ML16344A369
| ML16344A369 | |
| Person / Time | |
|---|---|
| Site: | Cook |
| Issue date: | 10/24/2016 |
| From: | Indiana Michigan Power Co |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML16336A263 | List:
|
| References | |
| AEP-NRC-2016-42 | |
| Download: ML16344A369 (1) | |
Text
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
22 Table: 14.4.2-3C Page:
1 of 1 SUBMERGED LOWER VOLUME / CONTAINMENT SUMP DOSE RATES & DOSES1 Time Gamma Dose Rate (rad/hr)
Beta Dose Rate (rad/hr)
Total Dose Rate (rad/hr)
Gamma Dose (rad)
Beta Dose (rad)
Total Dose (rad) 1 second 1.201E+06 1.791E+05 1.38E+06 1.668E+02 2.488E+01 1.92E+02 30 minutes 9.675E+05 1.388E+05 1.11E+06 5.377E+05 7.812E+04 6.16E+05 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 8.100E+05 1.177E+05 9.28E+05 9.799E+05 1.418E+05 1.12E+06 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 6.118E+05 9.462E+04 7.06E+05 1.682E+06 2.467E+05 1.93E+06 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> 2.834E+05 5.775E+04 3.41E+05 4.061E+06 6.719E+05 4.73E+06 1 day 1.315E+05 3.291E+04 1.64E+05 7.072E+06 1.364E+06 8.44E+06 7 days 3.467E+04 8.429E+03 4.31E+04 1.511E+07 3.346E+06 1.85E+07 30 days 9.922E+03 3.262E+03 1.32E+04 2.527E+07 6.123E+06 3.14E+07 90 days 3.470E+03 1.753E+03 5.22E+03 3.307E+07 9.351E+06 4.24E+07 180 days 1.733E+03 1.221E+03 2.95E+03 3.838E+07 1.249E+07 5.09E+07 365 days 7.349E+02 7.538E+02 1.49E+03 4.328E+07 1.673E+07 6.00E+07 UNIT 2 1 Per Calculation RS-C-0046