7 to Updated Final Safety Analysis Report, Chapter 6, Table 6.2-1 - Safety Injection System Code Requirements. Page 1 of 1
ML16341B086
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16341B086 (1)


Text

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

22 Table:

6.2-1 Page:

1 of 1 SAFETY INJECTION SYSTEM CODE REQUIREMENTS1 Component Code Refueling Water Storage Tank Not applicable Residual Heat Exchanger Tube Side ASME B&PV Code Section III Class C Shell Side ASME B&PV Code Section VIII Accumulators ASME B&PV Code Section III Class C Valves ANSI B16.5, MSS-SP-66, and ASME B&PV Code Section III, 1968 Edition 1 Piping USAS B31.1, 1967 Edition 1 ASME III Appendix F 2 Boron Injection Tank ASME B&PV Code Section III Class C Recirculation Sump Strainers (Main and Remote)

AISC-69, 7th Edition Debris Interceptors (CEQ Fan Room, Flood-Up Overflow Wall, and Entrance to Containment Wide Range Sump Level Instrument)

AISC-69, 7th Edition 1 Repairs and replacements for pressure retaining components within the code boundary, and their supports, are conducted in accordance with ASME Section XI.

2 The evaluation criteria of ASME III Appendix F (faulted conditions) is applicable to accumulator fill line piping from outside containment isolation valve to the normally closed inlet valves at each accumulator and the normally closed valves in the flow path to the low head SI hot leg loops (CPN 32).