Steam Leak Detection Calculation - RWCU Penetration Room (I-501),Pump Rooms (I-502/503) & Heat Exchanger Rooms (I-504/505),Unit 1 Only
ML17157A808
Person / Time
Site: Susquehanna 
Issue date: 04/30/1990
From:
PENNSYLVANIA POWER & LIGHT CO.
To:
Shared Package
ML17157A805 List:
References
M-SLD-005, M-SLD-5, NUDOCS 9108260192
Download: ML17157A808 (138)


Text

I

~

~

CALCULATION COVER SHEET CALC.

NO. -5e-os.

FILE NO. R2=l SUPERSEDED BY N/S, SAFETY-RELATED Qc]

ASNE III OR XI f ]

OTHER QUALITY [ ]

NON QUALITY f

1 PROJECT S'TEA+ LEAl< DETECT'I OAJ PCo J K<V ER/CTN NO, hl A DESIGN ACTIVITY/PNR NUMBER Ku/R. + HSloOO PAGE I OF ~~Cp5

.TITLE/DESCRIPTION GT~

LEAIC. DETECTlcs~ C4~ -

RQJCU ET' EJ Boo z.-sol u&p Roosts z-s'02 503 HwW KxcÃAQ&~g.eoMG z=sz)4. sos Ov<T I oQi SYSTEMS AFFECTED 5 O 'EE 8 6 5 o 6 1

REFERS Tcs PA< e-3 Fo~ sTA,TElvlE.M> ol"-FRoet avf

~

gE'F~ ~ AVTAcQEO GKS16h3 INPUTS @~ERAfKD Fbd-THIS CALCVLAPW.

Rm~ ~ PAGFS Z R4 F:oa Re=a~e&S,.

REAna-Yo PASS l2. Po& Suolhtkc Y Ious)c.t.uS<omS

~

l!0 CU I

CT I

F.

(ETO)

BINDER AFFECTED?

t. ] YES-If Yes enter:

Binder 8 Cal c. File Vol.

Pgs.

tD Lr REV.

NO.

DATE

'Q 2-l-9o 9-29-'Po NO PREPARED BY REVIEMED/CHECKED BY DATE APPROVED BY DATE f22~//0 mls/frb006i (12)

I 9108260192 910819-PDR RDOCK'05000387 P

PDR

I* ~

TABLE OF CONTENTS Calc 4 M-SLD-005 Page 2 of 63 1.0 PURPOSE

2.0 REFERENCES

3.0 ASSUMPTIONS 4.0 METHODOLOGY

~ \\ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~

~

~

~

~

~

~

~

~

6 5.0 RESULTS/CONCLUSIONS 13 The following attachments represent the COTTAP Output from the various runs made for the RWCU Rooms.

1A

& 4A RWCU Penetration Room (I-501) 5 GPM Leak (Summer) 1B

& 4B RWCU Penetration Room (I-501) 5 GPM Leak (Winter) 1C 1D 4C RWCU Penetration Room (I-501) 25 GPM Leak (Summer) 4D RWCU Penetration Room (I-501) 25 GPM Leak (Winter) 2A

& 5A RWCU Pump Room (I-502/503) 5 GPM Leak (Summer) 2B

& 5B RWCU Pump Room (I-502/503) 5 GPM Leak (Winter) 2C 2D 5C RWCU Pump Room (I-502/503) 25 GPM Leak (Summer) 5D RWCU Pump Room (I-502/503) 25 GPM Leak (Winter) 3A

& 6A RWCU Heat Exchanger Room (I-504/505) 3B

& 6B RWCU Heat Exchanger Room (I-504/505) 3C

& 6C RWCU Heat Exchanger Room (I-504/505) 3D

& 6D RWCU Heat Exchanger Room (I-504/505) 5 GPM Leak (Summer) 5 GPM Leak (Winter) 25 GPM Leak (Summer) 25 GPM Leak (Winter)

Note:

Attachments 5A-5D are provided for information only.

The RWCU Pump rooms contain no lines with conditions of 440 F/

1190 psig.

t APPENDIX A APPENDIX B Data Input Section RWCU Rooms (I-501,I-502,I-503, I-504

& I-505)

Addendum-to Calc 5 M-SLD-005, Rev.

0 (All of the above except 5A to 5D rerun for separate ventilation exhaust

AgA

Calc 5 M-SLD-005 Page 3 of 63 The purpose of this calculation is to predict the room temperature profile expected when a small steam leak is introduced in any one of the Unit 1 RWCU Rooms (Room g I-501, I-502,I-503,I-504

& I-505).

The results of this calculation will be used as a basis for development of Steam Leak Detection System setpoints.

Revision 1 of this calculation models the affects of a steam leak in the same Unit 1 RWCU rooms with individual exhaust registers.

The original analysis utilized a common exhaust register located within the Penetration room.

2.0 REFERENCES

2.1 Calc g M-RAF-024, Rev.

0 "RB Post DBA Transient Temperature Analysis" 2.2 Bechtel Calc g 176-18, Rev.

5 "RB Cooling Loads" 2.3 SEA-EE-129, Rev.

0 "SSES Unit 1 and Unit 2 Reactor Building Heat Loads" 2.4 Drawings P&ID M-176, Rev.

20 P&ID M-144 Sht 1, Rev P&ID M-144 Sht 2, Rev V-25-4, Rev.

8 V-25-5, Rev.

13 V-25-6, Rev.

14 V-28-4, Rev.

15 V-28-5, Rev.

21 V-28-6, Rev.

18 M-25-5, Rev.

26 M-28-5, Rev.

20 C-188, Rev.

14 C-199, Rev.

16 C-201, Rev.

15 C-207, Rev.

9 C-209, Rev.

12 C-210, Rev.

17 DBB-122-1, Rev.

5 DBC-101-1, Rev.

13 DBC-102-1, Rev.

12 DBC-103-1, Rev.

6 DBC-104-1, Rev.

7 27

~

1

j1

Calc g M-SLD-005 Page 4 of 63 2.5 2.6 2.7 2.8 2.9 2.10 2.11 EBC-101-1, Rev.

6 EBC-101-2,. Rev.

5 EBC-102-3, Rev.

4 EBC-103-1, Rev.

5 M-199 Piping Class Sheets SEIS Pipeline General Index Crane Technical Paper No.

410, 23rd Printing, 1981 ASHRAE 1985 Fundamentals Handbook FSAR Table 3.11-6 Calc 5 M-PAF-001, Rev.

1 "HVAC Environmental Analysis Reactor Buildings 6 Control Structure" COTTAP-2 Theory and Input Description Manual (User's Manual),

Rev.

1, dated 1/27/89.

2.12 FSAR Figures 5.4-17 a

6 b

t~

, fj

/

1

~J, V(

k 3

Calc 5 M-SLD-005 Page 5 of 63 Plant is operating under normal conditions prior to introducing a steam leak.

All adjacent rooms will be maintained at their design maximum temperature for summer conditions and at the average temperature for the month of January (if blue-box data is available) for winter conditions.

Where winter temperature data is not available, the design minimum temperature of 60 F will be used.

The rooms under consideration will not be allowed to pressurize, as the blowout panel will relieve at approximately 0.5 psid.

Therefore, a leakage path out of the rooms will be used to maintain pressure as close to 14.7 psia as possible.

The temperature effects due to slight room pressurization are assumed to be negligeble.

The effects of adjacent room heatup are not considered in this analysis (i.e. adjacent room temperatures are held constant).

This results in a conservative temperature profile for the room under consideration.

The actual adjacent room heatup due to the steam leak is expected to be minimal (when considering conductive heat losses).

The COTTAP model assumes perfect mixing of the air and steam in the room under consideration.

Refer to APPENDIX B.for a special consideration related to the perfect mixing assumption.

l This calculation considers the following lines as high energy piping Qi RWCU Pump Suction from Vessel RWCU Pump Disch to Regen HX Regen HX to Non-Regen HX Non-Regen HX to Regen HX II II II II II It Regen HX to Feedwater Inlet Feedwater inlet to RX Vessel DBC-101 DBC-102 DBC-103 EBC-101 EBC-102 EBC-103 DBC-104 DBB-122 1025 psig/535 F

1190 II

/535 F

1190

/235 F

1190

/120 F

1190

/120 F

1190

/120 F

1190

/440 F

1190

/440OF For the purpose of this calculation, leaks of subcooled liquid at 235 F and 1204F are neglected.

The energy content of such leaks is considered negligable and probably cannot be detected by the current GE temperature-based leak detection system.

Subcooled liquid at 120 F will not even flash to steam within the RWCU Rooms (at 14.7 psia).

Subcooled liquid at 235 F only-flashes 34 to steam when allowed to expand adiabatically to 14.7 psia.

<~w If 1

Calc I M-SLD-005 Page 6 of 63 The only break conditions analyzed by this calculation are:

a) subcooled liquid at 1025 psig/535 F,

and b) subcooled liquid at 1190 psig/440 F

Section 4.7 discusses the pipe break data used in the COTTAP model.

For breaks of saturated or subcooled liquid (initially), a percentage of the break mass flow flashes to steam at 14.7 psia.

The remaining break mass flow enters the room as saturated liquid at 2124F.

For conservatism, this calculation neglects any heat load associated with the saturated liquid entering the room.

This is considered reasonable, since open floor drains exist in each of the rooms under consideration.

This temperature profile, although conservative, only underpredicts actual expected temperature response by 3 to 5 F (engineering judgement).

Section 4.7 calculates the break mass flow based upon actual conditions in the pipe.

Then, the amount of flashing is determined by allowing these conditions to expand adiabatically to the room pressure of 14.7 psia.

This percentage is applied to the break mass flow to determine the amount of pure steam which enters the room for the conditions being analyzed.

4.0 METHODOLOGY The Compartment Transient Temperature Analysis Program (COTTAP) was used to analyze the affects of a steam leak in various rooms within the plant.

Since the RWCU rooms contain process lines of varying energy conditions, the analysis was performed for two different sets of break conditions.

The first case analyzed a

break for normal conditions experienced at the inlet to the RWCU system (1025 psig/535 F).

The second case considered the lowest possible energy condition which was believed to be detectable by the existing GE temperature-based steam leak detection system (1190 psig/440 F).

All other process lines are of lower energy conditions and were assumed not to be detectable.

The program predicted temperature profiles for the room under consideration with the following set of conditions 1) 5 gpm subcooled water leak (Summer) 2)

5 gpm subcooled water leak (Winter) 3)

25 gpm subcooled water leak (Summer) 4)

25 gpm subcooled water leak (Winter)

The individual room models were developed from various sources of information, as identified in Section 2.0 References.

The RWCU rooms have been modeled as three inter-connected volumes which communicate with each other.

The effects of each leak are considered on all three rooms.

Therefore, the results will consist of 24 separate COTTAP outputs and the associated temperature profiles for the cond'.tions stated above.

The following discussion is provided to outline the steps used in developing the individual room models.

~6-'

4+

a4

~j A!

Calc N M-SLD-005 Page 7 of 63 Rooms Room Volumes Initial Pressure The room volume was taken from Reference 2.1 for the room under consideration.

Adjacent room volumes were set to a large value (i.e.

1.0 EE15 cu. ft.) to maintain constant properties such as temperature, pressure and relative humidity.

All rooms were assumed to be at an initial pressure of 14.7 psia.

Initial Temperature All rooms were assumed to be at their maximum normal design temperature initially for summer conditions.

Actual winter data was used, where available, as a starting point for the winter runs.

The winter data was taken as the "blue-box" average temperature for January 1988.

The January data was considered to be more conservative than February data.

Where actual winter data was not available, the design minimum room temperature of 60 F was used.

Where winter data was not available for the room in question, the room was started at a

temperature which allows it to reach a steady-state with its adjacent rooms.

The outside ambient temperature was taken as 79 F

(summer) and 26 F (winter).

The summer ambient was taken from Reference 2.8 as the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> daily average temperature, based upon the 14 ASHRAE design value for the Wilkes-Barre/

Scranton area.

The winter value was taken as the actual monthly average for January over the years 1986 thru 1989.

This average was based upon SSES Meteorological Data taken from the plant computer.

A comparison of February data over this same time period indicated that the January data was more conservative.

Relative Humidity The relative humidity for all rooms connected by ventilation or leakage paths is based upon outside air temperatures of 92 F

DB / 78 F

WB (summer) and -5 F DB / -5 F WB (winter).

Air at these conditions was then allowed to heat up or cool down (sensible heating/cooling only) to the initial room temperature, and the corresponding RH value calculated or read from the psychrometric chart.

e

.S4 1*,

1 4gh',

+

+7

~C

~4

Room Height Calc g M-SLD-005 Page 8 of 63 This value is no longer used by COTTAP. It' original purpose was associated with the wall condensation calculation used within COTTAP.

COTTAP has been revised and no longer uses this information.

Therefore, a value of 10.0 ft was inputted for each room.

This value has no significance to the calculation.

Note that the actual room height was used in the calculation of room volume.

4.2 Airflow and Leakage Path Data Airflow Data The design airflow is provided for the room under consideration.

All flow paths are identified (i.e. supply, exhaust and transfer air).

