~gN HtQy+

'o 0

I C

Cy

'~

~O

+ 1k**+

UNITED STATES NM EAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 pe 0 5 584 MEMORANDUM FOR:

James P. Knight, Assistant Director for Components and Structures Engineering Division of Engineering 5 fL{

Geor ge Lear, Chief Structural and Geotechnical Engineering Branch Division of Engineering FROM:

P. T.

Kuo-,. Leader Structural Engineering Section B-Structural and Geotechnical Engineering Branch Division of Engineering Harold Polk,. Structural

Engineer, Structural Engineering Section B

Structural and Geotechnical Engineering Branch Division of Engineering

SUBJECT:

TRIP REPORT* FOR MEETING OCTOBER 18,

1984, WITH PGEIE
  • ON DIABLO CANYON UNIT 2 AUDIT On October 18, 1984, two members of the NRC staff, P.. T.

Kuo and Harold Polk along with the NRC consultants, C. 'Miller, C. Constantino, A.

Philippacopoulos, P. Bezler and P.

C.

Wang of Brookhaven National Laboratory met with PGKE Diablo Canyon Project (DCP) staff at City College of New York.

The purpose of. the meeting was to continup the staff audit on the material provided by PGEE on October 12, 1984 in response to the staff's request,.

see Enclosure 1 for the list of material provided.

Each of the major items (1 thru 4) was discussed with the DCP staff so that the NRC staff. could fully understand the material supplied.

Items that were identified as requiring additional information from the DCP are shown on Enclosure 2.

cc:

See next page.

'I

-g q { { {'

&@3

. T. Kuo, Leader tructural Engineering Section B

Structural and Geotechnical Engineering Branch Division of Engineer ing p.r

'Harold Po k, S

ctural Engineer Structural Engineering Section B

Structural and Geotechni ca 1 Engineering Branch Division of Engineering

Knight cc.;

R. Vollmer G. Lear HW~Schiar14 ng P.

Kuo M. Reich, BNL

43 INVENTORY OF CIVIL/STRUCTURAL/ELECTRICALINFORMATION SENT TO NRC (H. E.

SCHIERLING) AND BNL (M. REICH)

ON OCTOBER 12, 1984 l.

Annulus Structure a.

Tangential Beam Evaluatlon (Attachment A)

A-1'eam Location Dra<ng,, El.. 101',

guad B (members B1266 and B1276)

A-2 Gale.

No. 1005C-l, Rev. 0, pgs.

1 and 2, Parameters for Code and Check by GT STRUDEL A-3 A-4 Calc.

No. 1005C-1, Rev. 0, p. 6, calculation to determine the CODETOL.parameter for GT STRUDL (see page 2.2.5-130 of Attachment E)

A-5 Calc.

No. 1005C-.1, Rev. 0, p; ll (prep. sheet for GT STRUOL

)nput)

A-6 Beam Input - GT STRUDL A-7 Member forces for code check thru

.A-12 A-13 DE Computer code check"

- thru A-28.

A-29 DDE computer code check thru A-41 A-42 Hosgrf computer code check thr u A-53 Special Notes

, 1 (1)

Beams B1266 and B1276 do not.have torsion loads.

For beams with tors)onal, loads,'ee Attachment D.

(2)

There. are seven tangential beams stfffened by a T-section.

In all cases; the tors$ ons are small.

(3)

The stiffened T-portfon of the beam was )gnored

$ n res$ st$ ng loads.

0052s

b.

Radial Beam Evaluat)on (Attachment B)

B-l Computer plot with beam

$ dent$ f$cat$ on, El. 101',

squad.

B B-2 Calc.

Xo. 1005C-l, Rev. 0, p. 10, parameter input code check B-3 Member forces fot code check thru B-8 B-9 DE, DDE, and Hosgrf code check thru B-13 c.

Column Evaluation (Attachment C)

C-1 Calc.

Xo. 1009C-l, Rev. 0, pgs.

8, 9, and 30 thru C-3

'C-4 GT STRUDL data. for column R15 and f15 thru C-8 d.

Horizontal Sef'sm$ c Analysis (1)

Descrfptfon of Model (a)

Gale.

Xo. 900C-1, Rev. 0, 20 Hi. Frequency Stu+,

Generat)on of Composite Damping, Multiple Support Method of Response Spectra

{b)

Calc.

Xo. 900C-2, Rev. 0, 20 Hz. Frequency Study, Horizontal Model, Calc. of Column Stfffnesses at El. 106'.

(c)

Gale.

Xo. 900C-3, Rev. 0, 20 Hz. Frequency

Study, Development of Horizontal Model, Interior Structure and Annulus Structure at El. 106'.

