ML17053C298

From kanterella
Jump to navigation Jump to search
Forwards LER 80-033/03L-0
Date released: 06/30/2017 Download: ML17053C298


LER 80-033/03L-0:on 801224,auxiliary Power Feed Experienced Loss to Emergency Power Bus.Caused by Feeder Breaker Trip Due to Setpoint on Over Frequency Protective Relay Being Set Too Close to Nominal Frequency.Relay Recalibr
ML18037A321
Person / Time
Site: Nine Mile Point 
Issue date: 01/23/1981
From: Harrison P
NIAGARA MOHAWK POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML18037A321 (2)
Forwards LER 80-033/03L-0
ML17053C297
Person / Time
Site: Nine Mile Point 
Issue date: 01/23/1981
From: Lempges T
NIAGARA MOHAWK POWER CORP.
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML17053C297 (2)