The source of the airflow data is the PAID associated with the particular ventilation system for that room.

The data identifies the room from which the air comes, and the room to which the air goes.

A conservative value of 110< design airflow is inputted to the model, since airflows are balanced to + 10%.

Refer to the data input section for the actual values used in this model.

The supply, exhaust and transfer air lines to the RWCU Rooms are equipped with back draft isolation dampers to prevent the spread of steam to adjacent rooms in the event of a high energy line break outside containment.

These dampers isolate at a differential pressure of 5 " WG.

The BDID's are not expected to close due to a steam leak of this magnitude.

Therefore, the model assumes the air flow path remains open throughout this event.

Revision 1 of this calculation models separate exhaust registers for each of the rooms under consideration.

The original analysis utilized a

common exhaust register located within the RWCU Penetration room.

The exhaust from each room was modeled as transfer air supplied to the Penetration

room, where it mixed perfectly prior to exiting the area.

Refer to Appendix A for the specific airflow data changes.

Leakage Path Data As with the airflow data, all rooms connected to the leakage path are identified.

The leakage path area is only used to scale the leakage flowrates for the entire compartment under consideration.

The intent of the leakage

t f

Calc 4 M-SLD-005 Page 9 of 63 path is to prevent compartment pressurization.

The open doorways between the RWCU rooms are modelled as leakage

paths, since these are large areas.

4.3 Heat Load Data Heat Load Type The type of heat load was identified using the following nomenclature Type Description Lighting Electrical Panels Motors Unit Coolers Piping Misc. Mechanical Equipment Heat Input Rate The heat rate input in Btu/hr for the associated heat load.

The values for heat load types 1 thru 3 were obtained from References 2.2

& 2.3.

The heat rate inputs for type 4 heat loads are inputted as negative values since the unit coolers remove heat from the room.

The heat input rate for type 5 heat loads were input as -1.

This value directs COTTAP to obtain piping information necessary to calculate the piping heat loads.

The heat input rate for type 8 heat loads was obtained from References 2.2

& 2.3, as necessary for the appropriate room.

To achieve an initial steady-state condition, a

miscellaneous heat load (positive or negative) was added to the main room to balance all other time zero heat loads.

This heat load was inputted as type 8.

Note that COTTAP neglects cold pipe and equipment as heat sinks.

This represents non-conservatism in this calculation.

A sample run made to determine the effects of these heat sinks indicated that resultant temperatures were only slightly lower than the values predicted when neglecting these heat sinks.

Therefore, this calculation assumes the effects of these heat sinks are negligable.

a

Calc N M-SLD-005 Page 10 of 63 4.4 Piping Input Data Only piping with a design temperature greater than that of the normal room design temperature was included, since COTTAP ignores cold pipe as a heat sink.

This generally meant that piping at or close to Reactor conditions was included.

Also note that this calculation neglects heat loss from small pipe (i.e. less than 2" OD).

Pipe OD The outside diameter of the pipe was obtained from Reference 2.4 Pipe ID The pipe schedule was obtained from Reference 2.5 Knowing the schedule, the inside diameter was obtained from Reference 2.7 Insulation OD The insulation OD was obtained from Reference 2.11 Pipe Length Emmisivity The pipe length was obtained from Reference 2.4 The emmisivity was obtained from Reference 2.11 Insulation k Value The insulation thermal conductivity (k) was obtained from Reference 2.11 Pipe Fluid Temperature The design fluid temperature was obtained from Reference 2.6 Fluid Phase The state of the fluid was determined by reviewing the system P&ID's and design temperatures/pressures.

For this model, the fluid carried within the piping is subcooled water.

4.5 General Data For Thick Slabs Room ID N

on Side 1

The room number on one side of the slab.

Room ID N

on Side 2

The room number on the other side of the slab.

When slab is adjacent to ground, a room 4 of "0" is used.

Thickness The thickness of the slab was obtained from

'Reference 2.4

i4 WL

'-',n

Calc N M-SLD-005 Page 11 of 63 Heat Transfer Area The area of the slab was obtained from Reference 2.4 The dimensions were scaled from plant ventilation drawings.

The slab areas are calculated in the Data Input Section (Refer to Appendix A).

Thermal Conductivity The thermal conductivity of the concrete slabs were obtained from Reference 2.8

, Chapter 23 Table 3A.

A value of 1.0 Btu/hr sq-ftF was used for all concrete slabs.

Density Specific Heat The density of all concrete slabs is assumed to be 140 ibm/cu ft.

This value was obtained from Reference 2.8

, Chapter 23 Table 3A.

The specific heat for-all concrete slabs was assumed to be 0.22 Btu/ibm F as obtained from Reference 2.8

, Chapter 23 Table 3A.

/The type of slab with respect to the room on Side 1 was defined using the following codes t 4.6 Film Coefficient Data For Thick Slabs Type w/r to Room on Side 1

Type 1

Type 2

Type 3

Vertical Wall Floor Ceiling hl 6 h2 All film coefficients (h) for inside walls were calculated by COTTAP.

The film coefficient for walls in contact with outside air were inputted as Summer Winter 4.0 Btu/hr-sq ft-oF 6.0 Btu/hr-sq ft-F (Per Reference 2.8

, Chapter 23, Table 1) 4.7 Pipe Break Data Fluid Pressure The fluid pressure within the pipe (psia).

~ h

Calc N M-SLD-005 Page 12 of 63 Mass Flow The total mass flow exiting the pipe break (ibm/hr) was inputted as follows o

5 gpm subcooled water leak 1040 psia/535 F

5 gal/min x 1 cu t/7.48 gal x 60 min/hr

/.02130 cu ft/ibm = 1883.0 ibm/hr From ASME Steam Tables 9 1040 psia/535 F.:

vf = 0.02130 cu ft/ibm hf = 530.47 Btu/ibm Percentage of flashing 9 1040 psia/535 F:

530.47

= 180.17 (1

x)

+ 1150.5 (x) x = 0.3610 1883.0 x 0.361

= 680.0 ibm/hr pure steam o

25 gpm subcooled water leak 1040 psia/535 F:

5 x 680.0

= 3400.0 ibm/hr pure steam I

o 5 gpm subcooled water leak 1205 psia/440 F:

5 gal/min x 1 cu ft/7.48 gal x 60 min/hr

/.01914 cu ft/ibm = 2100.0 ibm/hr From ASME Steam Tables 9 1205 psia/440 F:

vf = 0.01914 cu ft/ibm 9 1205 psia hf = 419.60 Btu/hr Percentage of flashing 9 1205 psia/440 F:

419.60

= 180.17 (1

x)

+ 1150.5 (x) x = 0.2468 2100.0 x 0.2468

= 517.0 ibm/hr pure steam o

25 gpm subcooled water leak 1205 psia/440 F:

5 x 517.0 ibm/hr = 2585.0 ibm/hr pure steam The break occurs at t=0.5 hrs.

This allows the room to reach equilibrium conditions prior to initiation of the break.

In all room models, the break mass flow is allowed to increase linearly (ramp) from 0 ibm/hr to its maximum value over 0.1 hrs.

) I t:4=

Lo bs

Calc I M-SLD-005 Page 13 of 63 RESULTS/CONCLUS IONS The following pages provide the temperature profiles resulting from the RWCU Room models for the conditions stated below 1) 5 gpm subcooled water leak (Summer) 2)

5 gpm subcooled water leak (Winter) 3)

25 gpm subcooled water leak (Summer) 4)

25 gpm subcooled water leak (Winter)

The COTTAP output for each case above can be found as Attachments 1A thru 6D, respectively.

Each output provides a summary of the data input, and the results of each time step within the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run time.

At the end of each COTTAP output, a summary table of Temp vs Time information is also provided.

APPENDIX B provides an Addendum to Calc g M-SLD-005, Rev.

0 The addendum reanalyzes a steam leak in each room utilizing separate ventilation exhausts.

The original analysis modelled the ventilation system with a common exhaust register in the RWCU Penetration room.

Although the actual installed system utilizes a

common exhaust, the model assumes all the transfer air from the Pump/Heat Exchamger rooms mixes perfectly with the Penetration room air.

The location of the exhaust register suggests that this mixing would only occur in a very localized part of the room.

The previous results tended to dilute the affects of a steam leak within the Penetration room.

The Penetration room was also very sensitive to steam leaks in the Pump/Heat Exchanger rooms.

The results of Revision 1 indicate that the temperature profile is significantly higher than the original analysis for the RWCU Penetration room.

The RWCU Pump/Heat Exchanger rooms did not experience any significant changes as a result of modelling individual exhaust registers.

These results were expected, since the Penetration room response was diluted by the transfer air from the Pump/Heat Exchanger rooms.

Refer to APPENDIX B for the results of the new analysis.

The output is provided in a similar manner to that of the original

analysis, as stated above.

hlbke:

cwing &c, tv'<cio<

I ted'cuJ

@)dan >'tb vdas dcferwllwe'~ Wag %e rn>Me((aceous ra~~+

lcm.ds ~i~d cuba.~gc

. S+ody -Ax&

gee not attain 4 poor + lnkociuc<g 5gnjv on(~ ~e pevveivtLhovl Roovn ooee slant fleILK'fQ g.[( ~~5 Lnyolv L~

a-I~4-(vl Ki5 voo vA rerun (veenHs inc(~ in ~<<ev)

Tive vemnini~ <O.ee<

ge e eo+rerv~ H save hme t si~~ +c.m ~ops wc.w no4

~ ~ee vevne<n<no eeeee i t4!, Room i'S ov~p~i C'd 4) epp eiee ~

S 'F.

I

The fo(laud<<g 24 popes aYe <<~~~~

Q~ ~e yarns Q,

102.S'+ig / ~3~

F (Isaac. conditions).

These, ~s~lhs ave.

gho<n in (paphian.a,l and %4ulc r QiwL(geV. O ).

hlote.:

The. Revisim l

rendu.the (keg

)i g. sic.~l a~d W4M.<ai )

a.~e, shoe~

@tip.ndit b.

RWcU ROOMS $ 501 5 GPk'i STEAM LEAK SUMMER 120 115 (3

Ld C5 110 l

CL l

105 100 10

'l5 TIME (HRS) 20 Z

o

(

w Q I

0 Legend 8 ROOM 1

O ROOM 2

~ ROOM 3

n dH 4 l ~

I

(

5 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 I5.000 I6.000 17.000 IB. 000
19. 000 20.000
21. 000 22.000 23.000 24.000 ROOMz I

115.00 115.76 I 15.87 115.84 II5.90 115.93 117.44 117.32 117.55 I17.50 117.55 117.54 117.57 117.87 117.81 117.98 117.48 118.06 118.25 118.04 I IB. 15 118.24 118.28 118.39 I18.33 118.39 118.42 118.52 118.59 118. 61 118.66 118.60 118.74 118. 13 118.88 119. 12 118.88 118.98 118.88 118.88 118.84 118.75 ROOMS 2

104.00 106.84 106.86 106.73 106.89 106.83 107.02 106.99 107.04 107.03 107.03 107. 12 107.02 107. 17 107.20 107.25 107.30 107.32 107.69 107. 21*

107.37 107.40 107.55 107.62 107.40 107.50 107.49 107. 51 107. 61 107.63 107.53 107.68 I07.67 I07.59 108.02

'I07 ~ 82 107.77 107.78 107.79 107.78 107.75 107 '6 ROOMP 3

110.00 111.05 I I I. 12 111. 18 111. 15 I I I. 17 111. 28 111.24

'I 11. 20 111. 24 111.20 111. 19 111. 18 111.29 111.34 111.36 111.38 111.44 I I I.60 111.32 111.57 111.49 111.61 111.64 111.53 111.58 111.60 111.62 111.73 111.69 111.69 111.45 111.75 111.87 111.91 111.79 III.73 111.85 111.83 111.83 111.80 111.87 ROOM¹ ROOMP ROOMt TEMPERATURE (OEG F)

ROOM>>

ROOM>>

ROOMAr ROOMS ROOM>>

ROOM¹ ROOMN ROOM>>

ROOM4 X

O V

1D0

t t

RWCU ROOMS $501 5 GPM STEAM LEAK WINTER 88 86 84 (3

82 Cl I

80 CL 78 76 74 0

10 15 TIME (HRS) 20 25 o

f

~ U O

U')

Legend 8 ROOM 1

0 ROOM 2

~ ROOM 3

I cJ

RWCU ROOMS >>501

(

5 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100
0. 200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 180.00
79. 98 79.91 79.95 79.95 79.95 82.83 83.47 84.44 84.55 84.68 84.80 84.79
85. 11
85. 19 85.33 85.42 85.39 85.46 85.56 85.59 85.63 85.66 85.71 85.72 85.76 85.88 85.81
85. 89 85.89 85.92 85.99 85.96 85.98 85.99 86.00 86.03 86.06 86.97 86.08
86. 16
86. 12 2

