Docket t<o.:

50-275 Dr. llilliam E. Cooper Teledyne Engineering Services 130 Second Avenue i(a 1 tham, Ilassachusetts 02254

Dear Dr. Cooper:

The staff and our consultant, Brookhaven National Laboratories (BNL),

have completed the review of Interim Technical Reports (ITRs) 13, 16, 39 and 40 (Reference 1 through 4).

These reports were prepared by R. L.

Cloud Associates (RLCA) as part of the Diablo Canyon Unit 1 Independent Design Verification Program (IDVP).

In addition, the staff and Btli assisted in a Region V inspection of background information referenced in the reports on June 8, 9 and 10, 1983 at the offices of RLCA.

Based on our review, we have concluded that ITRs 13, 39 and 40 do not adequately address a number of geotechnical issues related to the intake structure and therefore do not provide an acceptable basis for the conclusions contained therein.

Our principal concerns are:

(1)

ITR 13 does not define the material properties of the backfill and therefore the adequacy of the analysis and design cannot be assessed.

(2)

The methodology and the assumptions for determination of soil strength used in ITR 39 to compute lateral earth pressures are, in our opinion, inappropriate for large magnitude earthquakes.

(3)

ITR 40 only verifies the magnitude of the parameters used in the sliding analysis.

Consistent with IDVP objectives, we believe that the ITR should assess the factor of safety against sliding under the Hosgri seismic event.

The concerns listed above were discussed with representatives of RLCA in some detail at the exit interview following the audit.

At that time the staff agreed that these matters are difficult to discuss in a number of ITRs of narrow scope, as was attempted.

It is our understanding that 8307050349 83062i PDR ADOCK 05000275 R

PDR OFFICEI SURNAME/

OATE P NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1991~960

h f

l I

y

,I P

ex,

Dr. Nilliam E. Cooper revisions to the four ITRs referenced will be made and that this information, as well as the remaining geotechnical issues, will be combined into a single report.

The NRC staff is available to discuss these matters further if you desire.

Sincerely,

Enclosure:

List of References Qpg~ ">><a ea>

~@Etc/'QJ g C

~

F

'~BOQhttt Darrell G. Eisenhut, Director Division of Licensing Office of Nuclear Reactor Regulation cc:

See next page

.DISTRIBUTION IDocument Control 50-2757 LB¹3 Reading JLee HSchierling HDenton RVollmer JKnight GLear LHeller HPolk BJagannath BBuckley LChandler TBishop PMorrill NRC PDR L PDR NSIC PRC System

  • See Previous Con rrence OFFICE/

SURNAME/

DATE$

  • DL:LB¹3

~ ~ ~ ~I ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

~ ~

HSchi erl ing

~ ~ ~ ~ ~ ~ ~ ~ ~I~ 0 ~ ~ ~ ~ ~ ~ ~ ~ ~

~

D LB;

~

~

Ao ~ ~

~ I ~ ~ ~ti ni g.his'n....

~ ~ ~ ~ ~ 1 ~ I~ I~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~

  • DE

~

~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

80094M

  • n~

~ ~ ~ CSA'

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

GLea r DX:....I.C

..APi Ighe eg ik3 L.'t ovak 6/g'83 DLro

""~

~ ~ ~

D. Ã.1. enhut....

..e~83........

NRC FORM 310 (10-80) NRCM 0240 OFFlClAL RECORD COPY USGPO: 1931~&960 1

I

'\\

d IP, W

1 J

~

5 h P

i ~ ~

u I

>'l, N

References:

l.

ITR-13, Rev. 0, "Diablo Canyon Unit 1 - IDVP, Soils-Intake Structure,"

by R. L. Cloud Associates, Inc., November 5, 1982.

2.

ITR-16, Rev. 0, "Diablo Canyon Unit 1 - IDVP, Soils-Outdoor Water Storage Tanks,'" by R. L. Cloud Associates, Inc., December 8, 1982.

3.

ITR-39, Rev. 0, "Diablo Canyon, Unit 1 - IDVP, Soils-Intake Structure Bearing Capacity and Later',~a'1" Earth Pressure,"

by R. L. Cloud Associates, Inc., February 25, 1983.

4.