(2)

Computer'r)ntout of Input and Output Data (a)

Calc. 'Xo. 904C-'1, 'Rev. 0, 20 Hz. Frequency Study-Horizontal Model, EM Earthquake Tfme-History Analys)s (Xewmark Hosgrf), Output Accelerations at Annulus Pipe Supports for Lines K17-2314-3 and SG-3060-4.

e.

'Attachment D

a ~.

Calc.

Xo. 1007C-1, Rev. 0, p.

19 and 20, plus computer input/output.

f.

Attachment E

a.

Pages,2.2.5-127 through 2.2.5-160 of GT STRUDL Manual.

'(

2.

Raceway Supports a.

Calc.

No. 2CG-91-1, Rev.

0 b.

Gale.

No.26-176, Rev.

1 c'.

LCR Aid f2 3.

Turbine Building a.

b.

Dwg. No. 443117, Rev. 1, Turbine Building Structural Steel, Plan of D. 140'-0." South Dwg. No. 443118, Rev. 2, Turbine Building Structural Steel, Plan't Elevation 123'-0" c.

Dwg. No. 443121<

Rev. 5, Turbine Building Structural Steel, Plan of Elevation 119'0 South d.

- Dwg. No. 443123, Rev. 4, Turbine Building Structural Steel Plan of El., 104'0" and 107'-0" South e.

Roof Truss Stiffness Matrices, Calc.

No.. 64-T-275, Rev. 0, pgs.

366, 389, 390, and 391.

\\

4.'uried Conduit

'wg. 500820 Rev. 7, Sht.

4 of 4 - General Arrangement of Elect. Pull Boxes 4 Duct Runs - Unit 1 4 2 Dwg. 57683 Rev. 12, Sht 3 of 3 -General Arrangement of Elect. Pull Boxes 8 Duct runs - Unit-1

~

'wg.

500615 Rev.

4 - General Arrangement of Electrical Pull Boxes

h. Duct Runs - Unit 2 Dwg. 500682 Rev 16 - General Arrangement of Electrical Pull Boxes and Duct Runs - Unit 1 Dwg. 500817 Rev 7 - Condui 8 Lighting Layout - Intake Structure Plan at Elev. +5'.0" -,Unit 1 Dwg. 500614 Rev.

11 - Genera1 Arrangeme'nt of Electrical Pull Boxes and Duct Runs - Unit 2 Dwg. 50029 Rev; 43 - Sheets 16, 23, 25, 28, 29, 30, 34, 37 and 143.

Notes, Symbols and Typical Details for Raceways and Hire

e

At the time of the. original design, calculations. were not deemed necessary for the condu jts, s$ nce (a)

The connection at the building structure allows for se$ sm$ c

movement, and (b)

Conducts are only prov$ d$ ng voids

$ n the soil for pulling of cables and 'do not serve any other structural function.

0052s

\\

i ENCLOSURE 2 DIABLO CANYON OCTOBER 18, 1984.AUDIT CONTINUATION REQUIRED ITEMS The following items were identified by the staff during the October 18, 1984 design calculation audit continuation meeting held at City College New York.

l.

BURIED CONDUIT a.

Design calculations for the buried electrical conduits currently in place at the plant site.

2.

TURBINE BUILDING a.

Calculations showing the adequacy of the concrete buttresses.

b.

Calculations for the steel floor plates used to distribute the floor loads showing the plates meet the buckling and stress criteria considering. the interaction of all stress components.

3.

CONTAINMENT ANNULUS a.

Calculations for the justification of the 20 Hertz cutoff

~

frequency.

The calculations are similar to the Unit 1 calculations.

Additionally, provide individual stress check calculations for critical members.

b.

Provide the justification for the screening criteria used in selecting members for detailed torsional analysis.

c.

Provide 'a representative sample calculations for a member that was evaluated for a high torsional load.

This member should be one that was not reinforced to satisfy the 20 Hz minimum frequency criteria.

4.

RACEWAY SUPPORTS a ~

b.

Provide the basis for the-al-lowable stresses used in the design of the'supports.

Provide the. raceway-weight. and justification thereof,. used in the support design.

c.

Provide pertinent design drawings that can be used to verify the locations of the supports.

I

r d.

Confirm that the use of the factor KB used in the support calculations is correctly applied in the design aid LCR AID

'82.

e.

The dates shown in calculation package 25-176 for the originator and checker do not follow chronologically thru the sheets.

Provide.clarification:for the order of the calculations.

f..

The. reference cited on page 13 of calculations.25-176 is not contained in the package as indicated.

Provide the reference.

g.

Provide the verification that the information contained in design aid LCR AID 82 is applicable to the raceway support members.

h.

Provide the calculations for the transverse support KX.460 and the longitudinal support 25-176.

~ W

'