76.00 76.04 75.95 76.05 76.05 76.05

76. 17
76. 16
76. 15
76. 17
76. 11 76.22 76.12
76. 19
76. 16
76. 17
76. 17
76. 16 76.09 76.20
76. 18
76. 17
76. 19
76. 19
76. 17 76.20
76. 19
76. 17
76. 19
76. 19
76. 19
76. 17
76. 19
76. 13
76. 11
76. 14
76. 13
76. 15
76. 24
76. 15
76. 15
76. 17 3

75.00 74.81 74.77 74.75 74.75 74.74 74.96 74.89 74.85 74.87 74.84 74.87 74.85 74.90 74.88 74.90 74.89 74.87 74.85 74.90 74.88 74.87 74.86 74.90 74.89 74.88 74.90 74.87 74.89 74.89 74.89 74.87 74.89 74.86 74.83 74.87 74.84 74.86 74.95 74.85 74.85 74.86 ROOM>>

ROOMS ROOM>>

TEMPERATURE (DEG F)

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM¹ ROOM>>

ROOM>>

t t

RWCU ROOMS $501 25 GPM STEAM LEAK SUMMER 150 140 (3

130 l

120 Q

0 p p

lnr C

110 100 10 15 TIME (HRS) 20 25 Legend

~ ROOM 1

Cl ROOM 2

O ROOM 3

Fs

'3S.

i>r-4 C

nnfCU ROOMS ¹501 (25 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000
14. 000
15. 000 16.000 17.000 18.000
19. 000 20.000
21. 000 22.000 23.000 24.000 ROOM¹ I

I I5.00 115.76 115.87 I 'I5.84 115.90 115.93 128.72 132.93 135.05 136. 15 136.64 137. 15 138.32 139.05 139.43 139.69 139.95 140.02 140. 18 140. 27 140. 38 140. 50 140.72 140. 61 140.64 140. 71 140.84 140.87 140.90 140.98 141. 04 141. 12 141. 13 141. 16 141. 19 141. 0'I 141. 32 141. 19 141. 31 141.36 141. 34 141.38 ROOM¹ 2

104.00 106.84 106.86 106.73 106.89 106.83 107.65 107.76 107.88 108.07 108.03 108. 16 108. 19 108.43 108.50 108.60 108. 71 108.73 108.76 109.63 108.92 108. 91 109. 00 109. 01 109.01 109.05 109. 16 109. 18 109.33 109.23 109.38 109.36 109.38 109 '6 109. 49 109.46 109.58 109.62 109.67 109.69 109.75 109.80 ROOM¹ 3

110.00 111.05 111. 12 111. 18 111.15 111. 17 111.78 111.57 111.64 111.77 111.74

'111.80 111.80 112.00

'112.06 112. 11 112. 11 I 12. 20 112.29 112.36 112.35 112.48 112.42 112.51 112.50 112.55 112.68 112.64 112.87 112.71 112.87 112.83 112.89

'112.95 112.96 112.94 113.03 113.05 113. 10 113. 11 113. 18 113.24 ROOM¹ ROOM¹ TEMPERATURE (OEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ Q

C' I

o Q

6 o0

RWCU ROOMS $501 25 GPM STEAM LEAK WINTER 140 130 120 (3

1'l0 100 CL 90 80 70 10 15 TIME (HRS) 20 25 Legend a ROOM 0 ROOM 2

~ ROOM 3

RWCU ROOMS >>501 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900
1. 000
1. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000
13. 000 14.000
15. 000 16.000 17.000
18. 000
19. 000 20.000 21. 000 22.000 23.000 24.000 ROOM¹ 180.00 79.98 79.96 79.96 79.95 79.95 114. 10 118.98 121.63 123.08 124.08 124.94 127.59 128.98 129. 91 130.54 131. 03 131. 41 131.71 131.97 132. 18 132.36 132.57 132.72 132.74 132.93 133. 13 133. 31 133.44 133.58 133.70 133.79 133.89 133.95 134.02 134.08 134. 16 134. 21 134. 27 134.34 134.38 134.40 ROOMS 2

76.00 76.05 76.05 76.05 76.05 76.06 77.45 77.60 77.78

77. 91 77.99 78.06 78.26 78.52 78.61 78.72 78.74 78.81 78.88 78.92 78.97 79.00 78.99 79.09
79. 10
79. 13
79. 21
79. 16 79.25 79.29 79.35 79.37 79.42 79.45 79.56 79.52 79.55 79.58 79.62 79.68 79.72 79.68 ROOM¹ 3

75.00

74. 81
74. 77 74.75 74.75 74.75 75.98 75.99 76.28 76.38 76.47 76.52 76.74 76.93 77.02 77.10 77.16 77.22 77.28 77.33 77.37 77.39 77.45 77.52 77.46 77.57 77.60 77.66 77.71 77.75 77.83 77.83 77.90 77.93 77.96 7'8 78.02 78.04
78. 10
78. 13
78. 13 78.22 ROOM¹ ROOM>>

TEMPERATURE (OEG F)

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM¹ ROOM>>

ROOM>>

ROOM¹ ROOM>>

ROOM>>

Q P

p, P

t

~ P

~ o LA

~

~

RIA'CE l ROOMS $502/503 ( 5 GPM STEAM LEAK/SUMMER 120 115 C3 110 CL CL LIJ I

105 100 10 15 20 Legend J

a ROOM Cl ROOM 2 ~y 0 ROOM TlME (HRS)

\\D fI

RINCU ROOMS ¹502/503

(

5 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100
0. 200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 ROOM¹ I

115.00 115.78 115.85 115.88 115.89 I '15.91 116.91 116.76 117. 14 117. 19 117.33 117.41 I 17. 66 I 17.83

. 117.94 118.08 118.17 118.26 118.28 118.35 118.43 118.62 118.56 118. 61 I 18. 62 118. 70 118.75 118. 83 118.88 118. 98 119. 00 119.03

'I 19. 14 119. 19 119.47 119. 18 119.26 I 19. 31 119.42 I 19. 34 119.50 119.46 ROOM¹ 2

104. 00 106. 81 106. 85 106.87 106.90 106.93 112. 11 112. 94 113.84 114.23 I 14. 49 114. 69 115.41 115.97 116.27 116. 61 116.57 116. 61 116.78 116.82 116.99 118.76 117.06 117. 18 117.32 117.25 I '17.53 117.47

'I 17. 69 117.50 I 17. 78 117.43 118.01 118.50 117. 93 117. 77 117. 50 117.81 117.78 117.97 117.92 118.33 ROOM¹ 3

I 10. 00 111.03 111.11 111. 15 111. 16 111. 17 111.64 111.08 111.18 111. 18 111.23 111.21 111.27 111.29 111.35 111.33 111.39 111.42 111.40 111.42 111.43 111.49 111.48 111.54

'111.50 111.54 I '11.57 111.58 111.60 111.65 111.64 111.66 111.75 111.78 111.70 111.76 111.72 111.77 111.77 111.76 111.90 111.82 ROOM¹ ROOM¹ TEMPERATURE (OEG F)

ROOM¹ ROOMs ROOM¹ ROOM¹ ROOM¹ ROOM>>

ROOM¹ ROOM¹ ROOM¹ ROOM¹ pO P p

I c

p I00

t i

t RWCU ROOMS $502 505 5 GPM STEAM LEAK WINTER 110 105 100 (3

C) 95 90 I

LLI 80 75 70 10 15 TIME (HRS) 20 Legend g I' ROOM 1 Q+

P Q ROOM 2~<)

~ ROOM

RWCU ROOMS ¹502/503

(

5 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000
19. 000 20.000 2 I.000 22.000 23.000 24.000 ROOM¹ I

80.00 79.97 79.96 79.95 79.95 79.95 82.90 84.66

85. 18 85.34 85.56 85.67 86.25 86.52 86.74 87.00
87. 15 87.27 87.44 87.52 87.66 87.78 87.85 87.80 88.01 88.07 88'. 20 88.34 88.45 88.56 88.65 88.62 88.82
88. 91 88.98 89.05
89. 12 89.20 89.29 89.32 89.37 89.45 ROOM¹ 2

76.00 76.05 76.05 76.05 76.05 76.05 92.59 94.80 96.02 96.65

97. 12 97.60 99.29 100.02 100.69 101. 18 101. 56 101.91 102.24 102.44 102.68 102.85 103.03 103.26 103. 31 103.44 103.72 103.84 104.04 104.

'I 5 104.32 104.40 104.56 104.62 104. 72 104..81 104.87 104.93 105.02 105.06 105. 13 105. 17 ROOM¹ 3

75.00 74.81 74.77 74.76 74.75 74.75 75.00 74."'88 74.92 74.93 74.97 74.96 75.01 75.00 74.99 75.06 75.02 75.01 75.05 75.01 75.05 75.06 75.07 74.93 75.07 75.06 75.06 75.08 75.11 75.09

75. 10 75.02 75.08 75.09
75. 10 75.11 75.11 75.13
75. 15
75. 12
75. 12
75. 15 TEMPERATURE (OEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹

'WCU ROOMS $502/505 (25 CPM STEAM LEAK/SUMMER) 170 160 150 140 Ct I

130 CL 120 110 Legend a ROOM D

p p

n I

O C

O Vi 100 10 15 TIME (HRS) 20 25 Cl ROOM 2

~ ROOM 3

p1$

RWCU ROOMS >>502/503 (25 GPM STEAM LEAK/SUMMER)

TIME (HR I 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000
14. 000 15.000 16.000 17.000 18.000
19. 000 20.000
21. 000 22.000 23.000 24.000 ROOM¹ 1

115.00 115.78 115.85 115.88 115.89 115.91 122. 17 124.57 128. 12 130.09 130.74 131. 60 134.26 135.74 136.77 137. 21 137.70 138. 01 138. 21 138.46 138.55 138.93 138.70 138.83 138.86 139. 12 139.20 139. 18 139. 31 139.48 139. 43 139. 64 139.63 139.87 139. 85 139.87 140.08 140.08 140.03 140.08 140. 14 140. 14 ROOM¹ 2

104.00 106. 81 106.85 106.87 106.90 106.93 144.67 149.72 152.64 156.20 154.85 155.48 157.31 158.04 158.53 158.93 159.28 159.38 159.64 159.88 159.75 159.96 160.09 160.01 159.78 160.30 160. 15 160. 15 160.34 160.50 160.61 160.46 160.58 160.59 160. 61 160.79 160.93 160.90 160.73 160.78 160.92 160.89 ROOM¹ 3

110.00 111.03 111. 1'I 111. 15 111. 16 111. 17 112.02 111.77 111.83 111.90 111.92 112.00 112.26 112. 21 I '12.59 112.55

'112.69 112.74 112.82 112.98

'113.00 113. 10 113.04 113. 14 113. 21 113.26 113.35 113.38 113.48 113.54 113.67 113.74 113.79 113.82 113.88 113.95 114.09 114.07 114.01 114. 10 114. 16 114.23 ROOM¹ ROOM¹ TEMPERATURE (OEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM>>

ROOM¹ ROOM¹ ROOM>>

ROOM¹ ROOM>>

ROOM¹ 0 P g

X, r

I O

'WCU ROOMS $502 503 25 GPM STEAM LEAK WINTER 160 140 (3

1ZO 100 EL f

80 60 10 15 TIME (HRS) 20 p

P 0

U 6

0 0'egend S ROOM 1

0 ROOM 2

0 ROOM 3

p'

>e

<iA

~ IPl +

p, I~

RWCU ROOMS ¹502/503 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000
19. 000 20.000 21.000 22.000 23.000 24.000 ROOM>>

I 80.00 79.98 79.95 79.97 79.95 79.95 91.45 99.79 105.69 108.56 110.42 112. 17 117. 28 119. 93

'121. 40 122.72 123.67 124.44 124.93 125.37 125.93 126.27 126.45 126.84

'127.07 127. 21 127. 61 127.90 128. 18 128.39 128.68 128.89 129.08 129.30 129.27 129.47 129. 61 129.75 129.72 129.94 129.96 130. 12 ROOM¹ 2

76.00 76.04 76.07 75.99 76.05 76.05 134.05

'140. 16 144. 10 146. 24 147. 65

'I 48. 75 151. 74 153. 09 153.83 154. 47 154. 86 155. 28 155.45 155. 69 155.78 156.00 156. 13 156. 29 156. 31 156.42 156.69 156.56 156.86 156.89 157. 01 157.07 157.29 157.40 157.22 157. 41 157. 46 157.58 157.45 157.50 157.49 157.62 ROOM¹ ROOM¹ ROOM¹ 3

75.00

74. 81 74.77 74.77 74.74 74.74 76.33 76.34 76.49 76.54 76.64 76.75 77.06 77.28 77.46 77.62 77.84 78.07
78. 14 78.29 78.45 78.62 78.65 78.85 78.90 79.03 79.37 79.54
79. 81 80.02
80. 14
80. 19 80.57 80.57 80.76 80.99 80.96
81. 17
81. 18 81.35
81. 44 81.56 TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM>>

