IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

18 Table: 14.1.1-1 Page:

1 of 1 Unit 2 TIME SEQUENCE OF EVENTS Accident Event Time (sec)

Uncontrolled RCCA Withdrawal From A Subcritical Condition Initiation of uncontrolled RCCA withdrawal (63 pcm/sec) 0.0 High Neutron Flux Reactor Trip Setpoint (low setting) reached 12.2 Rods begin to fall into core 12.7 Minimum DNBR occurs 14.8 Peak Clad Average Temperature occurs 15.3 Peak Fuel Average Temperature occurs 15.6 Peak Fuel Centerline Temperature Occurs 16.0