IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

9.4-2 Page:

1 of 4 SPENT FUEL POOL COOLING SYSTEM COMPONENT DESIGN DATA System cooling capacity, Btu/hr 29.8x106 Spent fuel pool heat exchanger Number 2 (Shared)

Design heat transfer, Btu/hr 14.9x106 Shell Tube Design pressure, psig 150 150 Design temperature, °F 200 200 Design flow rate, lb/hr 1.49x106 1.14x106 Design inlet temperature, °F 95 120 Design outlet temperature, °F 105 106.9 Fluid Component Cooling Water1 Spent fuel pool (borated demineralized water)

Spent fuel pool pump Number 2 (shared)

Design pressure, psig 150 Design temperature, °F 200 Design flow rate, gpm 2300 Minimum developed head, ft.

125 Temperature of pumped fluid, °F, 80 - 180 Fluid Spent fuel pool water(borated demin. water)

NPSH, ft. (available/required) 30/10 Material Austenitic Stainless Steel 1 The plant has been evaluated for a CCW Hx outlet temperature range of 60°F to 105°F. It is acceptable for the CCW temperature to rise to 120°F during cooldown and post-LOCA conditions. See Section 9.4.2.

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

9.4-2 Page:

2 of 4 SPENT FUEL POOL COOLING SYSTEM COMPONENT DESIGN DATA Spent fuel pool skimmer pump Number 1 (Shared Design pressure, psig 50 Design temperature, °F 200 Design flow rate, gpm 100 Minimum developed head, ft.

50 Temperature of pumped fluid, °F 75 - 150 Fluid Spent fuel pool water NPSH, ft. (available/required) 30/2 Material Austenitic Stainless Steel Refueling water purification pump Number 1

Design pressure, psig 600 Design temperature, °F 200 Design flow rate, gpm Nom. 100, Max 150 Minimum developed head, ft.

130 Fluid Refueling water NPSH, Ft. (available/required)

@ 100gpm 30/5,

@ 150 gpm 43/7 Material Austenitic stainless steel Spent fuel pool demineralizer Number 1 (Shared)

Type Flushable Vessel design pressure, psig Internal -

200 External -

15 Vessel design temperature, °F 250 Design flow rate, gpm Maximum 150 Normal flow, gpm 100, Max 150 Normal operating temperature, °F 120 Normal operating pressure, psig Approx. 50 Resin type anion and cation

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

9.4-2 Page:

3 of 4 SPENT FUEL POOL COOLING SYSTEM COMPONENT DESIGN DATA Spent fuel pool filter Number 1 (Shared)

Type Replaceable (Cellulose and/or glass resin)

Internal design pressure, psig 200 Design temperature, °F 250 Design flow rate, gpm Nom. 100, Max. 150 Filtration requirement 98% retention of particles above 5 micron Spent fuel pool skimmer filter Number 1 (Shared)

Type Replaceable (Cellulose and/or glass resin)

Internal design pressure, psig 200 Design Temperature, oF 250 Design flow rate, gpm 150 Filtration requirement 98% retention of particles above 5 micron Refueling water purification filter Number 1 (Shared)

Type Replaceable (Cellulose and/or glass resin)

Internal design pressure, psig 200 Design temperature, °F 250 Design flow rate, gpm Nom. 100, Max. 150 Particle size retained, minimum, micron 5

Spent fuel pool strainer 2 (Shared)

Design flow rate, gpm 2300 Fluid Borated demineralized water

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

9.4-2 Page:

4 of 4 SPENT FUEL POOL COOLING SYSTEM COMPONENT DESIGN DATA Spent fuel pool skimmer strainer Number 1 (Shared)

Type Basket Design flow rate, gpm 100 Design pressure, psig 50 Design temperature, °F 200 Spent fuel pool skimmers Number 2 (Shared)

Design flow rate per unit, gpm 50