ROOM¹ ROOM¹ ROOM¹

t t

RWCU ROOMS $504/505 ( 5 GPM STEAM LEAK/SUMMER) 130 125 u

120 115 I

CL 110 I

105 100 10 15 TIME (HRS) 20 25 g! p o

Cp 6

Legend r ROOM 1

Cl ROOM 2

~ ROOM

0 t,

I4k~

4

RWCU ROOMS >>504/505

(

5 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900
1. 000
1. 500 2.000 2.500 3.000 4.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000
11. 000 12.000 13.000 14.000 15.000

'I6.000 17.000

18. 000 19.000 20.000
21. 000 22.000 23.000 24.000 ROOM>>

I 115.00 I 'I5.79 115.97 I15.88 115.89 115.92 116.23 I16.05 116.54 116.73 116.88 ll6.94 117.28 117.50 I 17.96 117.77 117.92 118. 00 118. 14 118. 19 I'18. 26 118.33 I18.35 118.42 118.48 118.59 118.66 118.80 118.83 118.92 119. 02 119.03 119. 10 119. 15 119.23 119.33 119.33 119. 37 119. 39 119.47 119.50 119. 55 ROOM¹

'2 104.00 106.78 106. 92 106.88 106.88 106.91 107.03 106.94 106.99 107. 01 107.04 107. 10 107. 14 107.20 107.39 107.23 107. 31 107.33 107.36 107.39 107.42 107.44 107.43 107.45 107.46 107.55 107.57 107.63 I07.63 107.69 107.74 107.73 107.77 107.78 107.82 108.07 107.88 107.94 107.86 107. 96 107.98 107.99 ROOM>>

3 110.00 111.05 I10.95 I 1 'I.15

'I 11. 19

'I 11. 17 1 13. 49 113.35

'I 17. 21 118.33 118.94 119

~ 40 120.97 121.97 122.99 123.26 123.64 123.95 124.27 I24.52 124.70 124.96 125.03 125.24 125.35 125.54 125. 81 126.01 126. 12 126.34 126.47 126.61 126.79 126.86 126.98 127. 01 127. 13 127.09 127. 15 127.31 127.31 127.42 ROOM>>

ROOM>>

TEMPERATURE (OEG F)

ROOM>>

ROOMS ROOMP ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

RWCU ROOMS $504 505 5 GPM STEAM LEAK WINTER 120 110 D

100 w

90 CL LIJ I

80 70 10 15 20 Legend 8 ROOM 1

a ROOM 2

~ ROOM TIME (HRS)

gd 4,

U

RWCU ROOMS ¹504/505 5

GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. '100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900

'I. 000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000

'16.000 17.000 18.000 19.000 20.000

21. 000 22.000 23.000 24.000 ROOM¹ I

80.00 79.92 79.95 79.95 79.95 79.96 80.93 82.31 83.36 83.64 83.80 83.95 84.47 84.83

85. 10 85.30 85.55 85.73 85.83 86.02
86. 13 86.24 86.35 86.46 86.58 86.64 86.82 86.95 87.11 87.23 87.37 87.46 87.54 87.67 87.79 87.83 87.93
88. 01 88.07
88. 15
88. 21 88.28 ROOM¹ 2

76.00 76.05 76.05 76.05 76.02 76.08 76.30 76.12

76. 16
76. 11
76. I 'I
76. 12
76. 18
76. 16
76. 12 76.08
76. 17
76. 19

= 76. 13

76. 18
76. 20 76.20 76.20 76.20 76.24 76.22 76.22 76.25 76.26 76.28 76.27 76.28 76.29 76.31 76.32 76.30 76.34 76.32 76.32 76.34 76.34 76.37 ROOM¹ 3

75.00 74.81 74.77 74.75 74.74 74.72 83.51 91.01

94. 17 95.35 96.24 96.96 99.62 101.31 102.72 103.70

'104.65 105.38 106.03 106. 61 107.20 107.58 108.00 108.38 108.82 109. 14 109.77 110.29 110.76 111.08 111.60 111.87 112. 15 112.49 112.75 113.00 113.27 113.46 113.65 113.85 113.97 114. 18 ROOM¹ "ROOM¹ TEMPERATURE (OEG F)

ROOM>>

ROOM¹ ROOM>>

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM>>

ROOM¹ P

o I

Q 0

I

180 160 (3

C)

LLI 140 I

CL LLI CL LLJ I

120 100 10 15 TIME (HRS) 20 25 Legend g

P ROOM OROOM 2 '

~ o

~ ROOM 3

~ 4

R INC U ROOMS TIME (HR) 0.000

0. 100
0. 200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000

¹504/505 (25 GPM STEAM LEAK/SUMMER)

ROOMS ROOMZ I

115.00 115.80 115.88 115.89 115.90 115.91 118. 16 120.09 121. 88 123.49 124.70 125. 71 128.92 130.76

'I31.87 132.70 I33.32 133.80 134. 19 134.50 134.79 135.04 135.25 135.41 135.58 l35.73 135.92 136. 12 136.31 I36.45 136. 60 136. 69 136.83 136. 88 137.00 137.07 137. 19 137.20 137.27 137.31 137. 40 137.46 ROOMS 2

104.00 106. 81 106.87 106.88 106.90 106. 91 107.72 107. 91 108. 01 108. 12 108. 22 108.33

'I08.74 109.03 109.23 109.42 109.56 109.69 109.80 109.90 109.99 110.09 110. 15 110.22 110.30 110.37 110.47 110.59 110.67 110.77 110.84 110.93 111.02 III.07 111. 12 111.24 111.30 111.35 111.43 111.50 111.56 111.62 ROOMS 3

110.00

'I11.04 111. 12 111. 14 111. 16 111. 18 135.29 144.98 152.27 155.60 157.72 159.32 163.85 165.79 166.93 167.69 168.26 168.70 169.02 169.29 169.55 169.76 169.90 170.03 170. 17 170.29 170.48

'I70.64 170.79 170.90 171. 03 171. 12 171. 23 171. 28 171.37 171.42 171. 56 171.54 171. 58 17 I. 63 171. 68 171. 73 TEMPERATURE (DEG F)

ROOM¹ ROOMS ROOM>K ROOMA'OOM>>

ROOMA'OOM¹ ROOMP ROOMS ROOMAF F

o

~

o

~ o

'WCU ROOMS $504 505 25 GPM STEAM LEAK WINTER 180 160 4

u 140 LJ C)

LJ 120 I

CL 100 I

80 60

'IO 15 20

=- 25 td 5 IrU o0 Legend a ROOM 1

CI ROOM 2

~ ROOM TIME (HRS)

¹504/505 RWCU ROOMS I

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900

'I. 000

1. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000
15. 000 16.000 17.000
18. 000 19.000 20.000 2 'I. 000 22.000 23.000 24.000 ROOM¹ I

80.00 79.96 79.95 79.95 79.96 79.95 85.91

88. 71 91.80
94. 73 96.99 98.98 106.07 110.22 113. 14 115. 21 116.79 117.96 118.93 119. 77 120.45 121. 05 121.61 122.04 122.48 122.88 123.47 124.00 124.44 124.83 125. 15 125.52 125.76 126.00 126.22 126.45 126.60 126.79 126.95 127. 12 127.23 127.37 (25 GPM STEAM LEAK/WINTER)

ROOM¹ ROOM¹ ROOM¹ 3

75.00 74.81 74.77 74.76 74.75 74.74 121. 13 129.90 137.98 142.03 144.99 147. 40 154.63 158. 16 160.25 161.68 162.67 163.44 164.07 164.56 164.97 165.31 165.60 165.87 166. 10 166.34 166.66 166.96 167.21 167.42 167.58 167.82 167.93 168.06 168. 19 168.32 168.40 168.49 168.60 168.67 168.74 168.81 2

76.00 76.05 76.05 76.05 76.06 76.05 77.75 77.56 77.54 77.58 77.69 77.83 78.25 78.60 78.89

79. 10 79.34 79.44 79.60 79.69 79.82
79. 91
79. 98
80. 10
80. 21 80.26 80.35 80.47 80.58 80.66 80.77 80.86 80.94 81.04
81. 16 81.27 81.35 81.44
81. 57 81.71
81. 75
81. 86 TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹

Ca.lc M-Sap-oo5 pa.ce. 39 of 6C

~C fO((OUJ>VIGj Z,4 pO.)CS ELM VCSlll4 JOY NC. YUA5 p I I lO p5tg /+4@

p peale. condAlois). Them K.sol4 ave.

gQo+g lA gYG.p4 ted&. l O.VLd 'bkku (Cl v fovnA. (RLV. O).

Re,vision I Ye.su.l4. (both gyp.p<~l gw4l ~y.la.V) GrC. 54,0UJVL

RWCU ROOMS f501 5 GPM STEAM LEAK SUMMER 120 115 (3

LLI Cl 110 LLJ 0

l 105 100 10 15 TIME (HRS) 20 25 Legend 0 ROOM 1

0 ROOM 2

~ ROOM 3

RINCU ROOMS 501

(

5 GPM STEAM LEAK/SUMMER)

TIME (nR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 ROOM>>

I 115.00 115.76 115.87 115.84 115.90 115.93 117. 15 117. 16 I 17. 12 117. 15 117.

17'17.29 117.25 117.36 117.46 117.50 117.56 I 17.61 117.57 117.75 117.74 117.75 117.82 117.81 I 17. 83 I 17. 87 117.89 117.99 118.03 118.04 118.07 118.07 118.08 118. 18 118. 17 118.24 118.24 118. 31 118.30 118. 21 118.34 118.40 ROOM>>

2 104.00 106.84 106.86 106.73 106.89 106.83 107.01 107. 01 106.92 106.98 107. 01 107. 12 107. 04 107. 07 107. 19 107.26 107. 24 107. 27 107. 29 I 07.42 I 07. 38 107. 38 107. 38 107.40 107. 39 107.43 107.49 107.52 107.55 107. 51 107.57 107.52 107.55 107. 65 107. 67 107. 60 107.66

,107. 71 107.72 107.77 107. 81 107.78 ROOM>>

3 110.00 111.05 111.12 111. 18 111. 15 111. 17 111.29 111.23 111.27 111.20 111.21 111.31 111. 18 111.27 111.37 111.42 111.39 111.46 111.53 111.49 111.49 111.46 111.49 111.51 111.50 111.52 111.57 111.62 111.66 111.70 111.66 111.52 111.70 111.68 111.59 111.74 III.75 111.76 111.77 111.81 111.88 111.91 ROOM>>

ROOM>>

TEMPERATURE (DEG F)

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

RV/CU ROOMS $501 5 GPlvl STEAM LEAK WINTER 84 82 C3 80 LLI CY I

w 78 CL I

76 10 TIME (HRS) 20 25 0

p P

~

X l

Legend 8 ROOM 1

Q ROOM 2

~ ROOM

8"

RWCU ROOMS >>501

(

5 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 I

80.00 79.98

79. 91
79. 95 79.95 79.96 82.21 82.37 82.42 82.46 82.52 82.54 82.55 82.49 82.63 82.65 82.69 82.68 82.69 82.66 82.72 82.74 82.76 82.77 82.77 82.79 82.79 82.72 82.84 82.87 82.88 82.90 82.91 82.90 82.91 82.94 82.89 82.96 82.99 82.99 82.99 83.01 2

76.00 76.04 75.95 76.05 76.05 76.05

76. 15
76. 16
76. 13
76. 13
76. 11
76. 12
76. 12 75.87
76. 12 76.09
76. 13
76. 13
76. 16
76. 13
76. 13
76. 13
76. 13
76. 15
76. 16
76. 14
76. 11 75.97
76. 14
76. 15 76.07
76. 15
76. 13
76. 15
76. 10
76. 12
76. 12
76. 13
76. 15
76. 15 76.11
76. 15 ROOM>>

ROOM>>

ROOM>>

3 75.00 74.81 74.77 74.75 74.75 74.74 74.95 74.85 74.80 74.81 74.84 74.83 74.67 74.78 74.83 74.85 74.82 74.83 74.83 74.82 74.84 74.83 74.84 74.83 74.84 74.82 74.82 74.78 74.82 74.81 74.77 74.80 74.81 74.83 74.79 74.80 74.81 74.88 74.82 74.81 74.82 74.83 ROOM>>

ROOM>>

ROOM>>

TEMPERATURE (OEG F)

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

RWCU ROOMS $501 25 GPM STEAM LEAK SUMMER 130 125 C3 LLI C) 120 LLI CL I

115 Q

110 105 100 10 15 TIME (HRS) 20 25 Legend 0 ROOM 1

0 ROOM 2

~ ROOM 3

RWCU ROOMS $501 25 GPM STEAM LEAK WINTER 130 120 u

110 W

100 I

CL 90 I

80 70 10 15 TIME (HRS) 20 25 O

P' QJ D

Legend a ROOM 0 ROOM 2

0 ROOM 3

\\

RWCU ROOMS 4501 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000

'11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000 21.000 22.000 23.000 24.000 ROOMP I

80.00 79.98 79.96 79.96 79.95 79.95 107. 01 111. '10 113.58 114.79 115.65 116.31 118.27 119.53

'120.37 120.90 121.37 121. 75 122.06 122.30 122.51 122.69 122.91 123. 01 123. 18 123.

