OPERATING DATA REPORT OPERATING STATUS
- 1.
Unit Name: Dresden I
......;;~---~------------------------------------
- 2.
Reporting Period: January. 1981
- 3.
Licensed Thermal
-P~o~w=e~r=*~(~MW-.-t~)--:.---. 7-0-0--------------------
- 4.
Nameplate Rating (Gross MWe):
209
- 5.
Design Electrical Rating (Net MWe): 200
- 6.
Maximum Dependab.le Capacity (Gross _M_W.;;..e.,...)_:_2_0_5_._...._ __ _
DOC KET NO. _0_50_* -_.O_l-...0 ___ _
DATE" Febr1,1ary 3 I r9;8l COMPLETED BY D. C. Maxwell.
TE*LEPHONE (815) 942-.29,,io~
x..:sso*
NOTES
].
Maximum Dependable Capacity (Net MWe):
197
- 8.
If Changes Occur in Capacity Ratings ""(_l __ t_e_m_.s.__,,.3-.,..,.T,...h-ro_u_g_h,... 7) Since Last Report, Gii/.e, Reasons:
N/A
- 9.
Power Level to Which Restricted, If Any (Net MWe):
NA
--'""'-'~--------------------------~
- 10.
Reasons For Restrictions, If Any:
N/A
--~;,;_-------------------------------------------,--c
- 11.
- 12.
l 3.
- 14.
- 15.
- 16.
- 17.
- 18.
- 19.
- 20.
- 21.
- 22.
- 23.
- 24.
Hours in Reporting Period Number of Hours Reactor Was Critical Reactor Reserve Shutdown Hours Hours Generator On-Line Unit Reserve Shutdown Hours Gross Thermal Energy Generated (MWH)
Gross Electrical Energy Generated (MWH)
Net Electrical Energy Generated (MWH)
Unit Service Factor Unit Availability Factor Unit Capacity Factor (Using MDC Net)
Unit Capacity Factor (Using DER Net)
Unit ~orced Outage Rate Shutdowns Scheduled Over Next 6 Months N/A This Month Yr-to-Date EXTENDED MODIFICATION OUTAGE (Type, Date, and Duration of Each):
- 25.
If Shut Down At End Of Report Period, Estimated Date of Startup: Extended Modification Outage - Shutdown Until June, 1.986 8102190511
OPERATING DATA REPORT OPERATING STATUS
- l.
Un it Name:
Dresden II
- 2.
Re po rt i ng Period : _J_a_n_u_a~r_._y_,_,_1_9_8_1 ___________ _
- 3.
Licensed Thermal Power (MWt):
2527
- 4.
Nameplate Rating (Gross M\\.Je):
, 828
-'-"-~----------
5, Design Electrical Rating (Net M\\.Je): 794
- 6.
Maximum Dependable Capacity (Gr:oss -M-'-\\*/-'-e""")-:-8.-L-2 ____ _
DOC KET NO. ~0;;._5 0;;._-_;;2~3""'7 ---.~-
DATE. Febru13.r:y 3,. 19,8J, COMPLETED BY D. C. M~xw¢J)
TELEPHONE (815) 9.42.;...,z9:2,p*
NOTES
- 7.
Maximum Dependable Capacity (Ne*t M\\.Je) :....,.....~7~7=2 _____ _
- 8.
If Changes Occur in CapacityRatings (Items 3 Through 7) Since Last Report, Give Reasons:
N/A
- 9.
Power Level to \\.Jhich Restricted, If Any (Net MWe):
NA l O.
Reasons For Restrictions, If Any:
N/A
- 11.
- 12.
l 3.
- 14.
1 s.
- 16.
- 17.
- 18.
- 19.
- 20.
- 21.
- 22.
- 23.
- 24.
