IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

16.1 Table:

14.G-3 Page:

1 of 1 HISTORICAL

SUMMARY

OF MAXIMUM STRESS INTENSITIES (PSI)

(1-MILLISECOND PIPE BREAK AND SEISMICS)

Hot Leg Break Cold Leg Break Maximum Total Seismic Component Maximum Membrane Maximum Total Maximum Membrane Maximum Total Vertical Horizontal Maximum Total Blowdown Plus Seismic Barrel (Girth weld) 21,440 31,340 38,900 46,200 133 533 46,733 Barrel-Flange (weld) 19,820 29,720 18,430 47,700 545 800 49,045 Fuel Assembly Top Nozzle Plate 28,700 0

8,000 0

0 28,700 Fuel Assembly Bottom Nozzle Plate 38,700 40,800 533 41,333 Fuel Assembly Thimbles 6,600 6,600 2,300 2,300 6,600 Allowable Stress, Sm:

Sm at 588°F = 16,600 psi Maximum Membrane Stress = Pm = 2.4 Sm = 39,800 psi Maximum Total Stress = Pm + Pb = 49,800 psi Per Winter 1969 Addenda ASME Section III Code