ML17158A724

From kanterella
Jump to navigation Jump to search

Discusses Util Response to Rai.Informs That 950327 Response Package Acceptable & Requests Schedule for Completion of All Corrective Actions Identified & Addl Info Concerning Ampacity Derating for Response Package of 941222
ML17158A724
Person / Time
Site: Susquehanna  
Issue date: 06/13/1995
From: Poslusny C
Office of Nuclear Reactor Regulation
To: Byram R
PENNSYLVANIA POWER & LIGHT CO.
References
GL-92-08, GL-92-8, TAC-M85613, TAC-M85614, NUDOCS 9506280240
Download: ML17158A724 (7)


Text

June 13, 19'.

Mr. Robert G.

Byram Senior Vice President-Nuclear Pennsylvania Power and Light Company 2 North Ninth Street Allentown, PA 18101

SUBJECT:

FOLLOWUP TO THE RE(UESTS FOR ADDITIONAL INFORMATION (RAI) REGARDING GENERIC LETTER (GL) 92-08, SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1

AND 2 (TAC NOS.

M85613 AND H85614)

Dear Hr. Byram:

The staff has completed its review of Pennsylvania Power Im Light Company's (PP8L)

December 22,

1994, and March 27,
1995, responses to the staff's requests for additional information concerning GL 92-08, "Thermo-Lag Fire Barriers."

Based on that review, the staff has determined that the March 27, 1995 response package is acceptable;

however, the December 22, 1994 response has been found to be incomplete.

Specifically, you need to provide a schedule for completion of all corrective actions identified by your analysis and testing effort in response to this GL, and you must also provide additional information concerning ampacity derating.

Specific details are discussed in the attachment to this letter.

Please provide a revision to the December 22, 1994 response within 45 days of receipt of this letter.

If you have any questions concerning this RAI, please contact me on (301) 415-1402 or E. Connell at (301) 415-2838.

This request affects 9 or fewer respondents, and therefore, is not subject to Office of Management and Budget review under P.L.96-511.

Docket Nos.

50-387/388

Enclosure:

RAI cc w/encl:

See next page DISTRIBUTION Sincerely,

/s/

Chester

Poslusny, Project Manager Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulations C)ocket=F"i-1:e-PUBLIC PDI-2 Reading SVarga JZwolinski JStolz CPoslusny MO'Brien EConnell CHcCracken OGC ACRS
JWhite, RGN-I OFFICE NAME DATE P

-2/LA PDI-2 PM

/

/95

/

5

/

CPoslusny:rb PDI-2 D

JStolz 6'i( i95 OFFICIAL RECO COPY DOCUMENT NAME:

SUS5Fi13. RAT 950b280240 950bi3 PDR ADOCK 05000387 F

PDR

June 13, 19 Hr. Robert G.

Byram Senior Vice President-Nuclear Pennsylvania Power and Light Company 2 North Ninth Street Allentown, PA 18101

SUBJECT:

FOLLOWUP TO THE REQUESTS FOR ADDITIONAL INFORMATION (RAI) REGARDING GENERIC LETTER (GL) 92-08, SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1

AND 2 (TAC NOS.

H85613 AND H85614)

Dear Hr. Byram:

The staff has completed its review of Pennsylvania Power 5 Light Company's (PPKL) December 22,

1994, and March 27,
1995, responses to the staff's requests for additional information concerning GL 92-08, "Thermo-Lag Fire Barriers."

Based on that review, the staff has determined that the March 27, 1995 response package is acceptable;

however, the December 22, 1994 response has been found to be incomplete.

Specifically, you need to provide a schedule for completion of all corrective actions identified by your analysis and testing effort in response to this GL, and you must also provide additional information concerning ampacity derating.

Specific details are discussed in the attachment to this letter.

Please provide a revision to the December 22, 1994 response within 45 days of receipt of this letter.

If you have any questions concerning this RAI, please contact me on (301) 415-1402 or E. Connell at (301) 415-2838.

This request affects 9 or fewer respondents, and therefore, is not subject to Office of Management and Budget review under P.L.96-511.

Docket Nos.

50-387/388

Enclosure:

RAI cc w/encl:

See next page DISTRIBUTION Sincerely,

/s/

Chester

Poslusny, Project Manager Project Directorate I-2 Division of Reactor Projects I/II Office of Nuclear Reactor Regulations Docket File PUBLIC PDI-2 Reading SVarga JZwolinski JStolz CPoslusny MO'Brien EConnell CHcCracken OGC ACRS
JWhite, RGN-I OFFICE NAME DATE P 3-2/L l

"/

/95 PDI-2 PM CPoslusny:rb

/

95 PDI-2/D JStolz 6( /95 OFFICIAL RECO COPY DOCUMENT NAME:

SU85613.RAI

f V'

~I

~

gP,Q RE00 0

Cy 00 IlO R

+

~O

++*++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555<001 June 13, 1995 Hr. Robert G.

