Notice of Violation from Insp on 980802-0912.Violation Noted:Procedure for Fire Protection Program Was Not Adequately Maintained
ML16342A530
Person / Time
Site: Diablo Canyon  
Issue date: 10/06/1998
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML16342A529 List:
References
50-275-98-14, 50-323-98-14, NUDOCS 9810140078
Download: ML16342A530 (4)


Text

ENCLOSURE 1 NOTICE OF VIOLATION Pacific Gas and Electric Company Diablo Canyon Nuclear Power Plant Docket Nos.:

50-275 50-323 License Nos.: DPR-80 DPR-82 During an NRC inspection conducted on August 2 through September 12, 1998, one violation of NRC requirements was identified. In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG-1600, the violation is listed below:

Technical Specification 6.8.1.h requires, in part, that the licensee implement and maintain procedures for the Fire Protection Program.

Procedure OM8.ID2 "Fire System Impairment," Revision 6, partially implements this requirement.

Contrary to the above, as of September 12, 1998, a procedure for the Fire Protection Program was not adequately maintained.

Specifically, Procedure OM8.ID2, Section 3;12.2, contained an inappropriate definition of a continuous fire watch that was implemented at Diablo Canyon.

The definition stated that a continuous fire watch is "a fire watch that monitors the immediate area of a non-functional fire rated assembly at least once per 15 minutes," without any further restrictions for its use.

This is a Severity Level IVviolation (Supplement I) (50-275;323/981 4-02).

The NRC has concluded that information regarding the reason for the violation; the corrective actions taken and planned to correct the violation and prevent recurrence; and the date when full compliance was achieved is already adequately addressed on the docket in the enclosed report. However, you are required to submit a written staten o.~t or explanation pursuant to 10 CFR 2.201 if the description therein does not accurately reflect your corrective actions or your position.

In that case, or if you choose to respond, clearly mark you response as a "Reply to a Notice of Violation," and sent it to the U.S. Nuclear Regulatory Commission, ATTN:

~ Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region IV, 611 Ryan Plaza Drive, Suite 400, Arlington, Texas 76011, and a copy to the NRC Resident Inspector at the facilitythat is the subject of this Notice, within 30 days of the date of the letter '.ransmitting this Notice of Violation (Notice).

If you contest this enforcement action, you should also provide a copy of your response to the Director, Office of Enforcement, United States Nuclear Regulatory Commission, Washington, DC 20555-0001.

Because your response willbe placed in the NRC Public Document Room (PDR), to the extent possible, it should not include any personal privacy, proprietary, or safeguards information so that it can be placed in the PDR without redaction.

If personal privacy or proprietary information is necessary to provide an acceptable response, then please provide a bracketed copy of your response that identifies the information that should be protected and a redacted copy of your 98iOi40078 98i006 PDR ADQCK 05000275 8

PDR

response that deletes such information. If you request withholding of such material, you must specifically identify the portions of your response that you "seek to have withheld and provide in detail the bases for your claim of withholding (e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR 2.790(b) to support a request for withholding confidential commercial or financial information). If safeguards informatio'n is necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21.

Dated at Arlington, Texas this 6th'day of October 1998