ML16343A629
| ML16343A629 | |
| Person / Time | |
|---|---|
| Site: | Cook |
| Issue date: | 10/24/2016 |
| From: | Indiana Michigan Power Co |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML16336A263 | List:
|
| References | |
| AEP-NRC-2016-42 | |
| Download: ML16343A629 (2) | |
Text
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
17.1 Table: 14.3.4-20 Page:
1 of 2 Unit 1 TABLE 14.3.4-20 SINGLE-ENDED HOT LEG BREAK MASS AND ENERGY RELEASES Time (sec)
Mass (lb/sec)
Energy (BTU/sec)
.00000 0.000000+4 0.000000+7
.00100 2.986053E+04 1.811825E+07
.00301 4.343918E+04 2.634650E+07
.00501 4.292521E+04 2.602551E+07
.01001 4.446135E+04 2.695169E+07
.01400 5.141999E+04 3.123442E+07
.01700 4.673055E+04 2.831411E+07
.02200 4.933676E+04 2.992951E+07
.02700 6.370431E+04 3.867952E+07
.03301 7.988087E+04 4.855038E+07
.03901 7.280847E+04 4.417453E+07
.05001 7.321976E+04 4.444181E+07
.06002 6.824339E+04 4.137223E+07
.06503 6.529671E+04 3.957400E+07
.07204 6.781116E+04 4.112542E+07
.08003 6.387430E+04 3.870615E+07
.08701 6.107294E+04 3.699999E+07
.09200 6.153000E+04 3.728505E+07
.10101 5.928957E+04 3.591744E+07
.11003 5.571592E+04 3.374574E+07
.12001 5.454139E+04 3.303515E+07
.13202 5.230680E+04 3.168585E+07
.14102 5.268915E+04 3.193353E+07
.14802 5.253517E+04 3.184939E+07
.16105 5.355463E+04 3.248006E+07
.17003 5.336413E+04 3.235884E+07
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
17.1 Table: 14.3.4-20 Page:
2 of 2 Unit 1 TABLE 14.3.4-20 SINGLE-ENDED HOT LEG BREAK MASS AND ENERGY RELEASES Time (sec)
Mass (lb/sec)
Energy (BTU/sec)
.18500 5.353877E+04 3.246602E+07
.20003 5.186517E+04 3.149525E+07
.22500 4.640067E+04 2.829631E+07
.25002 4.433356E+04 2.709931E+07
.30003 4.316692E+04 2.649927E+07
.32811 4.406912E+04 2.715201E+07
.35016 4.359122E+04 2.691206E+07
.40004 4.291035E+04 2.645033E+07
.42302 4.323305E+04 2.665236E+07
.45011 4.282392E+04 2.641563E+07
.52004 4.230519E+04 2.601617E+07
.60016 4.197678E+04 2.568951E+07
.70035 4.194488E+04 2.555825E+07
.80004 4.204749E+04 2.547428E+07
.88531 4.220963E+04 2.546782E+07 1.00012 4.190713E+04 2.535124E+07 1.50000 3.994366E+04 2.439612E+07 2.00023 3.835372E+04 2.358048E+07 2.50028 3.711276E+04 2.282196E+07 3.00016 3.583929E+04 2.204359E+07 5.00000 3.583929E+04 2.204359E+07