Hours in Reporting Peri6d Number of Hours Reactor Was Critical Reactor Reserve Shutdown Hours Hours Generator On-Line Unit Reserve Shutdown Hours Gross Thermal Energy Generated (MWH)
Gross Elect r i ca 1 Energy Generated (M\\.JH)
Net Electrical Energy Generated (MWH)
Unit Service Factor Unit Availability Factor Unit Capacity Factor (Using MDC Net)
Unit Capacity Factor (Using D.ER Net)
Unit Forced Outage Rate Shutdowns Scheduled Over Next 6 Months Presently in a Refueling Outage This Month Yr-to-Date 744 744 73.817
- 73. 817 0
0 69.400 69.400 0
0 74675 74675 22045 22045 17222 17222 9.328 9.328 9.328 9.328 2.998 2.998
- 2. 915 2.915
---~0~*~0~0~0-0.000 (Type, Date, and Duration of Each):
Curriula.t ive.
93,-98;4 73211.700 6
695.29. 45.o 137.37i731 43894.9:08 41486221 73.980 73.98"0 5 7' 17.8 55.594 12.519
- 25.
If Shut Down At End Of Report Period, Estimated Date of Startup: Approximately April 25, 1981
- l.
- 2.
- 3.
- 4.
5,
- 6.
. 7.
- 8.
OPERATING DATA REPORT OPERATING STATUS Unit Name:
Dresden III Reporting Period: January, 1981 Licensed Thermal
-P-o-'w"""e-r~(_,,.M_.W._t.,...)-:-2--5 __ 2 __ 7 _________ _
Nameplate Rating (Gross M\\.Je):
828
-~~--,---------
Design Electrical Rating (Net M\\~e): 794 Maximum Dependable Capacity (Gross _M...;_\\.J..;;..e""")-:-8.-1-2 ____ _
Maximum Dependable Capacity (Net M\\.Je):
77.3 DOCKET NO. 050"'."2.49
~-------~----,---c DATE February 3, 1~'$1 COMPLETED BY D. C. Maxwe Ll._
THEPHONE (815) 942-:-292.0..
NOTES I
I I
If Changes Occur in Capacity Ratings...,(,...1.-t_e_m_s'""'"*-3-T_h_r_o_u_g_h 7) Since Last Report, G-iv;e Reasons:
N/A
~. ~*..
- 9.
Power Level to \\*Jhich Restricted, If Any (Net MWe):
N/A
-;....:...'----------------'--(
- 10.
Reasons For Restrictions, If Ariy: N/A
--'---------------------------'-~
1 1.
- 12.
- 13.
- 14.
- 15.
- 16.
- 17.
- 18.
- 19.
- 20.
- 21.
- 22.
- 23.
- 24.
Hours in Reporting Period Number of Hours Reactor Was Critical Reactor Reserve Shutdown Hours Hours Generator On-Line Unit Reserve Shutdown Hours Gross Thermal Energy Generated (MWH)
Gross Electrical Energy Generated (MWH)
Net E 1 ect r i ca 1 Energy Generated (t1WH)
Unit Service Factor Unit Availability Factor Unit Capacity Factor (Using MDC Net)
Unit Capacity Factor (Using DER Net)
Unit Forced Outage Rate Shutdowns Scheduled Over Next 6 Months None This Month 744 729.317 0
714.267 1593308 0
498747 96.004 96.004 86.722 84.428 2.999 (Type, Date, and Yr-to-Da*te CuruuJat i. y.e, 744 83569 729.317 63016.. 450. c 0
. 0.
714.267 6034 i. 56 7 0
1593308 118.onns 0
498747
%521647 96 *. 004 72.* 2.13 96.004
- 72. 2t3 86.722 56.5.36 84.428 55.041 2.999 15.120 Du rat ion of Each):
- 25.
If Shut Down At End Of Report Period, Estimated Date of Startup:
N/A
AVERAGE DA It Y UN IT POWER LEVEL
- MONTH JANUARY, 1981 DAY 2
3 4
5*
6 7
8 9
10 11 12 13 14*
15
- 16.
