ML16343A770

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.3.9-21, In-Vessel Fuel Rod Debris Deposition
ML16343A770
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A770 (1)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

22 Table: 14.3.9-21 Page:

1 of 1 UNIT 1 IN-VESSEL FUEL ROD DEBRIS DEPOSITION Case Scale Thickness

(µm)

Total Deposition Thickness

(µm)

Total Deposition Thickness (mils)

Max Clad Temperature

(°F)

Unit 1 (min sump volume) 151 443 17 365.71 Unit 1 (max sump volume) 61 353 14 365.71 Unit 2 (min sump volume) 122 414 16 358.10 Unit 2 (max sump volume) 54 346 14 358.09