IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

16.1 Table:

5.2-2 Page:

1 of 3 SITE SOIL RESISTIVITY MEASUREMENTS DATA TAKEN APRIL 10 AND 11, 1969 Location Direction Elevation (Feet)

Pin Spacing (Feet)

Reading (Ohms)

Multiplier Average Ohm-Cm Unit No. 1 Reactor North-South 584 50 2.2 191.5 21,000 40 5.8 191.5 44,400 30 9.9 191.5 56,900 20 18.0 69,000 10 100.0 191,500 Unit No. 2 Reactor North-South 584 50 1.4 191.5 13,400 40 2.0 191.5 15,300 30 8.0 191.5 46,000 20 25.0 191.5 95,900 10 130.0 191.5 249,000 Between No. 1 and 2 Reactors East-West 584 50 70.0 191.5 727,000 40 19.0 191.5 145,600 Average Ohm-Cm = Reading Pin Spacing x Multiplier Actually Ohms per cubic centimeter

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

16.1 Table:

5.2-2 Page:

2 of 3 SITE SOIL RESISTIVITY MEASUREMENTS DATA TAKEN APRIL 10 AND 11, 1969 Location Direction Elevation (Feet)

Pin Spacing (Feet)

Reading (Ohms)

Multiplier Average Ohm-Cm 30 22.0 191.5 126,500 20 26.0 191.5 99,700 10 91.0 191.5 174,200 Unit No. 2 Turbine North-South 589 50 4.3 191.5 41,100 40 7.8 191.5 59,800 30 22.0 191.5 126,500 20 46.0 191.5 176,300 10 110.0 191.5 210,800 Unit No. 1 Turbine North-South 589 50 No. Reading 191.5 40 4.9 191.5 36,800 30 18.0 191.5 103,500 20 40.0 191.5 153,300 10 112.0 191.5 214,300

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

16.1 Table:

5.2-2 Page:

3 of 3 SITE SOIL RESISTIVITY MEASUREMENTS DATA TAKEN APRIL 10 AND 11, 1969 Location Direction Elevation (Feet)

Pin Spacing (Feet)

Reading (Ohms)

Multiplier Average Ohm-Cm Unit No. 1 Turbine East-West 589 50 8.0 191.5 76,500 30 21.0 191.5 120,800 10 104.0 191.5 199,300 On Beach Near Water (Sand)

North-South 580 50 7.05 191.5 67,500 40 5.40 191.5 41,400 30 8.50 191.5 48,900 20 13.0 191.5 49,800 10 18.0 191.5 34,500