TWO NORTH NINTH STREET, ALLENTOWN, PA. 18101 PHONEr (215) 821 ~ 5151 NORMAN W. CURTIS Vice Presidenr-Engineering 1L Construction-Nuclear 821-5381 November 19, 1980 Mr. Boyce H. Grier, Director Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 SUSQUEHANNA STEAM ELECTRIC STATION IE BULLETIN 80-03 ER 100450 FILE 841-4 PLA-574 DOCKET NOS.

50~387 AND 50-388

Dear Mr. Grier:

The following information is provided in response to IE Bulletin 80r03, "Loss of Charcoal From Standard Type II, 2 Inch, Tray Adsorber Cells."

Refer to our previous letters PLA-463 (March 25, 1980)and PLA-520 (July 30, 1980) explaining the delay in our response.

IE Bulletin actions to be taken (CP) 1.

Only one type of the subject cells is used at Susquehanna.

Results of visual inspection are provided in the attached inspection report.

This completes our response to IE Bulletin 80-03.

Very truly yours, N.

W. Curtis RMH:mks Attachment cc:

Director Division of Fuel Facility and Materials Safety Inspection Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Mr, R, M, Gallo U.S, Nuclear Regulatory Commission P.O.

Box 52 Shickshinny, PA 18655 Mr. Lou Narrow U.S. Nuclear Regulatory Commission 631 Park Avenue King: truss'ia, PA.. 19406 6 gg P E N N S Y L Y A N I A POWER IL L I G H T COMPANY SL 0 ggy

ITEMS INSPECTED:

HANUPXCUJRER:

HODEL NO..:

SERE'OS.:

t INSPECTION REPORT 2".Tray Type Chazcoal Absorber Cell Parr Fi1ter Company NPP-2, Type II 03442 03443 03445 03448 03449 INSPECTION GUXDE:

ANSI N510-1980 INSPECTION RESULTS:

1 kll five filters inspected showed no signs of screen casing separation.

2 Screen/casing integrity is maintained by spot welding screen to casing.

fields were on l" centers or less.

~ 3 The perforated screens are supported on 6" centers across the face of the filter.

4 The gasket around the fill/handle azea showed uniform compression and a tight seal.

.5 No evidence of charcoal leakage could be found at any seam or gasket.

INSPECTION PERFOR."Z3 BY INSPECTION WITNESSED BY R.A'res~~

- Project Construction h

Shezwood

.Bechtel QC H.B - Bechte1 witnessed the inspection of 3 of 5 ce11s, Nos.'03442,

03445, 03448.