Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17.1 Table: 14.3.4-26 Page:

1 of 3 Unit 1 TABLE 14.3.4-26 STEAM GENERATOR ENCLOSURE MODEL - TMD FLOW PATH INPUT STEAM LINE BREAK Flow Path K

f LI (ft)

DH (ft)

AT (ft2)

Leq (ft)

AT /A 46H-47 0.94 0.022 9.451 4.794 55.9 4.514 0.573 46R-48 0.673 0.022 6.590 3.538 25.4 1.948 0.290 46A-55 0.902 0.022 8.958 4.771 48.9 2.876 0.308 47H-51 0.938 0.022 9.891 4.297 50.1 5.102 0.691 47R-48 0.385 0.022 10.599 4.984 40.7 8.747 0.295 47A-56 0.765 0.022 7.776 4.976 25.5 3.065 0.352 48H-52 0.723 0.022 8.652 3.524 25.3 3.779 0.609 48R-49 0.296 0.022 13.767 5.057 41.3 12.841 0.947 48A-57 0.765 0.022 3.524 4.976 25.5 2.61 0.614 49H-53 0.757 0.022 9.229 3.744 26.712 4.375 0.662 49R-50 0.012 0.022 11.303 5.609 45.808 10.437 0.326 49A-46 0.662 0.022 7.522 3.967 28.302 2.93 0.326 50H-54 0.795 0.022 9.366 5.318 44.852 4.648 0.628 50R-47 0.677 0.022 7.590 5.079 41.48 5.008 0.295 50A-46 0.982 0.022 8.957 6.599 55.652 4.241 0.471 51H-2 1.339 0.022 8.248 4.107 46.4 3.522 0.564 51R-52 0.866 0.022 10.780 6.412 48.18 8.594 0.427

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17.1 Table: 14.3.4-26 Page:

2 of 3 Unit 1 TABLE 14.3.4-26 STEAM GENERATOR ENCLOSURE MODEL - TMD FLOW PATH INPUT STEAM LINE BREAK Flow Path K

f LI (ft)

DH (ft)

AT (ft2)

Leq (ft)

AT /A 52H-2 0.722 0.022 10.937 7.201 49.1 8.128 0.962 52R-53 0.244 0.022 13.263 6.553 49.24 12.392 0.949 53H-1 2.100 0.022 9.453 6.272 48.212 7.392 0.963 53R-54 0.090 0.022 10.939 6.736 50.614 9.147 0.415 54H-1 0.988 0.022 6.483 3.730 39.852 3.164 0.526 54R-51 0.442 0.022 8.412 6.539 49.135 5.253 0.402 55H-56 0.703 0.022 7.977 3.765 43.90 2.775 0.470 55R-57 0.673 0.022 6.590 3.538 25.4 1.961 0.290 55A-58 0.649 0.022 7.456 3.91 27.9 2.863 0.322 56H-60 0.518 0.022 7.572 2.856 33.3 2.898 0.501 56R-57 0.373 0.022 10.568 4.972 40.6 8.713 0.291 57H-61 0.723 0.022 8.617 3.506 25.17 3.750 0.608 57R-58 0.296 0.022 13.767 5.057 41.3 12.841 0.947 58H-62 0.626 0.022 8.410 3.322 23.7 3.652 0.591 58R-59 0.015 0.022 11.778 5.609 45.644 10.611 0.429 59H-63 0.744 0.022 9.215 4.730 36.217 4.548 0.632 59R-56 0.703 0.022 7.253 3.88 31.69 4.938 0.227 59A-55 0.943 0.022 7.807 5.236 40.097 3.002 0.380

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17.1 Table: 14.3.4-26 Page:

3 of 3 Unit 1 TABLE 14.3.4-26 STEAM GENERATOR ENCLOSURE MODEL - TMD FLOW PATH INPUT STEAM LINE BREAK Flow Path K

f LI (ft)

DH (ft)

AT (ft2)

Leq (ft)

AT /A 60H-2 1.111 0.022 7.718 3.567 40.3 3.304 0.529 60R-61 0.599 0.022 10.819 6.468 48.6 8.937 0.402 61H-2 0.857 0.022 9.837 6.292 42.9 6.169 0.839 61R-62 0.287 0.022 13.247 6.373 47.89 12.349 0.947 62H-3 2.121 0.022 9.457 6.245 48.00 8.091 1.0 62R-63 0.230 0.022 11.335 7.026 52.793 10.153 0.432 63H-3 0.820 0.022 5.494 2.564 26.517 2.727 0.412 63R-60 0.684 0.022 7.090 4.434 33.317 4.767 0.273