25'23.46 123.63 123.80 123.93 124.05 124.16 124.23 124. 31 124. 41 124.45 124.54 124.62 124.65 124.74 124. 75 124.80 ROOM¹ 2

76.00 76.05 76.05 76.05 76.05 76.06 76.93 77.07

77. 19 77.25 77.32 77.36 77.50 77.68 77.62 77.70 77.81 77.87 77.88 77.95 77.89 77.96 77.98 77.95 78.05 78.00 78.04
78. 10
78. 12
78. 14
78. 17
78. 19
78. 19 78.20 78.25 78.27 78.28 78.29 78.36 7'5 78.42 78.43 ROOMa' 75.00 74.81 74.77 74.75 74.75 74.75 75.61 75.57 75.79 75.87 75.93 75.97 76.09 76.20 76.23 76.28 76.36 76.43 76.48 76.51 76.49 76.51 76.55 76.57 76.61 76.57 76.63 76.67 76.70 76.75 76.77 76.79 76.81 76.80 76.85 76.87 76.87 76.91 76.92 76.96 76.98 76.99 ROOMS ROOMP TEMPERATURE (DEG F)

ROOMS ROOMS ROOM4'OOM¹ ROOM>>

ROOMS ROOM>>

ROOM4'OOMN ROOM¹ p

o Q

I 0l

t RWCU ROOMS $502 505 5 GPM STEAM LEAK/SUMMER 120 115 C3 bJ 110 CL EL I

105 100 10 TIME (HRS) 20 25 p

+ K OO Or o

Legend 8 ROOM t

0 ROOM 2

~ ROOM 3

RWCU ROOMS >>502/503

(

5 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900
1. 000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000
14. 000
15. 000 16.000 17.000 18.000
19. 000 20.000 21. 000 22.000 23.000 24.000 ROOM>>

I 115.00 115.78 115.85 115.88 115.89 115.91 I 16. 29 116.44 I 16. 61 116.67 I 16.90 116. 72 I '16.91 117.07 I '17. 21 117. 18 117.56 117.32 117.27 117.42 117.40 117.47 117.48 117.38 I '17.58 117.55 117.60 117.69 117.70 117.69 117.79 117.78 117.83 117.79 117.83 117.92 117.92 117.99 118. 12 118.01 118.05 118.03 ROOMP 2

104.00 106.8'I 106.85 106.87 106.90 106.93 109.60 110.05 110.92 110.80 111.41 111.47 112.01 112.46 112.60 112.68 111.32 112.87 112.53 112.80 112.96 113.02 112.98 113.23 113. 12 113.07 113. 17 113.23 113.27 113. 16 113. 13 113.20 113.26 113.27 113.28 1 '13.30 113.38 113.36 113.46 113.75 113.43 113.33 ROOM>>

3 110.00 111.03 111. 11 111. 15 111. 16 111. 17 111.20 111.09 111.29 111. 10 111.32 111.21 111.24 111.31 111.28 111.31 111.62 111.41 111.43 111.42 11'1.43 111.45 111.46

'111.50 111.57 111.49 111.53 111.56 111.50 111.58 11 1. 60 111. 63 111.65 111. 65 111.70 111.69 111.73 111.78 111.74 111.82 111.77 111.77 ROOM>>

ROOM¹ ROOM>>

TEMPERATURE (DEG F)

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

ROOM>>

RWCU ROOMS $502 503 5 GPM STEAM LEAK WINTER 100 95 90 bJ C3 85 I

CL 80 2 p n

X 0

t O

~ o Cq 75 70 10 TIME (HRS) 20 25 Legend 8 ROOM 1

0 ROOM 2

0 ROOM 3

RWCU ROOMS TIME (VR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 F 000 F 500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000

'12.000

'13.000 14. 000 15.000 16.000 17.000 18.000 19.000 20.000

21. 000 22.000 23.000 24.000 STEAM LEAK/WINTER)

ROOM¹

¹502/503 5

GPM ROOM>>

ROOM/

ROOM¹ ROOM¹ 2

76.00 76.05 76.05 76.05 76.05 76.05 87.74 89.64 90.47 90.94

91. 24 180.00 79.97 79.96 79.95 79.95 79.95 81.87 83.36 83.84 83.97
84. 12
84. 18 84.53 84.76 3

75.00

74. 81 74.77 74.76 74.75 74.75 74.94 74.83 74.85 74.85 74.90 74.88 74'9 74.87
74. 91
74. 91
74. 91 74.92 74.90 74.98 74.91 74.90 74.97 74.93
74. 91 74.92
74. 91 74.92 74.93 74.93 74.94 74.93 74.93 74.93 74.98 74.94 74.95 74.88 74.93 74.95 74.95 74.95
91. 54 92.54 93.26 84.98 93.76 94.06 94.36 94.62 94.85 95.06
85. 10 85.22 85.29
85. 41 85.60 85.58 95.19 85.56 85.80 85.80 85.85 85.87 85.98 86.09
86. 17
86. 25 86.33 86.39 86.44 86.52 86.61 86.61 86.67 86.60 86.74 86.81 86.84 86.91 95.39 95.48 95.59 95.70 95.80 95.99
96. 14 96.28 96.41 96.52 96.63 96.71 96.91 96.88 96.95 97.00 97.10
97. 14
97. 19
97. 24 97.30 TEMPERATURE (OEG F)

ROOM>>

ROOM¹ ROOM¹ ROOM4 ROOM¹ ROOM¹ ROOM¹ ROOM>>

ROOM¹ ROOM¹ p

o

RWCU ROOMS $502/503 (25 GPM STEAM EEAK/SUMMER) 160 150 u

140 130 I

120 110 100 10 15 20 25 gP M

0 Pq Legend S ROOM 1

0 ROOM 2

~ ROOM TIME (HRS)

RWCU ROOMS ¹502/503 (25 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000 21.000 22.000 23.000 24.000 ROOM¹ I

115.00 115.78 115.85 115.88 115.89 115.91 120.88 122. 41 124.82 126. 17 126.85 127.37 129.35 130.25 13 I. 07 131. 39 131.71 131.91 132. 16 132. 43 132. 51 132.62 132.69 132.72 132.93 132.91 133.04 133.28 133. 31 133.45 133.46 133.62 133.47 133.59 133.65 133.80 133.80 133. 91 133. 94 134. 04 134. 00 134. 00 ROOM¹ 2

104.00 106. 81 106.85 106.87 106.90 106.93 137.55 141. 74 144.29 145. 86 146. 47 147.20 149. 10 150. 11 150.64 150. 96 151. 25 151. 40 151. 82 151.76 151.85 152.00 152. 11 151.95 152. 16 152.26 152.39 152.58 152.49 152. 70 152. 68 152. 80 152.75 152.73 152.78 153.00 152.89 153. 17 153.05 153. 16 153. 31 153.08 ROOM¹ 3

110.00 111. 03 111. 11 111. 15 111. 16 111. 17 111.61 111.47 111.56 111.77 111.67 111.74 111.79 111.99 112.01 112.00 112.20 112. 18 112.30 112.38 112.44 I '12.50 112.55 112.55 112.58 112.60 112.71 112.74 112.80 112.84 112.92 112.97 112.99 113.02 113.11 113. 12 112.99 113. 17 113.22 113.25 113.31 113.37 ROOM¹ ROOM¹ TEMPERATURE (OEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹

RWCU ROOMS $502 503 25 UPM STEAM LEAK WINTER

'160 140 C3 Ld 120 Ld Cl f

100 CL I

80 60 10 15 TIME (HRS) 20 25 Legend a ROOM 1

C3 ROOM 2

4 ROOM 3

RWCU ROOMS ¹502/503 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 I'3. 000 14.000 15.000

'16.000

'17.000 18.000

19. 000 20.000
21. 000 22.000 23.000 24.000 ROOM¹ 180.00 79.98 79.95 79.97 79.95 79.95 89.62 93.82 98.73 100.98 102.52 103.96 108.07 110.50 112.20 113.39 114.33 114.94 115.62 116. 12 116.56 116.90 117.23 117.75 117.78 117.93 118.40 118. 51 119.07 119. 19 119.48 I 19. 71 I 19. 90 120. 11 120.28 120. 51 120.41 120.56 120.63 120.74 120.95 120.94 ROOM¹ 2

76.00 76.04 76.07 75.99 76.05 76.05 124.97 130.29 134.26 136.43 137. 65 138.81 141. 98 143. 53 144. 42 145. 18 145.57 145.86 146.37 146.46 146.79 146. 95 147.08 147. 41 147.44 147.46 147.63 147.57 148.00 148. 01 148. 14 148.26 148.32 148.70 148.72 148.52 148.69 148.56 148.68 148. 73 148. 83 148.93 ROOM¹ 3

75.00 74.81 74.77 74.77 74.74 74.74 75.86 75.85 75.96 76.08

76. 12 76.20 76.42 76.57 76.67 76.77 76.87 76.89 76.91 77.03 77.07
77. 14
77. 17 77.40 77.22 77.28 77.34 77.38 77.43 77.49 77.53 77.57 77.58 77.68 77.81 77.79 77.81 77.84 77.84 77.99 77.98 78.01 ROOM¹ ROOM¹ TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ g

P C'

0 Q4 0

RWCU ROOMS $504 505 5 GPM STEAM LEAK/SUMMER) 125 120 C3 Ld CL I

M 110 CL p

p o

0 60' 105 100 10 15 TIME (HRS) 20 25 Legend

~ ROOM 1

o ROOM 2

~ ROOM 3

I<<

~ I,

~ v

RINCU ROOMS ¹504/505

(

5 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100
0. 200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000
14. 000 15.000
16. 000, 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 ROOM¹ I

115.00 115.79 115.97 115.88 115.89 115.92 116. 14 116.04 116.05 116.25 116.35 116.41 116.64 116.80

'116.93 117.02 117.07 117.18 117. 22 117.25 117. 24 117.40 117.50 117.55 117.57 117.59 I 17. 73 117. 77 I 17. 83 117.92 117.94 117.99 118.03 118.03 118.

'I I 118. 15 118. 17 118.28 118.28 118.28 118.30

'118.36 ROOM¹ 2

104.00 106.78 106. 92 106. 88 106.88 106. 91 106.97 106.96 106.96 107.04 107.01 107. 01 107. 08 107. 15 107. 22 107. 22 107. 24 107.24 107.32 107. 31 107. 32 107.45 107.40 107.38 107.40 107.45 107.54 107.57 107. 56 107.64 107.62 107. 61 107. 64 107. 62 107. 70 107. 70 107.72 107.79 107.79 107. 76 107.78 107.82 ROOM¹ 3

110.00 111.05 110.95 111. 15 111. 19 111. 17 112.86 112.77 113.78 114.84 115.33 115.68 116.72 117.38 117.90 118. 10 118.45 118.65 118.99 119. 12 119.27 119.54 119.78 119.91 119.99 120. 12 120.32 120.55 120.68 120.85 120. 86 121.01 121. 14 121. 12 121. 28 121. 36 121. 35 121. 47 121. 55 121. 61 121. 58 121. 69 ROOM¹ ROOM¹ TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM>

RWP ROOMS $504 505 5 4P'M STEAM LEAK/WINTER 110 105 100 0

Cl 95 90 CL 8S LJ I

Legend r ROOM Q

P n

V) r 0

70 10 15 TtvE: (H~s) 20 0 ROOM

RWCU ROOMS >>504/505 5

GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900
1. 000
1. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000
19. 000 20.000 21. 000 22.000 23.000 24.000 180.00 79.96 79.95 79.95 79.96 79.95 80.44
81. 58 82.76 82.85 82.95 83.09 83.46 83.74 83.96
84. 13 84.29
84. 41 84.54 84.66 84.75 84.85 84.91
85. 01 85.09
85. 16 85.30 85.40 85.52 85.63 85.75 85.81 85.90 85.98 86.05
86. 13 86.20 86.25 86.30 86.37 86.43 86.48 2

76.00 76.05 76.05 76.05 76.06 76.05 76.12 76.06 76.11 76.13 76.11

76. 14
76. 17
76. 16
76. 20
76. 18
76. 18
76. 19
76. 19 76.20 76.20 76.21
76. 19 76.21 76.22 76.22 76.23 76.22 76.24 76.24 76.28 76.27 76.27

'6.27 76.29 76.30 76.29 76.29 76.34 76.31 76.30 76.32 ROOM¹ ROOM>>

ROOM¹ 3

75.00 74.81 74.77 74.76 74.75 74.74 77.86 86.95 89.77 90.67 91.26

91. 78 93.63 94.93 95.93 96.73 97.45 98.05 98.58 99.05 99.48 99.85 100. 21 100.53 100.83 101. 10 101. 63 102.06 102.46 102.83 103. 14 103.43 103.70 103.97 104. 17 104. 44 104.62 104.82 104.98 105. 18 105.37 105.48 ROOM¹ ROOM¹ ROOM¹ TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM>>