AVERAGE DAILY POWER (MWe-Net) 0 0
0 0
0 0
0 0
0 0
0 0
0 LEVEL DAY 17 18 19 20 21 22 23 24 25 26 27 28 29
~** *.
DOCKET NO. oso~o10 UIH T Dr.e*~den I DATE February 3, 1981 COMPLETED BY D. C. Maxwell TELEPHONE (815) 942-2920 AVERAGE DAILY PO\\~ER LEVEL (M\\*Je-Net) 0 0
0 0
0 0
0 0
0 0
0 0
AVERAGE DAILY UNIT POWER LEVEL MONTH JANUARY, 1981 MY AVERAGE DAILY PO\\.JER LEVEL DAY (M\\.Je-Net) 291 17 2
300 18 3
255 19 4,
0 20 5
0 21 6
0 22 7
- 0.
23 8
0 24 9
25 1 o.
26 11 0
27 12 0
28 13 0
29 14 0
30 15 0
31 16 0
DOCKET NO. 050.-237 Ufl IT Dre sci.en II DATE February 3, 1981 COMPLETED BY D. C.
M~xwell TELEPHO~E (815) 942~2920
.AVERAGE DAILY PO.WER LEVEL (M\\~e-Net)
- 0.
0 0
0 0
0:
0 0
- o 0
0 0
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050~249 UfJ IT Dresden III DATE February 3,. 1981 COMPLETED BYD. C. Maxwell TELEPHONE ($15) 942-2920 MOIHH JANUARY, 1981 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DA I LY PO\\JER LEVEL (MWe-Net)
(M\\Je-Net) 613 17 789.
2 303 18 692 3
523 19 772 4
628 20 787 5
165 21 787 6
486 22 794 7
634 23 794 8
725 24 768 9
25 l 0 26 l l 255 27 8
12 560 28 79fr 13 712 29 791 14 742 30 788 15 782 31 788 16 787
NO.
DATE TYPEl 8.
781031 s
1 2
F; Forced S:
Scheduled UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH JANUARY I 1981 METHOD OF DURATION REASON2 SHUTTING (HOURS)
DOWN REACTOR3 744 c
3 Reason:
A-Equipment Failure (Explain)
B-Maintenance of Test C-Refueling D-Regulatory Restriction LICENSEE EVENT REPORT fl E-Operator Training ~ License Examination F-Admintstrative G-Operation~i Error H-Other (Explain) 3 SYSTEM COMPONENT CODE4 CODES
\\
Method:
1-:Manual 2-Manuai Scram 3-Automatic Scram 4-0ther (Expl~in)
DOCKET NO. 050-010 UNIT NAME-D--re--sd_e_n __ I ________ _
DATE February 3, 1981 COMPLETED BYD. C. Maxwell TELEPHONE (815) 942-2920, X550 CAUSE & CORRECTIVE ACTION TO PREVENT RECURRENCE Refueling and chemical cleaning outage.
4 Exhibit G-Instructions for Preparation of Data Entry Sheets for Licensee Eyent Report (
) Fil~
NO.
DATE TYPEl 14 810103 s
1 2
F:
Forced S:
Scheduled UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH JANUARY, 1981 METHOD OF DURATION REASON2 SHUTTING (HOURS)
DOWN REACTOR3 674:36 c
2 Reason:
A-Equipment Failure (Explain)
B-Maintenance of Test C-Refueling D-Regulatory Restriction LICENSEE EVENT REPORT j}
E-Operator Training & License Exa~ination F-Administrative G-Operational Error H-Other (Explain) 3 SYSTEM COMPONENT CODE4 CODES Method:
1-Manual 2-Manual Scram 3-Automatic Sc.ram 4-0ther (Expl~in)
DOCKET NO. 050-237 UNIT NAME_D_r_e_s_d_e_n_I_I ___ _
DATE February 3, 1981 COMPLETED DY D. C. Maxwell TELEPHONE (815) 942-2920, X550 CAUSE & CORRECTIVE ACTION TO PREVENT RECURRENCE and turbine overhaul Refueling outage.
