INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 24.0 Table: 14.3.2-4 Page:

1 of 2 UNIT 2 Safety Injection Flows Used in the SBLOCA Analysis - Injection Phase (1 CHG pump, 1 HHSI pump, 1 RHR pump-faulted loop injects to RCS pressure)

(1.5-inch through 6-inch breaks)

RCS Pressure (psia)

Broken Loop (lbm / sec)

Intact Loops (lbm / sec)

Loop 1 Loop 2 Loop 3 Loop 4 14.7 177.8 155.5 157.6 156.5 34.7 169.2 148.1 150.0 149.0 54.7 159.3 139.5 141.2 140.4 74.7 148.1 129.8 131.2 130.6 94.7 135.8 119.1 120.3 119.8 114.7 121.5 106.7 107.7 107.4 134.7 103.3 91.0 91.5 91.5 154.7 77.0 68.1 68.2 68.4 174.7 31.3 28.5 27.6 28.4 194.7 31.1 28.3 27.4 28.2 214.7 30.9 28.1 27.2 28.0 234.7 30.6 27.9 26.9 27.8 254.7 30.4 27.6 26.7 27.6 274.7 30.1 27.4 26.5 27.4 294.7 29.9 27.2 26.3 27.1 314.7 29.7 27.0 26.1 26.9 414.7 28.4 25.8 25.0 25.8 514.7 27.2 24.7 23.9 24.6 614.7 25.8 23.4 22.7 23.4 714.7 24.4 22.1 21.5 22.1 814.7 23.0 20.8 20.2 20.8 914.7 21.4 19.3 18.8 19.3 1014.7 19.5 17.5 17.1 17.5 1114.7 17.4 15.6 15.2 15.5

INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 24.0 Table: 14.3.2-4 Page:

2 of 2 UNIT 2 Safety Injection Flows Used in the SBLOCA Analysis - Injection Phase (1 CBG pump, 1 HHSI pump, 1 RHR pump-faulted loop injects to RCS pressure)

(1.5-inch through 6-inch breaks)

RCS Pressure (psia)

Broken Loop (lbm / sec)

Intact Loops (lbm / sec)

Loop 1 Loop 2 Loop 3 Loop 4 1214.7 14.4 12.9 12.6 12.8 1314.7 10.1 8.8 8.8 8.7 1414.7 9.0 7.9 7.9 7.8 1514.7 8.6 7.5 7.5 7.4 1614.7 8.1 7.1 7.1 7.0 1714 7 7.6 6.6 6.6 6.5 1814.7 7.1 6.2 6.1 6.1 1914.7 5.3 4.6 4.6 4.6 2014.7 4.7 4.1 4.1 4.0 2114.7 3.9 3.5 3.4 3.4 2214.7 3.1 2.7 2.7 2.6 2314.7 0.0 0.0 0.0 0.0 2414.7 0.0 0.0 0.0 0.0