Application for Amend to License DPR-63,revising Tech Specs 3.1.2 & 4.1.2 Re Liquid Poison Sys & Associated Bases
ML17055D675
Person / Time
Site: Nine Mile Point 
Issue date: 03/07/1988
From: Mangan C
NIAGARA MOHAWK POWER CORP.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
Shared Package
ML17055D676 List:
References
NMP1L-0231, NMP1L-231, NUDOCS 8803170254
Download: ML17055D675 (10)


Text

- REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:8803170254 DOC.DATE-88/03/07 NOTARIZED-YES FACIL:50-220 Nine Mile Point Nuclear Station, Unit 1, Niagara Powe AUTH.NAME AUTHOR AFFILIATION MANGAN,C.V.

Niagara Mohawk Power Corp.

RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Application for amend to License DPR-63,revising Tech Specs re liquid poison sys.

DISTRIBUTION CODE:

AOOID

.COPIES RECEIVED:LTRj ENCL /

SIZE:

TITLE: OR Submittal:

General Distribution NOTES:

DOCKET 05000220 RECIPIENT ID CODE/NAME PDl-1 LA BENEDICT,R INTERNAL: ARM/DAF/LFMB NRR/DEST/CEB8H7 NRR/DEST/RSB 8E ILRB12 REG FILE 01 EXTERNAL:, LPDR NSIC COPIES LTTR ENCL 1

0 1

1 1

0 1

1 1

1 1

1 1

1 1

1 1

1 RECIPIENT ID CODE/NAME PD1-1 PD HAUGHEY,M NRR/DEST/ADS7E4 NRR/DEST/MTB 9H NRR/DOEA/TSB11F OGC 15-B-18 RES/DE/EIB NRC PDR COPIES LTTR ENCL 5

5 1

1 1

1 1

1 1

1 1

0 1

1 1

1 j

A D

S A

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 21 ENCL 18

~ t

V NIAGAR LJ MOHANK NIAGARAMOHAWKPOWER CORPORATION/301 PLAINFIELDROAD, SYRACUSE, N.Y, 13212/TELEPHONE (315) 474-1511 March 7,,1988 NMPlL 0231 U.S. Nuclear Regulatory Commission Attn: 'ocument Control Desk Nashington, D.C. 20555 Re:

Nine Mile Point Unit 1

Docket No. 50-220 DPR-63 Gentlemen:

Niagara Mohawk Power Corporation hereby transmits an application for an amendment to Nine Mile Point Unit 1 Operating License DPR-63.

Also enclosed are the proposed changes to the Technical Specifications set forth in Appendix A to the above mentioned license.

Supporting information and analysis demonstrating that the proposed changes involve no significant hazards consideration pursuant to 10 CFR 50.92 are included as Attachment B.

Pursuant to 10 CFR 170.12, a one hundred and fifty dollar ($ 150.00) application fee is enclosed.

The proposed Technical Specification change contained herein represents revisions to Specifications 3.1.2 and 4.1.2, Li uid Poison S stem, and the associated Bases.

Niagara Mohawk requests approval of the attached proposed changes to the Technical Specifications by April 11, 1988.

Pursuant to 10 CFR 50.91(b)(l),

Niagara Mohawk has provided a copy of this license amendment request and the associated analysis regarding no significant hazards consideration to the appropriate state representative.

Very truly yours, NIAGARA MOHANK POWER CORPORATION C.

V.

Man n

Senior Vice President KBT/pns 4433G Enclosures (Check II196469-Manufacturers cc: Regional Administrator, Region I Mr. R. A. Capra, Director Mr. R. A. Benedict, Project Manager Mr. H. A. Cook, Resident Inspector SS03170254 SS0307 PDR ADOCK 05000220 P

DCD Hanover)

Mr. Jay Dunkleberger Division of Policy Analysis and Planning New York State Energy Office Agency Building 2 tIgO I Empire State Plaza

Albany, NY 12223 r P)o

/~ elk

T I

f K

UNITED STATES NUCLEAR REGULATORY COMMISSION In the Matter of

)

)

NIAGARA MOHAWK POWER CORPORATION

)

)

(Nine Mile Point Nuclear Station Unit No.

1)

Docket No. 50-220 APPLICATION FOR AMENDMENT TO OPERATING LICENSE Pursuant to Section 50.90 of the regulations of the Nuclear Regulatory Commission, Niagara Mohawk Power Corporation, holder of Facility Operating License No.

DPR-63, hereby requests that Sections 3.1.2 and 4.1.2 of the Technical Specifications set forth in Appendix A to that License be amended.

These proposed changes have been reviewed in accordance with Section 6.5 of the Technical Specifications.

The proposed Technical Specification changes are set forth in Attachment A

to this application.

Technical Specifications 3.1.2 and 4.1.2 for the Liquid Poison System have been modified to incorporate changes required by 10 CFR 50.62 for the reduction of risk from ATWS events.

The changes proposed for Technical Specification 3.1.2 are to delete Figure 3.1.2a, identify the Liquid Poison System minimum volume requirements, incorporate the equivalency equation for determining the concentration of sodium pentaborate solution enriched in the boron-10 isotope, and revise Figure 3.1.2b for lower allowable concentrations.

Technical Specification 4.1.2b has been changed to incorporate additional surveillance requirements for monitoring the enriched boron-10 isotope concentration.

The Bases for Technical Specifications 3.1.2 4433G

and 4.1.2 have been revised to incorporate the Equivalency Equation for

't relating boron-10 enrichment and solution concentration.

Reference to the minimum and maximum injection times has been removed since the rate of boron-10 injection is determined by the Equivalency Equation.

The proposed change would not authorize any change in the types of effluents or in the authorized power level of the facility in conjunction with this Application for License Amendment.

Supporting information and analysis which demonstrate that the proposed changes involve no significant hazards consideration pursuant to 10 CFR S0.92 are included as Attachment B.

WHEREFORE, Applicant respectfully requests that Appendix A to Facility Operating License No.

DPR-63 be amended in the form attached hereto as Attachment A.

NIAGARA MOHAWK POWER CORPORATION By C. V.

angan Senior Vice President Subscribed and sworn to before me on this W day of March 1988.

~ETH A MENIKHE(g Notary Public Irr the state ot Ne yo k

" " Onondaga County No. 43gan Ouatlftcd My Cornnrtsstsn ptrcs "rSv8 st 3t,;3 q%

NOTARY PUBLIC 4433G

ATTACHMENT A NIAGARA MOHAWK POWER CORPORATION LICENSE NO DPR-63 DOCKET NO. 50-220 Pro osed Chan es to Technical S ecifications The existing pages 41, 42, 43, 44 and 45 will be replaced with the attached revised pages.

These pages have been retyped in their entirety with marginal markings to indicate changes to the text.

4433G

0