ML17157A520

From kanterella
Jump to navigation Jump to search
Discusses Electrical Distribution Sys Insp Repts 50-387/90-200 & 50-388/90-200 on 900813-17 & 0827-31 & Forwards Notice of Violation
ML17157A520
Person / Time
Site: Susquehanna  
Issue date: 01/14/1991
From: Hodges M
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Keiser H
PENNSYLVANIA POWER & LIGHT CO.
Shared Package
ML17157A521 List:
References
NUDOCS 9101230039
Download: ML17157A520 (3)


See also: IR 05000387/1990200

Text

JAN 14

199~

Oocket Nos.

50-387

50-388

License

Nos.

NPF-14

NPF-22

Pennsylvania

Power 5 Light Company

ATTN:

Mr. Harold W. Keiser

Senior Vice President - Nuclear

2 North Ninth Street

Allentown, Pennsylvania

18101

Gentlemen:

Subject:

NRC Combined Inspection

Report Nos. 50-387;388/90-200

This letter refers to the special

NRC Electrical Distribution System Functional.

Inspection

conducted during August

13 through

17 and August 27 through 31,

1990.

The inspection

included

a review of activities authorized

by

NRC License

Nos.

NPF-14 and

NPF-22 for Susquehanna

Steam Electric Station Units

1 and 2.

Areas

examined during the inspection

have

been

documented

in

NRC Combined Inspection

Report Nos. 50-387/90-200

and 50-388/90-200,

which was forwarded to you on

October

15,

1990.

Based

on the results of this inspection,

certain of your activities appear to

be in violation of NRC requirements,

as set forth in the Notice of Violation,

enclosed

herewith

as Appendix A.

We are concerned

about your improper applica-

tion of undervoltage

relays

and your failure to evaluate

the drifting of over

current relays,

undervoltage

relays,

and timers and your failure to reassess

their surveillance intervals.

Drifting of instruments

outside their allowable

calibration range could result in inoperable safety-related

equipment which

would place the plant in an unanalyzed condition.

We are also concerned with

your use of inadequate

test procedures

and inappropriate test methods in your

testing of dc circuit breakers.

The test methods

used were not,representative

of actual

service conditions.

These violations have

been categorized

by Severity Level in accordance

with the

"General

Statement

of Policy and Procedure for NRC Enforcement Action," 10 CFR Part 2, Appendix C (Enforcement Policy).

You are required to respond to this

letter and in preparing your response,

you should follow the instructions in

Appendix A.

9iOi230039 9iOii4

PDR

ADQCK 05000387

8

PDR

OFFICIAL RECORD

COPY

. HATEHHII/13/90 - 0001.0.0

(

11/13/90

Pennsylvania

Power 5

Light Company

JAN 14 891

2

Your cooperation with us in this matter is appreciated.

Sincerely,

Marvin W. Hodges,

Director

Division of Reactor

Safety

Enclosure:

Appendix A, Notice of Yiolation

'cc w/encl:

A.

R. Sabol,

Manager,

Nuclear guality Assurance

J.

M. Kenny, Licensing Group Supervisor

R.

G. Bryam, Superintendent

of Plant-SSES

S.

B. Ungerer,

Manager, Joint Generation

Projects

Department

J.

D. Decker,

Nuclear Services

Manager,

General Electric Co.

B. A. Snapp,

Esquire, Assistant Corporate

Counsel

H.

D. Woodeshick,

Special Office of the President

J.

C. Tilton, III, Allegheny Electric Cooperative,

Inc.

Public Document

Room (PDR)

Local Public Document

Room (LPDR)

Nuclear Safety Information Center

(NSIC)

NRC Resident

Inspector

Commonwealth of Pennsylvania

bcc w/encl:

Region I Docket

Room (with concurrences)

R. Bellamy,

DRSS

P. Swetland,

DRP

R. Blough,

DRP

P.

Kaufman,

DRP

J. Caldwell,

EDO

M. Thadani,

NRR

J. Jacobson,

NRR

RI:DRS

athew

11/i(/90

RI:DRS

Lara

~y

11/(f/90

RI:DRS

Anderson

11//(/90

RI: DRS

Dur~

Wwgo

ll/83/90

RI:DRS

Hodges

~/Q/pl

OFFICIAL RECORD

COPY

MATEHWll/13/90 - 0002.0.0

11/13/90