ROOM¹ ROOM¹ ROOM¹ 1

O 5

ID0

RWCU ROOMS f504 505 25 GPM STEAM LEAK SUMMER) 170 160 150 (3

140 1SO CL

'120 110 100 10 15 TIME (HRS) 20 25 Legend A ROOM 1 ~>

C3 ROOM 2

C t ROOM B

o

,I j,

ql

RWCU ROOMS ¹504/505 (25 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000
14. 000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 ROOM¹ I

115. 00 115.80 115. 88 I 15. 89 115 '0 115.91 117.35 119.08 120. 23 120.77 121.31 121.92 124. 12 125.56 126.54 127. 21 127.78 128.20 128.54 128.76 129. 14 129. 29 129.48 129.67 129.8'I 129.90 130. 16 130.35 130. 51 130.66 130.80 130.90 131. 00 131. 12 131. 22 131.32 131. 34 131.42 131. 49 131. 54 131. 63 131. 65 ROOM¹ 2

104. 00 106. 8 'I 106.87 106. 88

'I 06. 90 106.91 107. 34 I 07. 53 107. 63 107. 74 107.80 107.86 108. 15 108.34 108.45 108.59 108.72 108.83 108.91 108.93 109. 14 109. 10 109. 18 109. 23 109. 27 109.32 109.38 109.50 109.57 109.65 109. 71 109.78 109.84 109.89 109. 96 110.02 110.07 110. 11 110. 16 I 10. 22 110. 27 110.34 ROOM¹ 3

110.00 111.04 111.12 111.14 111. 16 111. 18 129. 13 137.83 144.26 147.23 149. 20 150.69 155. 11 157. 26 158.60 159.42 160. 11 160. 61 161. 04 16 I.34 161. 64 161.88 162.07 162.25 162. 41 162.52 162.77 163.00 163. 17 163.33 163.42 163.58 163.66 163.79 163.88 163.95 164.03 164. 10 164. 16 I64.20 164.28 164. 31 ROOM¹ ROOM>>

TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM>>

RWCU ROOMS $504/505 25 GPM STEAM LEAK WINTER 180 160 u

140 W

O 120 I

100 I

80 Legend a ROOM 1

PP Q

I00 60 0

10 15 TIME (HRS) 20 25 CI ROOM 2

~ ROOM

b 1

RWCU ROOMS ¹504/505 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 I9.000 20.000 21.000 22.000 23.000 24.000 ROOM¹ 180.00 79.92 79.95 79.95 79.95 79.96 84.75 87.38
89. 16 90.34
91. 19
91. 94
97. 17 100.67 103. 19 105.09 106.58 107. 71 108.67 109.65 110.38 I10.99 111.59 I12.00 112.55 1I2.85 113.67 114.08 114.65 115. 13 115.48 115.83 116. 11 116.49 116.60 116.81 117.08 117.35 117.43 117.56 117.83 I 17.97 ROOM¹ 2

76.00 76.05 76.05 76.05 76.02 76.08 77.22 77.03 76.97 77.04

77. 10
77. I9 77.52 77.72 77.91 78.05 78.18 78.25 78.36 78.57 78.51
78. 62
78. 68 78.72 78.79 78.82 78.96 79.00 79.03
79. II 79.22 79.22
79. 33 79.30
79. 46
79. 49 79.59 79.61 79.65 79.69 79.74 79.82 ROOM¹ 3
75. 00
74. 81
74. 77 74.75 74.74 74.72

'I 13. 15 121. 77 127.90 131.48 134. 15 136.36 143.27 147. 14 149. 55 151.21 152.47 153.38 154.11 155. 16 155. 15 I55.83 156. 18 156.53 156.73 157. 07 157.52 157.73 158.24 158.52 158.78 159

~ 01 159.22 159.40 159.53 159. 57 159.79 159.98 160 F 00 160. 13 160.27 160.38 ROOM¹ ROOM¹ TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹

(

f' o~ r0 I

W 0

E, ~

V

'l Pl

~ f

%It

SUSQ SES AREA SURVEY MAP Rx PWR REACTOR BUILDING-UNIT 1

4 I-I REACTOR WATER CLEAN-UP PUMPS I-501 2.

3 ~

4.

RWP iF DATE:

RAD INST HP g

CONTAMINATION INST RESULTS (OPM/100cm

)

5.

6.

7 8.

TIME:

AIR SAMPLER HP 4

9.

10.

11.

12.

13.

EFF.

SURVEY BY:

HP P

ACT.

BKG.

14.

15.

16.

17.

18.

SH 2 pCI/cc REVIEWED Health Ph sics Date 4-.

I6 I6 27-I S'IEAP, LOCATIONS CIRCLED.

RAD READINGS IN mR/hr.

UNDERLINE =

CONTACT RAD READINGS

--- =

RAD TAPE

-X-X- =

RAD TAPE 6 ROPE XXXX =

RAD ROPE 6 = A/S LOCATION

~

= S.o.p.

Z -5Oc)

= 2S.d

'be Ln m (A

ll m

w 4 V"- II29b Pf~

c. = /3 s'

t= 3'"

9= 2]37b P

~

qo 0

I (Q

II

~ <

~l 4

'0 II I<<

C=S.O'

/

l.=

8.0'-

rA'l

'O Ie el C)7 y I 63g

<<)

'-5o+

/See. ~ex g 5h cef )

ale'/<<e m,AM<<<<)oM AeeuOI X. A

'DP,~ JUPE"SECTION P*C,C I o(II

4/

Nt j/

v

~

I/

ff

REACTOR BUILDING-UNIT I SUSQ SES -

AREA SURVEY MAP EL.

4 '"1 HEAT EXCHANGER ROOM Rx PWR I-5O4 2.

3

~

4.

6.

7 ~

8.

RWP 4

DATE:

RAD INST HP g

CONTAMINATION INST RESULTS (DPM/100cm

)

5.

TIME:

AIR SAMPLER HP g

9.

10.

11.

12.

13 '

EFF.

SURVEY BY:

HP g ACT.

BKG.

14.

15.

16.

17.

18.

SH 3

pCI/cc REVIEWED:

Health Ph sics Date 4-(8IC Z7 i

SMEAR LOCATIONS CIRCLED.

RAD READINGS IN mR/hr.

UNDERLINE =

CONTACT RAD READINGS RAD TAPE

-X-X" =

RAD TAPE F

ROPE XXXX =

RAD ROPE 9 ~ A/S LOCATION

~

= S.O.P.

2 6

~

Z'-5oi /9-So3 (5'cc. ofhce~ ghee.+)

Q-5 o0 7 -50+

'I/ = bl f06 pp

~

Oo II II I

f OlO II'o R'.r.7zt qqp3 Lg~f(.5'-5 00 APPBJD l x. 4 Dg~ Z~PuT Sermon P~oc.

2. opal

D'

PPEL Form 2454 (10l83)

Cot. lr973401 Depb 4PE SCCA Date ~+19~

Designed by M~

Approved by PROJECT Cocle. H-SLD-OOS Sht. No.

~

of PENNSYLVANIAPOWER 8 LIGHTCOMPANY ER No.

CALCULATIONSHEET AbJAG~~

IZOOIN 54 A& DATA hieeuoic

~,

RoOrl Qo RCDOWL

+CS I4AJ 5LP g

+LA~

ED T&hp THK TVPF SLAB AREh Ga.LCuLATtOAJ Z-5'oo IOo/bo F 36" Z-soO Ioo/I 0 th t'-etta/5o9 t oo/eo

('2 > I <S.O-I3

~ S') (gS.>Z) + (>>.to )(IS.0 j A = so4 t,t+

0 = 7/ 5 -8'l~ '

7so '-8/i" =

Is.o L=

ll.o'=

169@

i)=)s.o'

= l&.S'+2,o.D

= 3/o,g

'=

548 ga

~

4 Ya Z-Soz/So3 io4-P,o r-soo Ioo// o L=

L=

A =

I S.o I'5, s 2o3+

777-Sl~" 76('-8'/2." = II.j r3 '

I/O I/(

Il/~

IO I/7 5OO/z zoS -llo/l,-o I<5/9o i-Soo T;/49O8 IOO 6o IE Io4/6 o 2.l I-40t/4ot.

looieo 0= IS.O L = (27. 0 -I3. 5')

-" I 3. 5 I A= zoag~

777-5'I/2.

75 o 8/2 41 Qg 7 5 I = 7T(3esz)(~i~i> j = t32.S A= tt4tZ g" 2

At'= 544 g (999 AttaottaDS~a)

$c'

PPI55. form 2454 (50I83)

Cat. 495340 I Dept IJPE WK5- 0 Date ~~

I 19'esigned by ~K Approved by PROJECT

~n.k.

M-SI D-opC Sht. No.

4 of Jt PENNSYLVANIAPOWER & LIGHTCOMPANY ER No.

CALCULATIONSHEET AzuAc~ Ro~ S~e DATA APPmOI)/ 4 Roo+

f2oo~

PzsIC 4 su 6 5~

bio ZP 7EQ P THK TfpK

&ms Aa~

~LCum~o<

Z-s'oO IOo/so e Z/5 1-5 O'L/503 tot /oo 33 Ig = ISO L=

S>.S'=so>gt I 7.0 I /5.o A = Zsoft~

Turbo ItJT eg.tJAL. VJ4LLS V3IW5+ ~~5 X-5oh Q L-SO+.

2/lo 1-sot/402 loo/6o 2ir3 Z-s oo I oo/6o 2/3 Z-5'04/Sos' I 0/6o 86 (36 5)(l.3.S)

=

(

5.65') (l3.5)

. 41'3 (6 I>.5-4..o

't.5'4.3

$t Z-5 oo IO%o Z 506/SOS-II %O '30 Z~ok I/%o 36 I< 1$

/3 0rt~OrS6I rZS/So tz Z ~l/~.

I>>/>>

21 53 I53,4 5

~ra~a L ~R~L ~

~ms z-s~Zz-sos IQ=

IS-0'=

2'7-0 A,= 4os'4.

q= I 0.7S'

= 3$.0'

= 3r3& $t H=IF 0 I = u).qS'I A - 3ll gt2 A= ('~"'~")( s o) = zoll.+

A = (~ stsr0)'(lq 25 ao).w 4-0(465)

+ (1Z-~r)(46.5)

I, IS6 Qt I

-0

  • gi 14

PPbL Form 2454 (s0r83)

Cat. 497340)

Dept. dPC MK Dale ~~r 19

'lo Designed by ~YLM Approved by PROJECT Sht. No.

~

of Il PENNSYLVANIAPOWER & LIGHT COMPANY ER No.

CALCULATIONSHEET ADJ4c&J7 ROOK SEAS D4TA PPPHJOIC A

SLA8 lg RooNI RooM oKsl6&

sLA&

SERI&

do ID TEileIp rypc r-SOO ra%O F l5'"

r-Soo l oo jrro SC.48 4(c'-EA CAL.r'( 47 40&

  • =(

s

)(les>-<2 o) n(@oI(I'-

+ (a ~s)(4S s).

A = II>ardf~

g= IS.O L= W~.S

h= qadi lioi:o: Wa aiooec cloaca coxne porn ic'efarences 2.4 lS Z."I 4,[so slaIx

/pe is led a.'- Isaac fxaragrapln 4 rn o$ r4etkodo loci

<<eciio>>.

I fPaoM Xio QOO gr I.D I

2.

3 7

5 9

Z-col I,-Sos/I-Sos

$-5'./ L-505 T-5'oo I-5o6 E-40'X-442Z T--roo8 t aywscc(sueeaassiov Fboq rlrae Seeeeq(l XrlrnOST Deer

PP8 L Form 2454 (I0/83t Col. 492340t Dept.

QPK M~

Date ~e-t 19 'lo Designed by ~K Approved by PROJECT lc.

-SL OO~

Sht. No.

~

of PENNSYLVANIAPOWER & LIGHT COMPANY ER No.

CALCULATIONSHEET DAT+ ~Pul Secmod -A. P~IX A I=Lou/ DavA:

Per I QZD M-I lio Rav. 2.u

)

Z-=O I z~o =f'~

co c g I

I ~ooc rn I

I>2.50 cflvl 5] 5'~ cf~

yucca

-(

74.

I-l I-

-'rax'.ttnn a<'n frere 4-Sos(Se'b x l. t rale,~ft'.r ai'r for~ I-I'0< ISo5 ~

I I

Inaxsfer oi~ frow r=sorr x I. I exhavsz at'r b

I I

2%0 CfM ZI750 l,7t'0 C(rn Ii S7Z cf~

C,IOW cfog g-S'opt ~o~,

2+Do haft< 5~epl I

I Z S~ M bure air@ Z-59I w I.l I

2I I5ocfN Z,750 Qw z-so4./sos:

(/ >/0 g C,7Pt SlJPPI) 2t',

I - ]

1,7&o c$rrt ltooo afrn transfer arr+> J-so.t x I-t

= tr76o ourn jPpvi &to~

I P~~ DA,~:

'Per-PB,LD H-I l41ReV. ZO Z-5'ol z; oosjsoz 2.oo ~

SuPI3lq civ X-l-l I,2.so efrrt ~stan ai'v frorrr s-soD x I

t III-50~

e*haV.d at~

7t'. I. I 2<50t3 C+A SVPPIst Qiv Q

I I

2-ISuO ~

QI44OQ.Sf aalu 5

I Zm gw I,>70 cf'~

l S'IS

~I7~o cQ 2;ISo ~

CfWL SIJI3t3lq 4r 4 I -I I, ta oo afrn extern.sp euv x I-I I(af o ~

Il~f>~

PPILL Form 2454 (10/83)

Car. 497340:

Date Q~t 1g~,

Designed by ~YA Approved by PROJECTCd~

Shf. No. ~of PENNSYLVANIAPOWER & LIGHTCOMPANY ER No.

