N sx~era EN ERGY February 29, 2016 ANL NG-1 6-0047 10 CFR 2.202 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Duane Arnold Energy Center Docket No. 50-331 Renewed Op. License No. DPR-49 NextEra Energy Duane Arnold Energy Center, LLC's Six Month Status Report in Response to March 12, 2012 Commission Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)

References:

1) Order EA-12-051, "Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation" dated March 12, 2012 (ML12054A682)
2) Letter, R. Anderson (NextEra Energy Duane Arnold. LLC) to U.S.

NRC. "NextEra Energy Duane Arnold, LLC's Overall Inteqrated Plan in Response to March 12, 2012 Commission Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)," NG-13-0086 dated February 28, 2013 (ML13063A014)

On March 12, 2012, the Nuclear Regulatory Commission (NRC) issued Reference 1, an immediately effective Order to all licensees including NextEra Energy Duane Arnold, LLC (hereafter NextEra Energy Duane Arnold). In Reference 2, NextEra Energy Duane Arnold submitted an Overall Integrated Plan for the implementation of this Order. The Order required licensees to provide periodic status reports for the Overall Integrated Plan.

The purpose of this letter is to provide the next six-month status report pursuant to Section IV, Condition C.2, of Reference 1, that delineates progress made in implementing the requirements of Reference 1. The enclosure to this letter p1 NextEra Energy Duane Arnold, LLC, 3277 DAEC Road, Palo, IA 52324

Document Control Desk NG-1 6-0047 Page 2 of 2 provides an update of milestone accomplishments since the last status report, including any changes to the compliance method, schedule, or need for relief and the basis, if any.

If you have any questions or require additional information, contact Curt Bock at 319-851-7645.

I declare under penalty of perjury that the foregoing is true and correct.

xecut~lon Febru ary 29, 2016 T. A. Vehec Vice President, Duane Arnold Energy Center NextEra Energy Duane Arnold, LLC Enclosure cc:

Regional Administrator, USNRC, Region IIl Resident Inspector, USNRC, Duane Arnold Energy Center Project Manager, USNRC, Duane Arnold Energy Center

Enclosure to NG-16-0047 NextEra Energy Duane Arnold. LLC's Six Month Status Report for the Implementation of Order EA-12-051. Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation 2 pages follow

NEXTERA ENERGY DUANE ARNOLD, LLC DUANE ARNOLD ENERGY CENTER Six Month Status Report for the Implementation of Order EA-1 2-051, Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation

1. Introduction NextEra Energy Duane Arnold, LLC (hereafter, NextEra Energy Duane Arnold) developed an Overall Integrated Plan (Reference 1), documenting the planned modification with regard to Reliable Spent Fuel Pool Instrumentation (SEPI) in response to Reference 2. This enclosure provides an update of milestone accomplishments since submittal of the Overall Integrated Plan and the last status update, including any changes to the compliance method, schedule, or need for relief/relaxation and the basis, if any.
2. Milestone Accomplishments The following milestones have been completed since the submittal of the last status update (Reference 3), and are current as of January 31, 2016.

Commence Engineering and Design Complete Design

3. Milestone Schedule Status The target completion date for Milestone "Complete Installation of SFP Instruments" has been revised to the second quarter of 2016.

The dates are planning dates subject to change as design and implementation details are developed.

TargetRevised MiesonrCmpetio Activity Target DattoeCopeto Status Completion Date Date Commence Engineering and Design In Progress Completed N/A Complete Design 4Q 2015 Completed N/A Complete Procurement of SFP 2Q 2016 Completed N/A Instruments Complete Installation of SEP 4Q 2016 Not Started 2Q 2016 Instruments Instruments Operational and Training 4Q 2016 Not Started N/A Complete________

4. Changes to Compliance Method There are no changes to the compliance method as documented in the Overall Integrated Plan and past status updates.

Page 1 of 2

5. Need for Relief/Relaxation and Basis for the Relief/Relaxation Duane Arnold is not requesting relief from the requirements of Order EA-12-051 (Reference 2) at this time.
6. Requests for Additional Information The NRC staff determined that additional information was required to enable the continued technical review of the NextEra Energy Duane Arnold's Overall Integrated Plan (OIP). Requests for Information (RAIs) were provided in Reference 4 as corrected by Reference 5. Per a letter to all licensees, (Reference 6), the NRC notified licensees to not formally submit responses to RAIs on the docket, but instead provide their responses and supporting information on their ePortals. The DAEC RAI responses and supporting information were uploaded to the CERTREC ePortal in December of 2015.
7. References
1) Letter, R. Anderson (NextEra Energy Duane Arnold, LLC) to U.S. NRC, "NextEra Energy Duane Arnold, LLC's Overall Integrated Plan in Response to March 12, 2012 Commission Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)," NG-13-0086 dated February 28, 2013 (ML13063A014)
2) Order EA-12-051, "Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation" dated March 12, 2012 (ML12054A682)
3) Letter, T.A. Vehec (NextEra Energy Duane Arnold, LLC) to U.S. NRC, "NextEra Energy Duane Arnold Energy Center, LLC's Six-Month Status Report in Response to March 12, 2012 Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)," NG 0280 dated August 27, 2015 (ML15243A033)
4) NRC Letter, "Duane Arnold Energy Center-Interim Staff Evaluation and Request For Additional Information Regarding the Overall Integrated Plan for Implementation of Order EA-12-051, Reliable Spent Fuel Pool Instrumentation,"

dated November 26, 2013 (ML13323B443)

