ML16343A141

From kanterella
Jump to navigation Jump to search
7 to Updated Final Safety Analysis Report, Chapter 14, Table 14.3.2-1, Plant Input Parameters for Small Break Loss-of-Coolant Accident
ML16343A141
Person / Time
Site: Cook  
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A141 (2)


Text

INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 25.0 Table: 14.3.2-1 Sheet:

1 of 2 Unit 1 Last Revised: Revision 25.0 Plant Input Parameters for Small Break Loss-of-Coolant Accident Core Rated Thermal Power-100% (MWt) 3304 Peak Linear Power, kW/ft 15.171 Fuel Type 15x15 Upgrade Fuel Total Core Peaking Factor, FQ 2.32 Hot Channel Enthalpy Rise Factor, FH 1.55 Hot Assembly Average Power Factor, PHA 1.38 Thermal Design Flow, gpm/loop 83,200 Nominal Vessel Average Temperature, °F 577.4(1)

Nominal Pressurizer Pressure, psia 2250(2)

Pressurizer Pressure Uncertainty (psia)

+/-67 Minimum Auxiliary Feedwater Flow Rate, lbm/s per SG 14.68 Steam Generator Tube Plugging (Maximum), %

10 Initial Accumulator Water Volume, ft3 946 Accumulator Tank Volume, ft3/tank 1350 Accumulator Water Temperature, °F 130 Minimum Accumulator Cover Gas Pressure (minus uncertainties), psia 600 Refueling Water Storage Tank Temperature, °F 105 Nominal Steam Pressure, psia 848.32

INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 25.0 Table: 14.3.2-1 Sheet:

2 of 2 Unit 1 Last Revised: Revision 25.0 Plant Input Parameters for Small Break Loss-of-Coolant Accident SI Flow Delay Time, seconds 54 HHSI Cross-Tie Valve Position Open (Injection & Cold Leg Recirculation)(3)

RHR Cross-Tie Valve Position Open (Injection)

Closed (Cold Leg Recirculation)

(1) Analysis supports operation over the range of nominal full-power Tavg values of 553.7°F - 575.4°F.

(2) Analysis supports operation at nominal initial pressurizer pressure (without uncertainties) of 2100 psia and 2250 psia.

(3) Conservatively modeled HHSI cross-tie valves closed in injection phase.