ITR-40, Rev. 0, "Diablo Canyon Unit 1 - IDVP, Soils Report - Intake Structure Sliding Resistance,"

by R. L. Cloud Associates, Inc., March 9, 1983.

OFFICE/

SURNAMEP DATE$

NRC FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1981-33&960

0, 1

l

Diablo Canyon Mr. J.

0. Schuyler, Vice President Nuclear. Power Generation c/o Nuclear Power Generation, Licensing Pacific Gas and Electric Company 77 Beale Street, Room 1435 San Francisco,.California 94106 CC-Philip A: Crane, Jr.,

Esq.

Pacific Gas 5 Electric Company Post Office Box 7442 San Francisco, California 94120 Mr.'alcolm H. Furbush

'Vice President - General Counsel Paci fic Gas 5 Electri c Company Post Office Box 7443 San Francisco, California 94120 Janice E. Kerr, Esq.

California Public Utilities Commission 350 McAllister Street

~ San Francisco, California 94102 Mr. Frederick Eissler, President Scenic Shoreline Preservation Conference, Inc.

4623 More Mesa Drive Santa Barbara, California 93105 Ms. Elizabeth Apfelberg 1415 Cozadero San Luis Obispo, CA

. 93401 Mr.

Gordon A. Silver Ms.- Sandra A. Silver 1760 Alisal Street San Luis Obispo, CA. 93401 Harry M. Willis, Esq.

Seymour 8 Willis 601 California Street, Suite 2100 San Francisco, CA 94108 Mr. Richard Hubbard MHB Technical Associates Suite K

1725 Hamilton Avenue San Jose, CA 96125 Mr. John Marrs, Managing Editor San Luis Obispo County Telegram Tribune 1321 Johnson Avenue P. 0.

Box 112 San Luis Obispo, CA 93406 Resident Inspector/Diablo Canyon NPS c/o US Nuclear Regulatory Commission P. 0.

Box 369.

Avila Beach, California. 93424 Ms.

Raye Fleming 1920 Mattie Road Shell Beach, California 93440 Joel

Reynolds, Esq.

John R.- Phillips, Esq.

Center for. Law in the Public Interest 10951 West Pico Boulevard Third Floor Los Angeles,'al.ifornia 90064 Pau'1 C. Valentine, Esq.

321 Lytton Avenue Palo Alto, California 94302 Dr. William E. Cooper Project Manager 5511 Teledyne Engineering Services 130 Second. Avenue

'altham, Massachusetts 02254 Mr. Dick Blankenburg Editor E Co-Publisher South County Publishing Company P. 0. Box.460 Arroyo. Grande, Cal iforni a 93420 Bruce Norton, Esq.

Suite 202 3216 North 3rd Street Phoenix, Arizona 85012 Mr.

W. C. Gangloff Westinghouse Electric Corporation P. 0.

Box 355 Pittsburg, Pennsylvania 15230 David F. Fleischaker, Esq.

P.

0.

Box 1178 Oklahoma City, Oklahoma 73101

4

Qgl I

a

~

g) Diablo Canyon Arthur C. Gehr, Esq.

Snell 8 Wilmer 3100 Val.ley Center Phoenix, Arizona 85073 Mr.

Owen H. Davis, Director Federal Agency Relations Pacific Gas E Electric Company 1050 17th Street, N.

W.

Suite 1180 Washington, D.

C.

20036 Regional Administrator - Region V

US Nuclear Regulatory Commission 1450 Maria Lane Suite 210 Walnut Creek, Cal.ifornia 94596 Dr. Jose Roesset 3506 Duval Road Austin, Texas 78759

.Michael J. Strumwasser, Esq.

Special Council to the. Attorney General

State of California 3580 Wilshire Boulevard, Suite 800 Los Angeles 90010
Mr. Thomas H. Harris

,San Jose Mercury News 750 Ridder Park Drive San.Jose, California 95190 Mr. Mark Gottlieb.,

California Energy Commission 1111 Howe Avenue, MS 27 Sacramento, California 95825 Maurice Axelrad, Esq.

Lowenstein,

Newman, Reis and Axelrad 1025 Connecticut Avenue, NW Washington, D. C.

20036

~y r4 W

I

'