Byram Senior Vice President-Nuclear Pennsylvania Power and Light Company 2 North Ninth Street Allentown, PA 18101 SUBJECT'OLLOWUP TO THE REQUESTS FOR ADDITIONAL INFORMATION (RAI) REGARDING GENERIC LETTER (GL) 92-08, SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1

AND 2 (TAC NOS.

M85613 AND H85614)

Dear Hr. Byram:

The staff has completed its review of Pennsylvania Power

& Light Company's (PP&L) December 22,

1994, and March 27,
1995, responses to the staff's requests for additional information concerning GL 92-08, "Thermo-Lag Fire Barriers."

Based on that review, the staff has determined that the March 27, 1995 response package is acceptable;

however, the December 22, 1994 response has been found to be incomplete.

Specifically, you need to provide a schedule for completion of all corrective actions identified by your analysis and testing effort in response to this GL, and you must also provide additional information concerning ampacity derating.

Specific details are discussed in the attachment to this letter.

Please provide a revision to the December 22, 1994 response within 45 days of receipt of this letter.

If you have any questions concerning this RAI, please contact me on (301) 415-1402 or E. Connell at (301) 415-2838.

This request affects 9 or fewer respondents, and therefore, is not subject to Office of Management and Budget review under P.L.96-511.

Sincerely, R

P~

Chester

Poslusny, Proj ct Manager Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulations Docket Nos.

50-387/388

Enclosure:

RAI cc w/encl:

See next page

V

'V~

Mr. Robert G.

Byram Pennsylvania Power

& Light Company N

Susquehanna Steam Electric Station, Units 1

& 2 CC:

Jay Silberg, Esq.

Shaw, Pittman, Potts

& Trowbridge 2300 N Street N.W.

Washington, D.C.

20037 Bryan A. Snapp, Esq.

Assistant Corporate Counsel Pennsylvania Power

& Light Company 2 North Ninth Street Allentown, Pennsylvania 18101 Mr. J.

M. Kenny Licensing Group Supervisor Pennsylvania Power

& Light Company 2 North Ninth Street Allentown, Pennsylvania 18101 Mrs. Maitri Banerjee Senior Resident Inspector U. S. Nuclear Regulatory Commission P.O.

Box 35 Berwick, Pennsylvania 18603-0035 Mr. William P. Dornsife, Director Bureau'of Radiation Protection Pennsylvania Department of Environmental Resources P.

O.

Box 8469 Harrisburg, Pennsylvania 17105-8469 Mr. Jesse C. Tilton, III Allegheny Elec. Cooperative, Inc.

212 Locust Street P.O.

Box 1266 Harrisburg, Pennsylvania 17108-1266 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, Pennsylvania 19406 Mr. Harold G. Stanley Vice President-Nuclear Operations Susquehanna Steam Electric Station Pennsylvania Power and Light Company Box 467 Berwick, Pennsylvania 18603 Mr. Herbert D. Woodeshick Special Office of the President Pennsylvania Power and Light Company Rural Route 1,

Box 1797 Berwick, Pennsylvania 18603 George T. Jones Vice President-Nuclear Engineering Pennsylvania Power and Light Company 2 North Ninth Street Allentown, Pennsylvania 18101 Dr. Judith Johnsrud National Energy Committee Sierra Club 433 Orlando Avenue State College, PA 16803 Chairman Board of Supervisors 738 East.Third Street

Berwick, PA 18603

SUS(UEHANNA STEAM ELECTRIC STATION UNITS 1&2 DOCKET NOS. 50-387, 50-388 FOLLOWUP TO REQUEST FOR ADDITIONAL INFORMATION REGARDING GENERIC LETTER 92-08 "THERMO-LAG FIRE BARRIERS" September 23,

1994, Request for Additional Information The RAI dated September 23,
1994, requested information regarding important barrier parameters, Thermo-Lag barriers outside the scope of the NEI, program, ampacity derating~

and schedules.

In the licensee's response dated December 22, 1994,. a schedule for the completion of corrective actions necessary for the resolution of the Thermo-Lag issue was not provided.

A schedule for completion of all corrective actions is requested.

During the public meeting held on March 14, 1995, with the licensees for the four lead plants for the resolution of Thermo-Lag issues, the staff responded to the question "Will the resolution of the ampacity derating concern be deferred until agreement is reached on the appropriate testing protocol(i.e.,

IEEE P848)?"

The staff reiterated the position which was previously stated in the September 1994 RAI, that the ampacity derating concern could be resolved independently of the fire endurance concerns.

At this time the staff is not

'aware of any NEI initiative to address the ampacity derating issue.

After a review of.the tests which were performed under the draft IEEE standard

P848, the staff transmitted comments which were designed to ensure the repeatability of test results to the IEEE Working group responsible for the test procedure.

The licensee 'is requested to submit it's ampacity derating evaluations, including any applicable test reports in order to provide an adequate response to. Generic Letter 92-08 reporting requirement 2.(c).

ENCLOSURE