ML16343A757

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.3.9-11, Loop 4 Alternate RCS Loop Piping Break (Dgbs) Debris Loads at the Main Strainer and Remote Strainer
ML16343A757
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A757 (2)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

22 Table: 14.3.9-11 Page:

1 of 2 UNIT 1 LOOP 4 ALTERNATE RCS LOOP PIPING BREAK (DGBS) DEBRIS LOADS AT THE MAIN STRAINER AND REMOTE STRAINER Debris Type Debris Load at Main Strainer at End of Pool Fill Phase Overall Debris Load at Main Strainer Overall Debris Load at Remote Strainer RMI Small Pieces, ft2 2791.89 4032.73 0

RMI Large Pieces, ft2 517.05 827.28 0

Cal-Sil Fines, lbs 23.2 31.9 34.684 Erosion of Cal-Sil Small Pieces to fines, lbs 0

4.64 3.712 Cal-Sil Small Pieces, lbs 2.32 4.64 0

Marinite I fines, lbs 0

0 0

Erosion of Marinite I Small Pieces to fines, lbs 0

0 0

Marinite I Small Pieces, lbs 0

0 0

Erosion of Marinite I Large Pieces to fines, lbs 0

0 0

Marinite I Large Pieces, lbs 0

0 0

Marinite 36 fines, lbs 0.2528 0.3476 0.4108 Erosion of Marinite 36 Small Pieces to fines, lbs 0

0.03 0.024 Marinite 36 Small Pieces, lbs 0.015 0.03 0

Erosion of Marinite 36 Large Pieces to fines, lbs 0

0.2268 0.0972 Marinite 36 Large Pieces, lbs 0.0648 0.1134 0

Min-K, lbs 0

0 0

Epoxy Paint (inside ZOI), lbs 1.824 2.508 2.964 Alkyd Paint (inside ZOI), lbs 0.608 0.836 0.988

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

22 Table: 14.3.9-11 Page:

2 of 2 UNIT 1 LOOP 4 ALTERNATE RCS LOOP PIPING BREAK (DGBS) DEBRIS LOADS AT THE MAIN STRAINER AND REMOTE STRAINER Debris Type Debris Load at Main Strainer at End of Pool Fill Phase Overall Debris Load at Main Strainer Overall Debris Load at Remote Strainer Unqualified OEM Epoxy (outside ZOI), lbs 0

6.76 12.168 Unqualified OEM Alkyd (outside ZOI), lbs 0

10.416 66.96 Unqualified Non-OEM Epoxy (outside ZOI), lbs 0

16.12 0

Unqualified Non-OEM Alkyd (outside ZOI), lbs 0

1.972 2.006 Unqualified Cold Galvanizing Compound, lbs 0

723.075 272.125 Dirt/Dust, lbs 40.8 88.4 95.2 Latent Fiber, ft3 3

6.5 7

Fire Proof Tape Fines, ft2 8.032 11.044 13.052 Fire Proof Tape Small Pieces, ft2 1.296 1.872 0

Fire Proof Tape Large Pieces, ft2 4.869 7.033 0

Ice Storage Bag Fibers, ft3 0.0117 0.01638 0.01092 Ice Storage Bag Liner Shards, ft3 0.000099 0.0001386 0.0000924 Pieces of Work Platform Rubber, ft3 0.0009 0.00126 0.00084 Electromark Label (inside ZOI), ft2 0.063 0.091 0.329 Electromark Label (outside ZOI), ft2 0

1.188 27.324 Unqualified Labels - Paper, ft2 0

0.2408 0.112 Unqualified Labels - Other, ft2 0

22.0676 10.264 Flex Conduit PVC Jacketing, ft2 0

1.57 0.471