4 Exhi~it G-Instructions for Preparation of Data Entry Sheets for Licensee Event Report (
) File (Nl}REG-0161)
~
~ t
-~
ti
~:
f f
- ~:*1~
- ~~{
NO.
DATE TYPEl 18 810101 F
19 810105 F
20 810111 s
1 2
F:
Forced S:
Scheduled UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH JANUARY, 1981 METHOD OF DURATION REASON2 SHUTTING (HOURS)
DOWN REACTOR3 9:55 A
3 12: 10 A
3 7:39 A
1 Reason:
A-Equipment Failure (Explain)
B-Maintenance of Test C-Refueling D-Regulatory Restriction LICENSEE EVENT REPORT {}
E-Operator Training & License Examination F-Administrative G-Operational Error H-Other (Explain) 3 S~STEM COMPONENT CODE4 CODES Method:
1-Manual 2-,Manual Scram 3-Automatic Scram 4-,0ther (Expl,in) 3A Hi 3A Hi DOCKET NO._0_5_0_-_2_4_9 ____ _
UNIT NAME Dresden III DATE February 3, 1981 COMPLETED BYD. C. Maxwell TELEPHONE (815) 942-2920, X550 CAUSE & CORRECTIVE ACTION TO PREVENT RECURRENCE Moisture Separator Tank Hi water level.
Moisture Separator Tank Hi water level.
Repair two (2) fast-acting s6lenoids on #2 C.I.v.*
4 Exhibit G-Instructions for Preparation of D~ta Entry Sheets for Licensee Event Report (
) File (NUREG-0161)
EQUIPMENT NATURE OF MA I llTENANCE Stack Gas Moni-Preventive WR #9578 tor DRESDEN UNIT 1 SAFETY RELATED MA I NTENAl~CE :- JANUARY, 1981 LER OR OUTAGE NUMBER MAL FUN.CT I ON*
CAUSE RESULT N/A N/A CORRECTIVf~ACTION Repaired lSOV pow~r supply & replaced log count meter.
EQUIPMENT NATURE OF MA I llTENAl~CE CRD's E-3 & D-9 Preventive WR 1f10447 APRM Rod Block Preventive WR #10508
& Scram LPRM 40-09B Preventive WR #9040 LPRM 32-49B (Ch. 1Fl)
Preventive WR #7460 Drive 6-43 Sera~ Corrective WR #10523 Discharge Valve Scram Inlet Corrective WR #10491 Valve CRD 54-19 Accurn. 18-19 Corrective WR #10524 Scram Discharge Valve LPRM G-1 24-25D Preventive WR #9436 LPRM 32-49D APRM 3 LPRM 16-09C APRM 6 Refuel Grapple Refuel Grapple Preventive WR #9634 Preventive WR #9660 Preventive WR #11117 Preventive WR #10987
.~~
Refuel FlOor Preventive WR #10964
~' Outside Inter-lock Door ORES OEN UN IT 2 SAFETY RELATED MAINTENAl~CE -
JANUARY, 1981 MAL FUN CT I Otl
- LER OR OUTAGE NUMBER C/\\USE RESULT N/A N/A N/A N/A N/A N/A N/A N/A Valve Stern Loose Leaked at Fitting Valve*. Ste~rn Loose Leaked at Fitting Valve *,steaTf! Loose Leaked at Fitting
. N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
-WI!>:
N,/A.
CORRECTIVt~ACTION Installed & removed jumpers for scram testing Lowered APRM rod block
& scram setpoirits bye Checked per procedures -
no faults.
Checked per procedures -
no faults:
Adjusted. valve stern
- down one turn.
Adjusted valve stern down.one turn.
Adjusted valve stern
- do.wn one turn.
Checked per procedur-no faults.
Checked per procedure -
no faults.
.~.
Checked per procedure -
- t.
no faults.
