UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 June 23, 1993 Docket No. 50-410 Hr. B. Ralph Sylvia Executive Vice President, Nuclear Niagara Mohawk Power Corporation 301 Plainfield Road
- Syracuse, New York 13212
Dear Hr. Sylvia:
SUBJECT:
NINE MILE POINT NUCLEAR STATION, UNIT 2 RESPONSE TO NRC BULLETIN 93-02, "DEBRIS PLUGGING OF EMERGENCY CORE COOLING SUCTION STRAINERS" (TAC NO. H86587)
This letter acknowledges receipt of Niagara Hohawk Power Corporation's (NHPC's) response dated June 10, 1993, to NRC Bulletin 93-02 (Bulletin).
The Bulletin was issued Hay 11, 1993, to all nuclear power reactor licensees.
It requested licensees to identify fibrous material in the primary containment, take any necessary compensatory
- measures, and remove any such material.
NHPC's response stated that no fibrous filter material or other temporary sources of fibrous material, such as described in the Bulletin, were identified as being installed or stored in the containment.
Based on that, we consider your actions to be complete.
Please retain any records of your actions in response to this Bulletin, as subsequent inspection activities may be conducted in regards to this issue.
Should you have any questions, please contact me at (301) 504-1406 or the Lead Project Manager for this issue, John B. Hickman at (301) 504-3017.
Sincerely, cc:
See next page jo E. Menning, Project Manager Project Directorate I-1 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
~5007~<
9306280251 930623 PDR ADOCK 05000410 PDR
C
'I H
J
~~
J.
II
Hr. B. Ralph Sylvia Niagara Mohawk Power Corporation Nine Mile Point Nuclear Station Unit No.
2 CC:
Mark J. Wetterhahn, Esquire Winston
& Strawn 1400 L Street, NW.
Washington, DC 20005-3502 Hr. Richard Goldsmith Syracuse University College of Law E. I. White Hall Campus
- Syracuse, New York 12223 Resident Inspector Nine Mile Point Nuclear Station P. 0.
Box 126
- Lycoming, New York 13093 Gary D. Wilson, Esquire Niagara Mohawk Power Corporation 300 Erie Boulevard West
- Syracuse, New York 13202 Mr. David K. Greene Manager Licensing Niagara Mohawk Power Corporation 301 Plainfield Road
- Syracuse, New York 13212 Hs.
Donna Ross New York State Energy Office 2 Empire State Plaza 16th Floor
- Albany, New Yor k 12223 Supervisor Town of Scriba Route 8, Box 382
- Oswego, New York 13126 Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Charles Donaldson, Esquire Assistant Attorney General New York Department of Law 120 Broadway New York, New York 10271 Hr. Richard H. Kessel Chair and Executive Director State Consumer Protection Board 99 Washington Avenue
- Albany, New York 12210 Hr. Hartin J.
HcCormick Jr.
Plant Manager, Unit 2 Nine Hile Point Nuclear Station Niagara Mohawk Power Corporation P. 0.
Box 32
- Lycoming, New York 13093 Hr. Neil S.
Cams Vice President Nuclear Generation Nine Hile Point Nuclear Station Niagara Mohawk Power Corporation P. 0.
Box 32
- Lycoming, New York 13093
l
I 4
gt June 23, 1993 Docket No. 50-410 Hr.
B. Ralph Sylvia Executive Vice President, Nuclear Niagara Mohawk Power Corporation 301 Plainfield Road
- Syracuse, New York 13212.
Dear Hr. Sylvia:
Distributi on:
Docket Fil'e NRC 3 Local PDRs PDI-1 Reading SVarga JCalvo RACapra
- RBarrett, 8H7 CVogan
CCowgill, RI
- JHickman, 13D1
SUBJECT:
NINE MILE POINT NUCLEAR STATION, UNIT 2 RESPONSE TO NRC BULLETIN 93-02, "DEBRIS PLUGGING OF, EMERGENCY CORE COOLING SUCTION STRAINERS" (TAC NO. H86587)
This letter acknowledges receipt of Niagara Mohawk Power Corporation's (NMPC's) response dated June 10, 1993, to NRC Bulletin 93-02 (Bulletin).
The Bulletin was issued Hay 11,
- 1993, to, all nuclear power reactor licensees.
It requested licensees to identify fibrous material',in the primary containment, take any necessary compensatory
- measures, and remove any such material.
NHPC's response stated that no fibrous filter material or other temporary sources of fibrous material, such as described in the 'Bulletin, were "
identified as being installed or stored in the containment.
Based on that, we consider your actions to be complete.
Please retain any 'records of your actions in response to this Bulletin, as subsequent inspection activities may be conducted in regards to this issue.
Should you have any questions, please contact me at (301) 504-1406 or the Lead Project Manager for this issue, John B. Hickman at (301) 504-3017.
Sincerely, Original signed by: