ML16341B090
Text
IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:
21.1 Table:
6.2-5 Page:
1 of 1 DESIGN PARAMETERS -ECCS PUMPS Centrifugal Charging Pumps Safety Injection Pumps Residual Heat Removal Pumps Number per unit 2
2 2
Design pressure, psig 2800 1700 600 Design temperature, oF 300 300 400 Design flow rate, gpm 150 400 3000 Design head, ft.
5800 2500 350 Max. flow rate, gpm 550 7001 4500 Head at max. flow rate, ft.
1400 1500 300 Motor horsepower 600 400 400 Pump Speed, rpm 48102 3570 1780 Type Horizontal Multistage Centrifugal Horizontal Multistage Centrifugal Vertical, in-line Single stage Centrifugal Material Stainless Steel or Stainless Steel clad Carbon steel Stainless Steel Stainless Steel The motor starting times from electrical activation to full speed (steady-state-voltage) as obtained by a computer simulation are as follows:
Centrifugal Charging Pump 1.14 seconds Safety Injection Pump 1.13 seconds Residual Heat Removal Pump 0.704 seconds 1 Maximum flow rate is limited to 675 gpm for pumps that have not been qualified to a higher flow rate, up to a maximum of 700 gpm.
2 Equipped with speed increaser gear.