- ~
- /,
.. ', rt{f Adjusted track switcp.
- ~;~
f;~~
.. -.. *~i~c,,
Adj:µst~d lo~d -c~.11.
1~f 1t;~;*:.e.* ~~~;*~*~~c,k -:,.c;~I
EQUIPMENT Rx Bldg./Turb.
Bldg. Inter-lock Door 2A Rx Bldg.
Vent Outboard Isolation Valve Rx Bldg; Vent System CRD Accum 34-1.'.:
Interlock Door Torus Manway Reducer Bushing for Snubbers Drywell Cover Rx Head Refuel Grapple Drywell Equip.
Hatch CRD Hatch NATURE OF MA lllTENAl~CE.
Corrective WR #11027 Corrective WR #10845 Corrective WR #3153 Preventive WR 1/:10833 Corrective WR 1/:10836 Preventive WR #9182 Prevet)tive WR #8424 Preventive WR #9187 Preventive WR #9185 Preventive WR #11020 Preventive WR #9192 Preventive WR #9180
\\
DRESDEN UN IT 2 SAFETY RELATED MAINTENAl~CE -
JANUARY, 1981 LER OR OUTAGE NUMBER MAL FUN CT I OU*
CAUSE RESULT CORRECTIVf~ACTION Broken Bolts Door Not Operating Replaced 2 broken bolts.
Bad Coil Leaking Pilot Sole noid & Miller Pis.ton Operator N/A Magnet Failing N/A N/A N/A
. N/A N/A N/A N/A J
Valve Wol1ld Not Open Solenoid Blowing Air & Valve Stuck Closed
- N/A Door Won't *close N/A N/A N/A N/A N/A N/A N/A Replaced coil.
Repaired piston & re-placed solenoid.
Replaced accumulator.
Replaced magnet.
Opened manways.
Fabricated bushings.
Removed cover per pr_A cedure.
W Removed Rx head per.
pro~edure.
Replaced ba4 section of \\
snu])ber hose in ~ir l:i-ae:~:~
Opened hatch.
Op,ened hatch. -
EQUIPMENT Spare 2/3 CRD Ser. 418227 2/3 DG Inter-lock Refuel Floor Rx Bldg.
Interlock DG Room Door Lock
.spare 2/3 CRD 418960 Spare 2/3 CRD 1!2248 Spare 2/3 CRD 11276 7 Spare 2/3 CRD 118793 NATURE OF MAlllTENANCE Preventive WR 418357 Corrective WR 4110443 Preventive WR 4110423 Preveritive WR 4110327 Preventive WR 418356 Preventive WR 418358 Preventive WR 418354 Preventive WR 418355 DRESDEN UNIT ~/3 SAFETY RELATED MAINTENANCE - JANUARY, 1981 MA~FUNCTION*
LER OR OUTAGE NUMBER CAUSE RESULT N/A N/A CORRECTIVf~ACTION Assembled.frQm spare parts.
Door *Latch Defective Door Sticks Open Replaced latch.
. N/A N/A Adjusted limit switch.
N/A N/A Adjusted door latch.
N/A N/A Assembled from spare parts.
N/A N/A Ass em.I:> led from spare parts.
N/A N/A Assembled from spare par.ts.
- N/A N/A A~sembled from sp~re e parts.
DRESDEN UN IT 3 SAFETY RELATED Hi\\ I NTENl\\NC E -
JANUARY, 1981 NATURE OF LER OR OUTAGE MALFUNCTI OU EQUIPMENT MA I llTENANCE NUMBER CAI.JS E RESULT CORRECTIVf~ACTION HPCI Turning Preventive WR 118138 N/A N/A Replaced bad contact &
Gear Interlock rewired.
Relay Outlet Scram Corrective WR 1Fl0506 Valve Stem Loose Valve Stem Leaked Tightened one turn. e Valve CRD C-7 (l0-27) 3B LPCI *Heat Preventive WR 1f7642
- N/A N/A Plugged 4 tubes & in-Exchanger stalled new head gasket.
