IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

4.1-6 Page:

1 of 2 REACTOR COOLANT PUMPS DESIGN DATA1 Number of Pumps 4 Design Pressure/Operating Pressure, psig 2485/2235 Hydrostatic Test Pressure (cold), psig 3106 Unit 1, 31072 Unit 2 Design Temperature (casing), oF 650 RPM at Nameplate Rating 1189 Suction Temperature, oF 536.3 (Unit 1)/541.003 (Unit 2)

Required net positive suction head, ft 170 Developed Head, ft 277 Capacity, gpm 88,500 Seal Water Injection, gpm 8

Seal Water Return, gpm 3

Pump Discharge Nozzle ID, in 27.5 Pump Suction Nozzle ID, in 31 Overall Unit Height, ft-in.

27-0 Water Volume, ft3 81 Pump-Motor Moment of Inertia, lb-ft2 82,000 MOTOR DATA:

Type AC Squirrel Cage Induction, Single Speed, Air Cooled Voltage 4000 Insulation Class F

Phase 3

1 Quantities are for each pump.

2 Original design.

3 Original design power capability parameter.

IINNDDIIAANNAA AANNDD M MIICCHHIIGGAANN PPOOW WEERR DD.. CC.. CCOOOOKK NNUUCCLLEEAARR PPLLAANNTT UUPPDDAATTEEDD FFIINNAALL SSAAFFEETTYY AANNAALLYYSSIISS RREEPPOORRTT Revision:

17 Table:

4.1-6 Page:

2 of 2 MOTOR DATA:

Type AC Squirrel Cage Induction, Single Speed, Air Cooled Frequency, Hz 60 Starting Current, amp 4800 Input (hot reactor coolant), kw 4337 Input (cold reactor coolant), kw 5663 Power, HP (nameplates )

6000 Pump Weight, lb. (dry) 175,200