ML16343A429

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.3-1-5, D.C. Cook Unit 1 Best-Estimate Large Break LOCA Results
ML16343A429
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A429 (1)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

23 Table: 14.3.1-5 Page:

1 of 1 D. C. COOK UNIT 1 BEST-ESTIMATE LARGE BREAK LOCA RESULTS Parameter ASTRUM Result for Original HHSI and RHR Injection Flow Value ASTRUM Result for Adjusted HHSI and RHR Injection Flow Value 10 CFR 50.46 Acceptance Criteria 95th Percentile PCT at the 95-Percent Confidence Level (°F) 2106 2128 2200 95th Percentile LMO at the 95-Percent Confidence Level (%)

10.0 11.1 17 95th Percentile CWO at the 95-Percent Confidence Level (%)

0.35 0.40 1