3C ccsw Pump Corrective WR 1f10351 Broken Nipple In Sprays ).,1 2
When Replaced nipple & ~ gate Casing Pump is Off valve.
Scram Outlet Corrective WR 1Fl0796 Valve Stem Loose Valve Stem.Leaked Ti$htened one turn.
Valve Ac cum.
10-51 Scram Outlet Corrective WR #10795 Valve Stem.Lopse Valve Stem Leaked Tightened one turn.
Valve Ac cum.
26-11
~
Scram Outlet Corrective WR 1f10794 Valve* Stem Loose Valve Stem Leaked Tightened one turn. e Valve Accum.
18-15 Scram Outlet Corrective WR 1110793 Valve Stem Loose Valve Stem Leaked Tightened pne turn.
Valve Ac cum.
10-35
. ~:
2301-64 AO Vlv.
Corrective WR 1fl0742 Valve* Did Not Close Faulty Air.
Replaced same.
- .r
- '. ~.
in Line 2301-3 Diaphragm
- ,{
1.
_j, U-3 Diesel Gen.
Preventive WR #10456 N/A N/A Performed SE;!mi-=annual
)
.,,.;i.
'~
insp~ction.
- .... ~~
D/G Air Start Preventive WR 1H0813 N/A N/~
T.i;ght;~n~q c:ilJ. cpu;p:l in:g'~\\:i~}~
svstem
E<lU I PMENT D/G Air Start System HPCI Stearn Line Drain Po HPCI Oil Filter Yarway Level Switch Valve Block 2D. MSIV Dash Pot CRD Accurn L-2 3D LPCI CCSW Pump RPS MG Set Relay Refueling Grapple Diesel Gen.
Air Start Press. Regu-lator A0-3-1601-23 Valve Iso. Condense MO ).-UQ1-l NATLJP,E OF Ml\\ lllTENAl~CE Corrective WR #10814 Preventive WR #6766 Preventive WR #10422 Corrective WR #6944 Preventive WR #10659 Preventive WR 1tl0732 Preve*n ti ve WR 1tl0261 Preventive WR #9833 Preventive WR #10558 Corrective WR #10746 Preventive WR #10444 Corrective WR #9689 OHESOEI~ UN i T J..
SAFETY RELl\\TF.D M/\\ll~TEl-l1\\l~ct -
JANUARY, 1981 LER OR OUTAGE NUM13ER M/\\LFUMCTIOtl*
CAUSE RESULT Leaking Solenoid Leaking Air Out
.N/A N/A N/A N/A Bad Valve & Gaskets Leaked N/A N/A
. N/A N/A N/A.
N/A N/A N/A N/A N/A Bad.Air Regulat9r Air Leakage N/A N/A CORRECTIVf~/\\CTIOM Replaced solenoid.
Replaced bad valve seat
& disc.
Removed, cleaned, re-~
installed.
Replaced valve & gaskets.
Repacked 0-ring, added oil, repaired set screws.
Changeq fitting on N2 block nipple.
Repa.cked
- pump.
Block relays.
Prepared grapple for transport to. U-2* Rx cavity.
Installed new air regulator.
Defective ~r~?l<e:r
~.reaker Tripped
~epl?c~d br~~ker.
i lfuile 'cxcling Valve
ORESDHI UN IT 3.
