INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 25.0 Table:
11.5-2 Page:
1 of 2 Last Revised: Revision 25.0 BLOWDOWN TREATMENT SYSTEM COMPONENTS PUMP Number 1 per unit Fluid Steam generator blowdown Pressure, Suction Atmospheric Temperature 200°F Head 125 ft.
Flow 60 gpm Type Horizontal centrifugal Material, Casing Stainless Steel Impeller Stainless Steel NPSH, minimum Ft. H2O 2.5 HEAT EXCHANGER1 Number 1 per unit Shell Side (blowdown liquid)
Inlet Temperature 200°F Outlet Temperature 120°F Max. pressure 70 psi Operating pressure 50 psi Flow 60 gpm Material 304 Stainless Steel Pressure drop, normal 4 psi maximum allowable 15 psi 1 The current plant design basis has been changed to reflect a new NESW pump discharge temperature of 88.9°F.
INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 25.0 Table:
11.5-2 Page:
2 of 2 Last Revised: Revision 25.0 BLOWDOWN TREATMENT SYSTEM COMPONENTS Tube Side (non-essential service water)
Inlet Temperature 76°F Outlet Temperature 106°F Max. pressure 150 psig Operating pressure 75 psig Flow 160 gpm Material 304 Stainless Steel Pressure drop, normal 5 psi maximum allowable 9 psi MIXED BED DEMINERALIZERS Number 3 per unit Type Flushable Vessel, design pressure, psig 200 Operating pressure, psig 50 Vessel, design temperature, °F 250 Operating temperature, °F 120 Resin volume, ft3 56 (Nos. 1 & 2) 20 (No. 3)
Design flow rate, gpm 50 Resin type Cation and anion Material of construction Austenitic stainless steel