CALCULATIONSHEET deAr lOWC Odrl m DAM Z4Pvt z~~woU APPEhGL 9 A

<-5'0/

(i ) / /6//rrnrC (IrJOre,~Or )

(2 ) Piping - Dora

+ DSO IAr Pe.r SEA -cZ-/2~

gay. p St2/

DSA -/o I bSC- /ol 08C-Io I 050- /OZ.

OGC-/0 Z.

AC-/04-EM-Io I CGC-/OZ ES C.-/03 de II b.&i3

b. 6 Z5'.

so Q. 5o

3. 5'0 0-so 4.s o O.s o 4;So ZL0

~7/rp I 5, 5oi 3.9x I Z.g Z.4-9.62.$

3.9&

3.82.6

3. S2.0

~~air o Ir

/2..6>S

/Z. &ZS

/o.so I O.S 0

8. go

/0.S 0

+.5o 4.so 4.S0 8.a I7 o 54'.0 9I o 26 o

// o (or.o

/I-S b3.o P au 0 8

o. 04f'35'/

Z

/o2

/oZ 0 038 o.oda 440

/20 0

/Zo 0

/2o P" 4 K-So2.:

(>)

L.IGIITlAIG(NORMAL)

(2)

POmP' I/ 2.ZI 8)

(3)

PiPwt & DATA 0 IZ I~ / Av SEA ~I2$

/2ev-0 I

lb ooo

/Ar Per Cole

/7G-/$ M,F e*

&BC-/0 I DeC-/0Z DD ZD 4.S'o" '.o~"

+ s o 3.624.

XdS 0C)

/0 So"

/0 So L F'~

28. o

/8. o k

0.8 c'-044 535 I=

0-8 O. 044 AS

/ Aasa'-

2

/0 2

//f 5 pSr.

Z-50 5 (Sh/VlG r ICA7 LOADS A5 /=OR.

Roo/fdI Z.- S 02)

~l l~

'I

PPSL Form 2<<54 (10/83)

Cat. <<973401 DepL IJ II4LCQ Date ~t 19 'Ib Designed by ~m Approved by PENNSYLVANIAPOWER IIt LIGHTCOMPANY CALCULATIONSHEET PROJ ECT Qxlc.

I4-SLD-OO ER No.

Sht. No.

8 of Il DP,M W'Ja<</<

5'ec:no "J - C PI ~ ~IW 4 Z-'DO/

(rt Irdwnu o(do~gr'h )

(z,)

ReGepJ l4x (I5-o F )

( 3 )

P/ / //1/O - DA T A 2 38/

/~r Per 5E'A-~-/2.g IZev. 0 s/

//

/

/

/

4;4 o'p

/lr Fpen 4 4.

/7& -/$ 6v. S

'VGC-Io2 DGC-/04.

DPC /03 E/

-/0 I ABC-/og OO

4. so

<<It 5Q 4;So

4. So 4.5o T.g
9. 624 S.C z,g 3.b2.4 3 Sz.4 3-8>

tcs IO 5o" IO.So

/o.so 4.5o

4. 5o

/4.o

'.o 95-0

/2. O 24-O 0.8 0.8 o.z d.S 0.8 ZuSOD C A C

k

o. O4td 0.044 0.040 0

o 7

S'3S F 44g 235

/2o IZo Pha sc.

2 2

2 2

z

/Ig l-5 o5

(/

7 L/6//7/hl5 (AIORAAI )

(< I

/alo/t/-/<<gee M l-4'/~o'/=)

(3)

PI p/PJCa D/rs / /th Z/ 3 8 g

/4'r, per SEA -EE-/Zg/ Rev. 0 3,8~

/hr, Pcr 6dc '/76-I<< rgb.5 D8C-/03 ZGC -/O I O+

4. s-o "

4" 5 o 00 Z<s 00 L A:

6 k

T PhoM P

3.6Lf

/0.<<0"I<<.0 0.3

.0400 231 p Z

Ii<<0 9-82.tc 4 5 o

/9 o O.8 Ct l2o Z.

//g o

/

/

/

/

PlOTE:

A8OVP-P/PI@& OihTA CAME FMK IZEFGEEVC 5 Z.2 2.3 2.Z Z.S'.6 8 2.7

PP8 L Form 2454 (10/83)

Cat. a973403 Dept. <~ MM Date ~at 19 rtrt Designed by R~~

Approved by PENNSYLVANIAPOWER 8c LIGHTCOMPANY CALCULATIONSHEET PROJECT Ca.lc 4-5LD-005 ER No.

E Sht. No.

DAM ~Pur GSC.moV - h,P~Ik 4

/t'oofy I!OLvfhf DEs/c /J 7 EgP DE.C /6IJ 7-5 0 I 2 -5'oZ.

7-5 og

7. ->0//

I-505

/4(ob2. P Z/374 2/94 9

/,74o 7/2/ /

//Lt

/2o f

/04. j&o

/O4. tbo

//6

&0

//o/6o 5%o7o O%o Vo/to 1%o 9o/to Roo~

I Rooa 9

Wo~:

(i)

R'oolv1 tfoc.~~/= /5 c+c.cd,k~D / ~

4'/tO DIM&)SiOfVS.

C<)

DL.</<+ +WQERATVrZE AUO AXATlVC )+et/ar r/ U4LuZ5 Are~ /=no~ /=x4~ ~pc.E g.//-6

PP5L Form 2454 (10/83)

Cat. 497340(

Dept. VPe MeC Date 2.~(

19~~

Designed by ~IS Approved by PROJECT C Lc Q-S(O-OOG Sht. No Io of IL PENNSYLVANIAPOWER &LIGHTCOMPANY ER No.

CALCULATIONSHEET atm ~PVr S~Tf~- APP~IX 6, F( oor2 P g,KA, Roow Z-501

27. 0 0

ll.o 4,o (5.5

'~0(

=

(3.5 (5'(.o) + l>.5((I.O)

AQ

=

837.0

( %oo) Vz. los.ojsio 4z. (os o) cor.<z x z

= zatt o g~

Aoo

~

8%7 0 LQS 0'=

o4.o

PPSL form 24S4 (10/83)

Car. <<97340r DepI.

APE NtEC Date ~~t 19~to Designed by IM,~<~

Approved by PENNSYLVANIAPOWER IIt LIGHT COMPANY CALCULATIONSHEET PROJECT C l~ 8-sco~oZ ER No.

ShI. No.

III oI 0am ~P~ Seem~

-APPcxOI X 4

( e( (WC AtE'6 FoR.

lZoOnrt 7-SoI 2-&08 IS ~ S 4'I 2 o IS-S A,

= (ta.9 t

1.5 coo<<.L)(st.o) Aee AtD

=

Tl (aa.s)

(

/aao)

'/a (st o-a(r.s.)uo4>) (at.s coo 4a)

= tgs.a

~ /5+/

'I st

~ E tws to

=

ttZ t gt

APPENDIX B ADDENDUM TO CALC 5 M-SLD-005, REV.

0

p E

ice hf\\

ja hg

ADDENDUM TO CALC 5 M-SLD-005, REV.

0 The addendum to the original analysis utilizes the same data inputs with the following exception.

The airflow data input has been changed to provide separate room exhausts in each of the three rooms under consideration.

For the original analysis, the rooms under consideration utilize a common exhaust duct located within the Penetration room.

Since the model assumes perfect mixing occurs within each room, the transfer air from the Pump/

Heat Exchanger rooms dilutes the temperature response for a leak in the Penetration room.

Additionally, the Penetration room is especially sensitive to a leak in any other room under consideration.

For this purpose, an additional set of runs are provided which models separate exhausts from each room.

This is intended to prevent any diluting affects from transfer air between the Pump/Heat Exchanger rooms and the Penetration room.

The exhaust register is located in the southeast corner of the Penetration room (a relatively common area between all three rooms).

The location suggests that the transfer air from the Pump/Heat Exchanger rooms would not mix appreciably with the air flow from the Penetration room.

Some mixing can be expected near the exhaust register, but it is not reasonable to assume this transfer air could significantly dilute the Penetration room temperature response during a steam leak.

This dilution affect caused by the transfer air helps to explain the need for such

a. low Steam Leak Detection setpoint in the Penetration room.

The following pages provide the results for the new analysis.

Temperature vs.

Time curves are provided along with the tabular results for each set of conditions analyzed originally.

The computer output supporting these results follow the curves.

Refer to the Results/Conclusions Section for a discussion of the affects of the ventilation system changes.

popes:

Due<'ar ~

Re~<simn l vevicA Cycle

> i4 u)o.S d<4rmi~~ ~op+~

vn<sc.e,llo~eous w~ hen+ loads regild cM~c. SKndq -st, room ~~+em Aa~ no% atlniee.d pyioe fo <npodvcing +he. w~4.

Since o~lg ~ p~e.+re+on Woo~ uJas eig~ific.ant~a agQc~Qp

~l( Ln.sos lmvolvivtg a. leak- >e Mis roow vJere rerun. (des<(f-5 imi~u.lcd In Appendix p ). ~e w.wainr<g cams Weve, ~of 0

mru~ +o So~e, *~4.

> a<nc~ 44asA'co~5 uJam no<- sig~igicanflq

@Beefed.

For ~so ve.nnaiwi<g ca.ms', We Roo~ + i ~I~ag~

ts ~oat'pwp<Hed by <)io<L~WZ 5 F'.

g F

govz

RWCU ROOMS S501

(

5 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000
1. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000
18. 000 19.000 20.000 21. 000 22.000 23.000 24.000 ROOMS I

115.00 115.00 I 14. 99 I 15. 01 114.99

'115.00 115.95 116.63 117.07 118.09 I 18. 54 118.90 119.78 120.52 120.98 121. 28 121.50 121. 75 122. 13 122. 16 122.37 122.49 122.69 122.70 122.79 122. 91 123. 19 123.22 123.34 123. 42 123.58 123.62 123.76 123. 71 123.78 123.85 123.77 124.00 124.03 124 02 124.09 124. 18 ROOMS 2

104.00 105.83 105. 88 105.81 105.91 105.88 106.01 106.04 106.02 106.02 106.05 106.04 106.55 106. 14 106. 15 106. 19 106. 23 106. 19 106. 20 106. 23 106.32 106. I/

106.23 106.22 106.23 106.24 106.23 106. 32 106.32 106.30 106.35 106.33 106.38 106.34 106.38 106.38 106.33 106.40 106.43 106.43 106.47 106.46 ROOMs 3

IIG.OO 110.00 110.01 110.00 110.00 109.97 I 10.07 110.06 110.01 109.94 I 10. 03 I 10. 01 110. IO 110.03 110. 01 110.01 110.06 110.05 110.02 110.04 110. 11 109.95 I 10. 01 110.02 110.02 109.99 109.96 110.03 110. 06 110. 0'I 110.03 109.98 109.98 109.99 109.99 109.98 109.92 110.00 109.99 109.98 110.00 109.98 ROOMS ROOMS TEMPERATURE (OEG F)

ROOMS ROOMS ROOMs ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS

t t

RWCU ROOMS $501 ( 5 GPM STEAM LEAK/SUMMER 440 F) 125 120 (3

115 Q

110 CL I

'f05 100 10 15 TIME (HRS) 20 Legend

~ ROOM CI ROOM 2

~ ROOM

RWCU ROOMS /501

(

GPM STEAM LEAK/WINTER)

TIME (VR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000

'10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000 21.000 22.000 23.000 24.000 ROOM$

I 80.00 80.00 80.00 79.99 79.98 79.98 82.95 90.08 93.47 94.58

95. 19
95. 76 97.79 99.06 100.09 100.94 101.63 102.24 102. 76 103.23 103.50 104.04 104.37 104.69 104. 96 105.38 105. 71 106. 12 106.49 106. 81 107. 11 107.34 107.62

'I 07. 82

'108. 06 108. 27 108. 46 108.60 108. 51 108.93 109.08 109.22 R OOMPH'

76. 00 79.66 79.63 79.76 79.76 79.78 79.84 79.76 79.82 79.81 79.85 79.86 80.24 79.93 79.96 79.98 80.00 80.01 80.03 80.05 80.06 80.06 80.09 80.09 80.11
80. 12
80. 14
80. 16 80.20 80.20 80.22 80.21 80.26 80.29 80.28 80.30 80.26 80.29 80.31 80.31 80.33 80.35 ROOMJY 3

