ML17138B805
| ML17138B805 | |
| Person / Time | |
|---|---|
| Site: | Susquehanna |
| Issue date: | 08/13/1980 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | |
| Shared Package | |
| ML17138B800 | List: |
| References | |
| 50-387-80-17, 50-388-80-11, NUDOCS 8102240124 | |
| Download: ML17138B805 (1) | |
Text
APPENDIX A
'NOTICE 'OF 'VIOLATION Pennsylvania Power and Light Company Docket No. 50-388 This refers to the inspection conducted by a representative of the Region I (Philadelphia) office at the Susquehanna Steam Electric Station, Unit No.
2, Berwick, Pennsylvania, of activities authorized by NRC License No.
CPPR-102.
During this inspection, conducted on July 8-11, 1980, the following apparent item of noncompliance was identified.
10 CFR 50, Appendix B, Criterion V, states, in part, that:
"Activities affecting qual.ity shall be prescribed by documented instructions, procedures, or drawings...'nd shall be accomplished in accordance with these instructions, procedures, or drawings."
The Susquehanna PSAR, paragraph D.3.3.3, states, in part, that:
"General procedures for carrying out;.. construction are contained in the following...
documents...
Bechtel general and technical engineering standards..."
The Bechtel Technical Specification for. Forming, Placing, Finishing, and Curing Concrete, 8856-C-8, paragraph 18, Inspection states, in part, that:
Inspection of all work... shall include the following:
a ~
Inspection of forms... joints, cleanups, waterstops....prior to concrete placement.
d.
Inspection of concrete, after form removal, for rock pockets, grout leaks, and other imperfections.
Contrary to the above, on July 8, 1980, loose debris was observed in the
'onstruction joint of concrete placement 391-W-21 at approximate elevation 702', azimuth 142. - 30', in the Unit No.
The debris caused an.imperfection approximately 4 feet in length by 1 1/2 inches in height and in excess of 3 inches in depth.
The Field Inspection Plan C-8, 1, 2, 3, - 391-W-21 indicates that satisfactory preplacement cleanliness inspection was performed and that no post placement inspection was made.
This is an infraction.