IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
17.1 Table: 14.3.4-34 Page:
1 of 1 Unit 1 PEAK DIFFERENTIAL PRESSURE (PSI)
FEEDWATER LINE BREAK AT SIDE (BOUNDING)1 Limiting Containment Conditions Across Structures:
DP55-25=5.3159 PSI
.220 SEC TLow/PLow/ICELow DP56-25=5.3788 PSI
.217 SEC TLow/PLow/ICELow DP57-25=5.3801 PSI
.219 SEC TLow/PLow/ICELow DP58-25=5.8566 PSI
.222 SEC TLow/PLow/ICELow DP59-25=6.0058 PSI
.161 SEC TLow/PLow/ICEHigh DP60-25=5.6043 PSI
.214 SEC TLow/PLow/ICELow DP61-25=5.5785 PSI
.212 SEC TLow/PLow/ICELow DP62-25=6.8782 PSI
.022 SEC TLow/PLow/ICEHigh DP63-25=16.2857 PSI
.012 SEC TLow/PLow/ICEHigh DP55-46=3.2606 PSI
.045 SEC TLow/PLow/ICEHigh DP56-47=3.3787 PSI
.030 SEC TLow/PLow/ICELow Node 54 Break DP57-48=2.9672 PSI
.039 SEC TLow/PLow/ICEHigh DP60-51=5.2378 PSI
.021 SEC TLow/PLow/ICELow Node 54 Break DP61-52=5.0053 PSI
.027 SEC TLow/PLow/ICEHigh Across Steam Generator Vessel:
DP56-58=-1.4657 PSI
.023 SEC THigh/PLow/ICEHigh DP57-59=-3.9920 PSI
.015 SEC TLow/PLow/ICEHigh DP60-62=-2.2928 PSI
.027 SEC TLow/PLow/ICEHigh DP61-63=-15.5871 PSI
.011 SEC TLow/PLow/ICEHigh 1 All breaks are in Node 63 unless otherwise noted.