IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

22 Table: 14.3.9-10 Page:

1 of 2 UNIT 1 LOOP 4 RCS CROSSOVER LEG BREAK (DEGB) DEBRIS LOADS AT THE MAIN STRAINER AND REMOTE STRAINER Debris Type Debris Load at Main Strainer at End of Pool Fill Phase Overall Debris Load at Main Strainer Overall Debris Load at Remote Strainer RMI Small Pieces, ft2 5267.52 7608.64 0

RMI Large Pieces, ft2 975.5 1560.8 0

Cal-Sil Fines, lbs 89.568 123.156 133.904 Erosion of Cal-Sil Small Pieces to fines, lbs 0

23.2 18.56 Cal-Sil Small Pieces, lbs 11.6 23.2 0

Marinite I fines, lbs 0.0448 0.0616 0.0728 Erosion of Marinite I Small Pieces to fines, lbs 0

0.005 0.004 Marinite I Small Pieces, lbs 0.0025 0.005 0

Erosion of Marinite I Large Pieces to fines, lbs 0

0.0322 0.0138 Marinite I Large Pieces, lbs 0.0092 0.0161 0

Marinite 36 fines, lbs 0.3456 0.4752 0.5616 Erosion of Marinite 36 Small Pieces to fines, lbs 0

0.036 0.0288 Marinite 36 Small Pieces, lbs 0.018 0.036 0

Erosion of Marinite 36 Large Pieces to fines, lbs 0

0.3024 0.1296 Marinite 36 Large Pieces, lbs 0.0864 0.1512 0

Min-K, lbs 0.512 0.704 0.832 Epoxy Paint (inside ZOI), lbs 69.12 95.04 112.32 Alkyd Paint (inside ZOI), lbs 0.608 0.836 0.988 Unqualified OEM Epoxy (outside ZOI), lbs 0

6.76 12.168

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

22 Table: 14.3.9-10 Page:

2 of 2 UNIT 1 LOOP 4 RCS CROSSOVER LEG BREAK (DEGB) DEBRIS LOADS AT THE MAIN STRAINER AND REMOTE STRAINER Debris Type Debris Load at Main Strainer at End of Pool Fill Phase Overall Debris Load at Main Strainer Overall Debris Load at Remote Strainer Unqualified OEM Alkyd (outside ZOI), lbs 0

10.416 66.96 Unqualified Non-OEM Epoxy (outside ZOI), lbs 0

16.12 0

Unqualified Non-OEM Alkyd (outside ZOI), lbs 0

1.972 2.006 Unqualified Cold Galvanizing Compound, lbs 0

723.075 272.125 Dirt/Dust, lbs 40.8 88.4 95.2 Latent Fiber, ft3 3.00 6.5 7

Fire Proof Tape Fines, ft2 8.032 11.044 13.052 Fire Proof Tape Small Pieces, ft2 1.296 1.872 0

Fire Proof Tape Large Pieces, ft2 4.869 7.033 0

Ice Storage Bag Fibers, ft3 0.0117 0.01638 0.01092 Ice Storage Bag Liner Shards, ft3 0.000099 0.0001386 0.0000924 Pieces of Work Platform Rubber, ft3 0.0009 0.00126 0.00084 Electromark Label (inside ZOI), ft2 0.063 0.091 0.329 Electromark Label (outside ZOI), ft2 0

1.188 27.324 Unqualified Labels - Paper, ft2 0

0.2408 0.112 Unqualified Labels - Other, ft2 0

22.0676 10.264 Flex Conduit PVC Jacketing, ft2 0

1.57 0.471