IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

18.1 Table: 14.3.4-9 Page:

1 of 1 UNIT 1 1.4 ft2 DOUBLE-ENDED STEAMLINE BREAKS Operating Power, %1 102 70 Aux. Feed Failure w/o w/o MSIV Failure w

w Tmax °F 323.3 323.0 Time of Tmax sec 8.01 11.96 4.6 ft2 DOUBLE-ENDED STEAMLINE BREAKS Operating Power, %(1) 102 70 Aux. Feed Failure w/o w/o MSIV Failure w

w Tmax °F 322.7 321.7 Time of Tmax sec 6.2 6.2 1 Based upon a core power of 3588 MWt.