Person / Time
Site: Dresden  
Issue date: 11/20/1981
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Reed C
COMMONWEALTH EDISON CO.
References
NUDOCS 8111240600
Download: ML17194A276 (2)


Text

.,.

Docket No~- 50-237 Docket No.

50~249 Comro::>nwealth Edison Company ATTii:

1'4'.r. Cordell Reed Vice President Post Office Box 767 Chicago, IL 60690 GentJ.emen:

CONFIRNATION OF ACTION LE" Nov 2 o 1sa1 This refers to the telephone co:iiversation between Mr. c. E. Norelius and Nr. D. Scott and others of our respective staffs on November 19, 1981 regarding

. the diesel generator cooling\\.water pump operability at the Dresden station.

With regard to the matters discussed we understand that you will declare Unit 3 diesel generator inoperable with respect to ful..filling technical specification operability requirements until you have dem0nstrated the cause of the cooling water insufficiency that _occurred on November 19, 1981,.and taken corrective action, or have provided alternate assurances that the probability of a similar event occurring has been significantly reduced.

Except during tests which require otherwise, the Unit 3_ diesiH generator will be iined up f9r standby service.

During the period that the Unit 3 diesel generator is inoperable, you will:

1.

Vent the Unit 2 and 2/3 diesel generator cooling water pwnps approximately hourly.

I

2.

Pen:onstrate the operability of the Unit 2/3 diesel generator cooling water

. pum~ at least once per shift by operating the pump; and

3.

Operate the Unit 2/3 diesel generator cooling water pump to demonstrate 6j)erability i~...cdiately following any testing which may introduce air into the system.

ATTACHMENT 1

- *..')'

cmlFlRHATIO~l OF ACTIO!! L:i:TIL::.

Commonwealth Edison Company e NOV 2 0 i]31 Please inform us immediately if your understanding of these actions is different from that stated above.

cc: Louis O. DelGeorge, Director

  • of Nuclear Licensing Mr. D. J. Scott, Station Superintendent.

mm/Document Contra1.tnesk (RIDS)

Resident Inspector, RiII Mary Jo Murray. Office of.

Assistant Attorney General OFFICE~ ---------------


ONF Sincerely, James G. Keppler Regional Administrator


~--~------

1'!00--0F--Aef-

-1:.E'f'fER----- ---------------

SU.RNAME ~ ---------------

DATE~ ----~-*----~------

."-1 :'-,..... ~ ""!

  • m 1 1 Q P I 0 T'TT l I ' * ~ u' "1 '7\\ r., 4 n...,, r\\

.