SAFETY RELATED MAINTENANCE - JANUARY, 1981 NATURE OF LER OR OUT/\\GE MALFUNCTIOtl EQUIPMENT Ml\\ I JITENAMCE NUMIJER C/\\USE RESULT CRD 58-27 Corrective WR #10946 Valve Stem.Loose Valve Stem Leaked Turbine CV 1t2 Corrective WR 1F11036 Bad Solenoid No Fast Closure Scram Received While Testing Turbine CV 1t3 Corrective WR #11037 J?ad Solenoid No Fast Closure Scram Received While Testing Turbine Con-Preventive WR 1t9626 N/A N/A trol Valves 25.0VDC Bus 3B Preventive WR 4F10128 N/A N/A Drywell Spray Preventive WR 4Fl0627 N/A N/A Valve CRD 38-03 Corre*ctive WR 1tl094 7 Valve *steani Loose Valve Stem Leaked Accum. 50-19 Preventive WR 1Fll062 N/A N/A Interlock Preventive WR 1F11311 N/A N/A Doors MO 3-202-7A Preventive WR 4F11178 N/A N/A Valve I
i CORRECTIVf~/\\CTION Tightened.valve.
Replaced vickers fast closing solenoid.
Replaced vickers fast-*
closing solenoid.
Checked all N~mco limit switches - ok.
RebuHt 2 spare breakers
~ completed ins\\?ection.
Operated 3 times, no problem found.
Tightened valve.
Replaced accum~lator.
Replaced fuse holder. e Back-seated with ammeter.
- ~*~
',fi j.*
r ii l~
~
'*~
{
- t
- s
.f
- ~
):_:*~~~
- r,.._
SUMMARY
OF OPERATING EXPERIENCE UNIT ONE 1-1 to 1-31 JANUARY, 1981 Unit One was shutdown for the entire month, awaiting license approval for the chemical cleaning.
Major work scheduled to be completed following chemical cleaning is as follows:
HPCI installation for ECCS upgrading, equip-ment upgrade to IEEE 279, major in-service inspection, and refuel.
1-1 to 1-3
SUMMARY
OF.OPERATING EXPERIENCE UNIT TWO JANUARY, 1981 Unit Two started the month operating at a power level of 350 MWe.
On January 3, at 2124 hours0.0246 days <br />0.59 hours <br />0.00351 weeks <br />8.08182e-4 months <br />, Unit Two was taken off line and conunenced its scheduled refueling outage.
1-4 to 1-31 By the end of the reporting period, all fuel has been removed and maintenance work is being accomplished as scheduled.
The Unit had a capacity factor of 3.55%
and an availability of 9.33%.
SUMMARY
OF OPERATING EXPERIENCE UN.IT THREE 1-1 to 1-2 1-2 to 1-5 1-5 to 1-il 1-11 to 1-31 JANUARY, 1981 Unit Three entered the month at a power level of 695 MWe and load was steadily in-creased at 5 MWe per hour throughout the day.
At 2050 hours0.0237 days <br />0.569 hours <br />0.00339 weeks <br />7.80025e-4 months <br />, the reactor auto-matically scrannned because of a hi-hi water level in the 3A Moisture Separator Drain Tank.
The reactor was brought critical at 0410 hours0.00475 days <br />0.114 hours <br />6.779101e-4 weeks <br />1.56005e-4 months <br /> and the Unit was placed in service at 0645 hours0.00747 days <br />0.179 hours <br />0.00107 weeks <br />2.454225e-4 months <br /> on January 2, reaching a power level of 705 MWe.
On January 5, at 0024 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, the reactor automatically scranuned because of a hi-hi water level in the 3A Moisture Separator Drain Tank.
The reactor was made critical at 0745 hours0.00862 days <br />0.207 hours <br />0.00123 weeks <br />2.834725e-4 months <br /> and the Unit was placed in service at 1234 hours0.0143 days <br />0.343 hours <br />0.00204 weeks <br />4.69537e-4 months <br /> on January 5, reaching a power level of 750 MWe.
On January 11, the turbine was manually tripped off the line to repair two (2) fast-acting sole-noids of the #2 C.I.V. (the reactor remained critical).
The Unit was placed in service at 1756 hours0.0203 days <br />0.488 hours <br />0.0029 weeks <br />6.68158e-4 months <br /> on January 11 and operated during the remainder of the month, reaching a power level of 833 MWe with a capacity factor of 84.67% and an avail-ability of 96.00%.