INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 24.0 Table:

7.5-2 Page:

1 of 2 ENGINEERED SAFETY FEATURES EQUIPMENT EXPOSED TO HARSH ENVIRONMENT Equipment Quantity Inside Containment Outside Containment Operating Mode LOCA or MSLB Design Operating Duration Miscellaneous Containment Air Recirculation/

Hydrogen Skimmer Fan 2

X Approximately 2 minutes after 2/3 hi containment pressure.

1 Year Safeguards Equipment Power, Control and Instrument Cable X

X As required by equipment serviced As required by equipment serviced Valves Containment Isolation 34 14 20 2 open, 8 remain as is, 2 switch & 22 close Various ECCS Process 40 8

32 14 remain as is, 6 close & 20 switch Various Other ESF Process 38 8

30 16 open, 9 remain as is, 4 close & 9 switch Various

INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 24.0 Table:

7.5-2 Page:

2 of 2 ENGINEERED SAFETY FEATURES EQUIPMENT EXPOSED TO HARSH ENVIRONMENT Equipment Quantity Inside Containment Outside Containment Initiate LOCA or MSLB Monitor Design Operating Duration Instrumentation Auxillary Feedwater Flow 4

X X

4 Months Containment Pressure 4

X X

X X

4 Months Main Feedwater Flow 2/Stm. Gen.

X X

1 Minute Main Steam Flow 2/Stm. Gen.

X X

1 Minute Main Steam Pressure 3/Stm. Gen.

X X

X 4 Months Pressurizer Level 3

X X

4 Months Pressurizer Pressure 3

1 X

X X

X X

X X

4 Months 1 Minute Wide Range Reactor Coolant Pressure 2

X X

4 Months Narrow Range Reactor Coolant Temperature 2/Loop X

X X

1 Minute Wide Range Reactor Coolant Temperature 2/Loop X

X 4 Months Steam Generator Narrow Range Level 3/Stm. Gen.

X X

X 4 Months Containment Water Level 8

X X

4 Months Includes a redundant pair of overlapping level monitors and a redundant pair of level switches.