75.00 76.46 76.74 76.82 76.85 76.87 77.09 76.91 76.89 76.88 76.93 76.95 77.03 77.01

77. 06 77.07 77.11 77.09
77. 12
77. 15 77.15
77. 16
77. 19
77. 19 77.20 77.21 77.23 77.25 77.28 77.28 77.30 77.31 77.33 77.34 77.35 77.36 77.35 77.37 77.39 77.38 77.40 77.42 ROOMS ROOM>>

TEMPERATURE (PEG F)

ROOMS ROOMS ROOMS ROOMS ROOMS ROOM>>

ROOMS ROOMS ROOM/

ROOMk'

RWCU ROOMS $501 ( 5 GPM STEAM LEAK/WINTER440 F) 110 IOO (3

LLJ O

LLI 90 I

I LLI CL I

80 70 10 15 20 Legend X ROOM 1

0 ROOM 2

~ ROOM 3

TIME (HRS)

A t 1

q4 J rt

RWCU ROOMS S501 (25 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000
1. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000
19. 000 20.000
21. 000 22.000 23.000 24.000 ROOMS I

I 15. 00 I 14. 87 115.00 115.02 115.01 115.01 130. 48 140.45 147.25 150.52 152.39 153.80 158.22 160.32 161.58 162.43 163. 10 163. 71 163.88 164. 12 164.38 164.67 164.89 165.06 165.30 165. 19 165.68 165.72 165.86 166.02 166.23 166.40 166.31

!66.50 166. 51 166.67 166. 61 166.87 166. 71 166.84 166.92 166.95 ROOMs 2

104. 00 105.75 105.88 105.90 105.91 105.92 106.56 106.64 106. 71 106. 93 106. 99 107.06 107.35 107.58 107.70 107.94 107.67 108.07 108.09 108.28 108.25 108.30 108. 4 I 108. 38 108.46 108.45 108.57 108.04 108. 7 I 108. 76 108.83 108.87 108.99 109.02 109.00 109. 10 109. 18 109.34 109. 17

'109. 32 109.45 109.44 ROOMS 3

110.00 110.00 110. 01 110.01 110.01 110.00 110.51 110.28 110.39 110. 61 110.62 110.72 I 10.81 110.93 111.03 111.22 111.07 111.30 111. 29 111.47 111.42 111.48 111.51 111.54 111.59 111.58 111.67 111.60 111.79 111.80 111.84 111.85 111.96 111.98 111.94 112.04 112.09 112. 17 1 12. 18 112. 17 112.26 112.27 ROOMS ROOMS TEMPERATURE (OEG F)

ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS ROOMS

II

t t

t RWCU ROOMS $501 (25 GPM STEAM LEAK/SUMMER 440 F) 170 160 150 LLI C5 140 I

130 LLI 120 110 100 10 15 TIME (HRS) 20 25 Legend

~ ROOM 0 ROOM 2

~ ROOM 3

RWCU ROOMS

>F501 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 I. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 I I. 000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000
21. 000 22.000 23.000 24.000 ROOMS 80.00 79.99 79.99 79.99 79.99 79.99 116.09 124.68 131. 50 135.20 138.00 140. 18 147. 11 150.89 153.22 154.85

'156.04 156.93 157.68 158.26 158.77 159. 18 159.54 159.86 160. 15 160.40 160.82 161. 18 161. 48 161. 74 161.95 162. 15 162.32 162.48 162.62 162.73 162.85 162.97 163.08 163. 16 163.25 163.33 ROOMS 2

76.00 79.67 79.76 79.75 79.77 79.78 80.50 80.37 80.48 80.56 80.65 80.73

81. 07
81. 33
81. 55 81.72
81. 79 81.96 82.07
82. 19 82.28 82.35 82.47 82.49 82.55 82.62 82.71 82.82 82.90 83.00 83.09
83. 17

'3.24 83.32

83. 41 83.47 83.54 83.65 83.72 83.82 83.89 83.96 ROOMP 3

75.00 76.46 76.75 76.82 76.85 76.87 77.73 77.37

77. 51 77.58 77.65 77.71 77.96 78.21 78.37 78.51 78.66 78.75 78.87 78.95 79.03 79.11
79. 18 79.24 79.32 79.41 79.64 79.81 79.99
80. 18 80.34 80.49 80.64 80.78 80.94 81.01
81. 16 81.31 81.43
81. 54
81. 66
81. 73 ROOM>>

ROOMS TEMPERATURE (OEG F)

ROOMS ROOMS ROOM>>

ROOMA'OOMk'OOMS ROOMs ROOMS ROOMt ROOMN

t t

t RWCU ROOMS $501 (25 GPM STEAM LEAK/WINTER440 F) 180 160 u

140 f20 100 80 60 IO TIME (HRS) 20 Legend E ROOM t

0 ROOM 2

~ ROOM 3

RWCU ROOMS >>504/505

(

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 1.500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000

'19.000 20.000 21.000 22.000 23.000 24.000 ROOM>>

I 115. 00 120. 12 120. 52 120.64 120.74 120. 81 120.84 120.83 120.88 120.92 120.98 121. 00 12'I. 10 121. 40 121.56 121. 63 121.81 121.93 122.01 122. 10 122. 19 122.34 122.36 122.42 122.47 122.54 122.73 122.85 122.95 123. 10 123. 18 123.11 123.40 123.44 123.56 123.62 123.72 123.83 123.89 124.08 124. 17 124.06 5

GPM STEAM LEAK/SUMMER)

ROOM>>

ROOM>>

3 110.00 111.05 111. 13 111. 16 111.17 111. 17 112.77 112.75

'I 13. 71 114.93 115.30 I '15. 63 116 66 117.30 117.77 118.05 118.45 118.66 118.92 119. 10 119.33 119.56 119.72 119.89 119.99 119.87 120.36 120. 51 120.72 120.87 121.04 121.61 121. 13 121. 19 121. 21 121. 35 121.31 121.47 121.45 121.56 121. 64 121. 66 ROOM>>

2 104.00 106.76 106.86 106.88 106.90 106.90 107.00 107.08 106.97 107.02 107.04 107.03 106.99 107. 15 107. 21 107. 18 107.24 107.28 107.32 107.33 107.35 107.38 107.39 107.37 107.42 107.36 107.48 107.52 107.53 107.62 107.59 107.44 107.64 107.64 107.68 107.64 107.73 107.76 107.77 107.82 107.84 107.80 ROOM>>

TEMPERATURE (OEG F)

ROOM>>

ROOM>>

R()OM>>

ROOM>>

ROOM¹ ROOM>>

ROOM

ia

RWCU ROOMS $504/505 5 GPM STEAM LEAK SUMMER) 125 120 C3 LLJ CL 110-CL l

105 100 10 15 TIME (HRS) 20 25 Legend

~ ROOM 1

0 ROOM 2

~ ROOM 3

0 4l 0

RWCU ROOMS /504/505 5

GPM STEAM LEAK/WINTER)

T I ME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000
1. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000
19. 000 20.000
21. 000 22.000 23.000 24.000 ROOMC 180.00 83.77 84.40 84.55 84.60 84.63 84.72 84.48 84.58 84.62 84.66 84.68 84.75 84.84 84.85 84.89 84.93 84.97 84.99 85.03 85.05 85.09
85. 12
85. 14
85. 16
85. 18 85.23 85.27 85.31 85.35 85.38 85.41 85.45 85.48 85.51 85.54 85.57 85.60 85.62 85.65 85.68 85.69 ROOMS 2
76. 00
76. 01 76.05 76.06 76.05 76.04 76.11 76.04
76. 12
76. 12
76. 13
76. 14
76. 15
76. 19
76. 17
76. 18
76. 18 76.20
76. 19 76.21
76. 21 76.22 76.22 76.22 76.23 76.23 76.23 76.24
  • 76.25 76.24 76.27 76.28 76.27 76.28 76.28 76.29 76.31 76.30 76.29 76.30 76.32 76.30 ROOMS 3

75.00

74. 81
74. 77 74.76 74.75 74.74 77.92
87. 12 89.80 90.68
91. 28
91. 75 93.65 94.94 95.93 96.76 97.45 98.05 98.58 99.05 99.49 99.86 100.22 100.54 100.83 101. 11 101. 61 102.07 102.47 102.82 103. 14 103.45 103.70 103. 96 104.20 104.44 104.63 104.83 105. 01 105. 16 105. 32 105.47 ROOMJF ROOM>>

TEMPERATURE (OEG F)

ROOM/

ROOM>>

ROOMN ROOM/

ROOMu ROOMs ROOMAF ROOMs ROOM4'OOMS

RWCU ROOMS $504 505 5 GPM STEAM LEAK WINTER 110 105 100 C3 C3 95 LLI 90 CL 85 80 75 70 10 15 TIME (HRS) 20 Legend

~ ROOM 1

CI ROOM 2

~ ROOM 3

RINCU ROOMS JF504/505 (25 GPM STEAM LEAK/SUMMER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 I. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000 19.000 20.000 21.000 22.000 23.000 24.000 ROOMA(

I I 15. 00 120. 12 120.52 120. 65 120.74 120.8'I 120.76 120.68 120.84 120.89 120. 91 120. 97 121. 24 121. 39 121.59 121. 78 121.92 122.07 122.22 122.35 122.44 122.57 122.69 122.94 122.89 123.01 123. 19 123.38 123.51 123. 67 123. 83 123.95 124. 14 124.23 124.35 124.47 124.58 124. 71 124.81 124. 90 125.00 125. 10 ROOMS 2

104.00 106.80 106.84 106.88 106.90 106. 91 107.28 107.53 107.62 107.73 107.79 107.90 108. 00 108.40 108.60 108.73 108.77 108.89 108.97 109.06 109.09 109. 17 109.20 109.03 109.30 109. 40 109.57 109.60 109.68 109.76 109.78 109.84 109.80 I 10.01 109. 95 110.05 110.08

'I 10. 14 110. 21 I IO. 26 110.24 110.30 ROOM/

3 110.00 111.05 111. 13 111.15 111. 17 111. 18 129.04 137.86 144.27 147.25 149. 23

'150. 72 155. 19

'157. 29 158.58 159. 51 160. 13 160. 61 161. 06 161. 36 161. 64 161.87 162.09 162.22 162.42 162.59 162.86 163. 01 163. 18 163.34 163.50 163.55 163.70 163.79 163.88 163.95 164. 05 164. 10 164. 16 164. 17 164.26 164.32 ROOMJY ROOMS TEMPERATURE (DEG F)

ROOMS ROOMS ROOMe ROOMS ROOMg ROOM>>

ROOMP ROOMS ROOMS ROOMS

t RWCU ROOMS f504 505 25 GPM STEAM LEAK SUMMER) 170-160 150 (3

140 LLI 130 120 1IO 100 10 15 TIME (HRS) 20 25 Legend 0 ROOM I

Cl ROOM 2

~ ROOM

f laf W~P 4

RWCU ROOMS ¹504/505 (25 GPM STEAM LEAK/WINTER)

TIME (HR) 0.000

0. 100 0.200 0.300 0.400 0.500 0.550 0.600 0.700 0.800 0.900 1.000 I. 500 2.000 2.500 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000 16.000 17.000 18.000
19. 000 20.000 2'I. 000 22.000 23.000 24.000 ROOMP-I 80.00 83.76 84.40 84.55 84.60 84.67 84.91 84.67 84.79 84.81 84.87 84.89 85.05 85.24 85.37 85.48 85.63 85.73 85.88 85.93 86.06
86. 12
86. 19 86.29 86.36 86.41 86.57 86.34 86.75 86.86 86.98 87.08 87.08 87.26 87.32 87.37 87.55 87.53 87.64 87.70 87.80 87.86 ROOM¹ 2

76.00

76. 10
76. 14
76. 18 76.05
76. 10 77.00 76.96 77.03 77.09 77.22 77.39 77.74 78.00 78.22 78.36 78.54 78.65 78.76 78.83 79.00 78.99 79.03 79.11
79. 13
79. 19 79.26 79.37 79.38 79.49 79.59 79.62 79.55 79.70 79.73 79.74 79.84 79.90 79.94 79.97 80.00 80.08 ROOM¹ 3

75.00 74.79 74.73 74.44 74.71 74.57 113.40 121. 81 127.92 131. 55 134. 12 136. 31 143. 31 147. 18 149.55 151. 23 152.48 153. 46 154. 21 154.90 155.39 155.86 156.23 156.53 156.88 157. 13 157. 54 158.07 158. 19 158.56 158.82 159.07 159.23 159.40 159. 61 159. 71 159.80 160.00 160.04 160. 18 160.28 160.37 ROOM¹ TEMPERATURE (DEG F)

ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹ ROOM¹

pl

'8 e

I t

t t

RWCU ROOMS $504 505 25 GPM STEAM LEAK WINTER 180 160 Lu 140 120 CL I

100 I

80 60 0

10 15 TIME (HRS) 20 25 Legend

~ ROOM 1

0 ROOM 2

~ ROOM 3

t

ATTACHMENT C

P'I

~l