UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 IN IAGARA MOHAWK OWE CORPORAT 0

~DOCK Q. 50-410 PO N

UC AT ON UN DMENT TO F

C 0

RAT NG C

Amendment No.

48 License No. NPF-69 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Niagara Mohawk Power Corporation (the licensee) dated April 7,

1993, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter '1; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been. satisfied..

2.

Accordingly; the license is amended by changes to the Technical Specific'ations's indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-69 is hereby amended to read as follows:

9310080108 9'30930 PDR 'DQCK',,050004i0, P

'PDR

i

c ons nd nvi onment P ote t o The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, both of which are attached

hereto, as revised through Amendment No. 48 are hereby incorporated into this license.

Niagara mohawk Power Corporation shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance to be implemented within 30 days.

FOR THE NUCLEAR REGULATORY CONNISSION

(.f (I

< Robert apra, Direct r

. Project rectorate I-I Division of Reactor Projects I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

September 30, 1993

DM 48 C

MENT 0

C NS AM NDM NT AC OP N

C NS N

-6 D

K 50-0 Revise Appendix A as follows:

Remov Pa e

3/4 1-19 Insert Pa 3/4 1-19

REA TI TY NTR L

Y TEM 41 A DBYLI ID NTR L

Y TE LIMITIN NDITI N F

R PERATI N

3.1.5 The standby liquid control system shall be OPERABLE.

  • >>:0 *0 OO IOOO

~TQg:

a.

b.

With one pump and/or one explosive valve inoperable, restore the inoperable pump and/or explosive valve to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

With the standby liquid control system otherwise inoperable, restore the system to OPERABLE status within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

VE LLAN E RE IREIVIENT 4.1.5 The standby, liquid control system shall be demonstrated OPERABLE:

a.

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying that; 1.

The temperature of the sodium pentaborate solution in the storage tank is greater than or equal to 70'F.

2.

3.

The available volume of sodium pentaborate solution is within the limits of Figure 3.1.5-1.

The temperature of the pump suction piping is greater than or equal to 700F.

NINE MILE POINT - UNIT 2 3/4 1-19 Amendment No. 48