APPENDIX A NOTICE OF VIOLATION Niagara Mohawk Power Corporation Docket No. 50-220 This refers to the inspection conducted by representatives of the Region I (Philadelphia) office at the Nine Mile Point Nuclear Station, Unit 1,

Scriba, New York, of activities authorized bv NRC License No.

DPR-63.

During this inspection, conducted on April 24-25,

1979, May 1-4, 1979

'nd Ma'y 8-13, 1979, the following apparent item of noncompliance was identified:

The Nine Mile Point Unit 1 Technical Specification 6.8.1 states, in part, that "Written procedures...shall be established, implemented and maintained."

Specification

22A6904, "Preheat and Postweld Heat Treatment for Steam Outlet Safe End Replacement,"

paragraph 4.3.3. states that "Thermocouple temperatures shall be recorded on a multi-channel chart recorder.

In addition, the thermocouple shal'1 be read and recorded on a temperature Tog sheet at intervals not to exceed 1/2 hour."

Contrary to the above, on May 9, 1979, thermocouple readings were recorded at one hour intervals on Temperature Log Sheet No. 2'or May 8-9, 1979.

This item is an infraction.