INDIANA AND MICHIGAN POWER D. C. COOK NUCLEAR PLANT UPDATED FINAL SAFETY ANALYSIS REPORT Revision: 24.0 Table:

5.2-4 Page:

1 of 1 TABLE OF DAMPING VALUES Percent of Critical Damping Type of Structure Operating Basis Earthquake Design Basis Earthquake Containment Structure and all internal concrete structures 4%, 2%

7%, 5%

Other conventionally reinforced concrete structures above grade, such as shear walls or rigid frames 2%

5%

Welded structural steel assemblies 1%

1%

Bolted or riveted steel assemblies 2%

2%

Piping 0.5%

0.5%

Analyzed with accident conditions Analyzed without accident conditions Note 1: AEC Reg. Guide 1.61 (Oct. 1973) permits the use of higher damping values than those values indicated in this Table.

Note 2: In support of the Dry Cask Storage Project, damping values based on Regulatory Guide 1.61 Rev. 1 were used for the design analysis that increased the Maximum Critical Load (MCL) rating of the east auxiliary building crane.