IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
17.1 Table: 14.3.4-19 Page:
1 of 2 Unit 1 TABLE 14.3.4-19 SINGLE-ENDED COLD LEG BREAK MASS AND ENERGY RELEASES Time (sec)
Mass (lb/sec)
Energy (BTU/sec)
.00000 0.000000+4 0.000000+7
.00200 2.4652E+04 1.2752E+07
.00900 3.4491E+04 1.7946E+07
.01400 5.0203E+04 2.6009E+07
.02100 6.0914E+04 3.1606E+07
.03203 7.2136E+04 3.7456E+07
.04304 8.3502E+04 4.3434E+07
.05101 8.5426E+04 4.4414E+07
.06503 8.4836E+04 4.4078E+07
.08305 8.0678E+04 4.1866E+07
.09607 7.5506E+04 3.9152E+07
.11001 7.4227E+04 3.8487E+07
.13403 7.5861E+04 3.9362E+07
.14601 7.6620E+04 3.9755E+07
.16010 7.6233E+04 3.9551E+07
.18303 7.5634E+04 3.9236E+07
.19804 7.4886E+04 3.8846E+07
.21101 7.3690E+04 3.8219E+07
.23006 7.4895E+04 3.8860E+07
.24610 7.5605E+04 3.9233E+07
.25607 7.5224E+04 3.9028E+07
.26309 7.4595E+04 3.8696E+07
.28206 7.3024E+04 3.7873E+07
.30006 7.3101E+04 3.7920E+07
.31610 7.4255E+04 3.8528E+07
.33509 7.4163E+04 3.8475E+07
.35108 7.4723E+04 3.8773E+07
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
17.1 Table: 14.3.4-19 Page:
2 of 2 Unit 1 TABLE 14.3.4-19 SINGLE-ENDED COLD LEG BREAK MASS AND ENERGY RELEASES Time (sec)
Mass (lb/sec)
Energy (BTU/sec)
.37109 7.3988E+04 3.8382E+07
.41506 7.5856E+04 3.9368E+07
.44107 7.5568E+04 3.9214E+07
.46702 7.4918E+04 3.8871E+07
.49303 7.4959E+04 3.8896E+07
.53003 7.4459E+04 3.8635E+07
.64516 7.3810E+04 3.8313E+07
.69503 7.3409E+04 3.8118E+07
.73001 7.3524E+04 3.8194E+07
.77006 7.3550E+04 3.8224E+07
.83001 7.1814E+04 3.7342E+07
.87509 7.2210E+04 3.7577E+07
.92001 7.1425E+04 3.7191E+07
.96002 7.1669E+04 3.7344E+07 1.0400 7.0980E+04 3.7031E+07 1.1701 7.0215E+04 3.6723E+07 1.3202 6.9872E+04 3.6671E+07 1.4001 6.9903E+04 3.6760E+07 1.7002 6.5502E+04 3.4750E+07 2.0000 6.2185E+04 3.3253E+07 2.5001 5.5091E+04 2.9852E+07 3.0002 4.8491E+04 2.6562E+07 5.0000 4.8491E+04 2.6562E+07