7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.4.6-6c, West Steam Enclosure Steamiline Break - Backflow (Pressure Response)
ML16344A402
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16344A402 (2)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.6 Table: 14.4.6-6c Page:

1 of 2 WEST STEAM ENCLOSURE STEAMLINE BREAK - BACKFLOW (PRESSURE RESPONSE)

Time (sec)

Mass Flow 103 lb/sec Energy Release 106 Btu/sec 0.0 7.54 8.99 0.1 5.09 6.07 0.2 4.61 5.50 0.3 4.41 5.26 0.4 4.30 5.13 0.5 4.58 5.46 0.6 4.97 5.92 0.7 5.09 6.07 0.8 5.11 6.09 0.9 5.13 6.11 1.0 5.07 6.04 1.5 5.29 6.31 2.0 5.11 6.10 2.5 4.96 5.91 3.0 4.93 5.88 3.5 4.81 5.77 4.0 4.68 5.58 4.5 4.59 5.47 5.0 4.53 5.40 5.5 4.65 5.16 6.0 5.28 5.17 6.5 5.90 5.55 7.0 6.46 5.78 7.5 6.88 5.93 UNIT 2

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision: 16.6 Table: 14.4.6-6c Page:

2 of 2 UNIT 2 WEST STEAM ENCLOSURE STEAMLINE BREAK - BACKFLOW (PRESSURE RESPONSE)

Time (sec)

Mass Flow 103 lb/sec Energy Release 106 Btu/sec 8.0 7.32 6.10 8.5 7.79 6.32 9.0 8.23 6.53 9.5 8.61 6.72 10.0 8.92 6.88