5) NRC Letter, "Correction Letter-Duane Arnold Energy Center Regarding Interim Staff Evaluation and Request for Additional Information for Reliable Spent Fuel Pool Instrumentation (Order EA-12-051 )," dated January 17, 2014 (ML14007A215)
6) NRC Letter dated March 26, 2014, Nuclear Regulatory Commission Audits of Licensee Responses to Reliable Spent Fuel Pool Instrumentation Order EA-12-051 (ML14083A620)

Page 2 of 2

N sx~era EN ERGY February 29, 2016 ANL NG-1 6-0047 10 CFR 2.202 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Duane Arnold Energy Center Docket No. 50-331 Renewed Op. License No. DPR-49 NextEra Energy Duane Arnold Energy Center, LLC's Six Month Status Report in Response to March 12, 2012 Commission Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)

References:

1) Order EA-12-051, "Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation" dated March 12, 2012 (ML12054A682)
2) Letter, R. Anderson (NextEra Energy Duane Arnold. LLC) to U.S.

NRC. "NextEra Energy Duane Arnold, LLC's Overall Inteqrated Plan in Response to March 12, 2012 Commission Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)," NG-13-0086 dated February 28, 2013 (ML13063A014)

On March 12, 2012, the Nuclear Regulatory Commission (NRC) issued Reference 1, an immediately effective Order to all licensees including NextEra Energy Duane Arnold, LLC (hereafter NextEra Energy Duane Arnold). In Reference 2, NextEra Energy Duane Arnold submitted an Overall Integrated Plan for the implementation of this Order. The Order required licensees to provide periodic status reports for the Overall Integrated Plan.

The purpose of this letter is to provide the next six-month status report pursuant to Section IV, Condition C.2, of Reference 1, that delineates progress made in implementing the requirements of Reference 1. The enclosure to this letter p1 NextEra Energy Duane Arnold, LLC, 3277 DAEC Road, Palo, IA 52324

Document Control Desk NG-1 6-0047 Page 2 of 2 provides an update of milestone accomplishments since the last status report, including any changes to the compliance method, schedule, or need for relief and the basis, if any.

If you have any questions or require additional information, contact Curt Bock at 319-851-7645.

I declare under penalty of perjury that the foregoing is true and correct.

xecut~lon Febru ary 29, 2016 T. A. Vehec Vice President, Duane Arnold Energy Center NextEra Energy Duane Arnold, LLC Enclosure cc:

Regional Administrator, USNRC, Region IIl Resident Inspector, USNRC, Duane Arnold Energy Center Project Manager, USNRC, Duane Arnold Energy Center

Enclosure to NG-16-0047 NextEra Energy Duane Arnold. LLC's Six Month Status Report for the Implementation of Order EA-12-051. Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation 2 pages follow

NEXTERA ENERGY DUANE ARNOLD, LLC DUANE ARNOLD ENERGY CENTER Six Month Status Report for the Implementation of Order EA-1 2-051, Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation

1. Introduction NextEra Energy Duane Arnold, LLC (hereafter, NextEra Energy Duane Arnold) developed an Overall Integrated Plan (Reference 1), documenting the planned modification with regard to Reliable Spent Fuel Pool Instrumentation (SEPI) in response to Reference 2. This enclosure provides an update of milestone accomplishments since submittal of the Overall Integrated Plan and the last status update, including any changes to the compliance method, schedule, or need for relief/relaxation and the basis, if any.
2. Milestone Accomplishments The following milestones have been completed since the submittal of the last status update (Reference 3), and are current as of January 31, 2016.

Commence Engineering and Design Complete Design

3. Milestone Schedule Status The target completion date for Milestone "Complete Installation of SFP Instruments" has been revised to the second quarter of 2016.

The dates are planning dates subject to change as design and implementation details are developed.

TargetRevised MiesonrCmpetio Activity Target DattoeCopeto Status Completion Date Date Commence Engineering and Design In Progress Completed N/A Complete Design 4Q 2015 Completed N/A Complete Procurement of SFP 2Q 2016 Completed N/A Instruments Complete Installation of SEP 4Q 2016 Not Started 2Q 2016 Instruments Instruments Operational and Training 4Q 2016 Not Started N/A Complete________

4. Changes to Compliance Method There are no changes to the compliance method as documented in the Overall Integrated Plan and past status updates.

Page 1 of 2

5. Need for Relief/Relaxation and Basis for the Relief/Relaxation Duane Arnold is not requesting relief from the requirements of Order EA-12-051 (Reference 2) at this time.
6. Requests for Additional Information The NRC staff determined that additional information was required to enable the continued technical review of the NextEra Energy Duane Arnold's Overall Integrated Plan (OIP). Requests for Information (RAIs) were provided in Reference 4 as corrected by Reference 5. Per a letter to all licensees, (Reference 6), the NRC notified licensees to not formally submit responses to RAIs on the docket, but instead provide their responses and supporting information on their ePortals. The DAEC RAI responses and supporting information were uploaded to the CERTREC ePortal in December of 2015.
7. References
1) Letter, R. Anderson (NextEra Energy Duane Arnold, LLC) to U.S. NRC, "NextEra Energy Duane Arnold, LLC's Overall Integrated Plan in Response to March 12, 2012 Commission Order to Modify Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)," NG-13-0086 dated February 28, 2013 (ML13063A014)
2) Order EA-12-051, "Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation" dated March 12, 2012 (ML12054A682)
3) Letter, T.A. Vehec (NextEra Energy Duane Arnold, LLC) to U.S. NRC, "NextEra Energy Duane Arnold Energy Center, LLC's Six-Month Status Report in Response to March 12, 2012 Commission Order Modifying Licenses with Regard to Reliable Spent Fuel Pool Instrumentation (Order Number EA-12-051)," NG 0280 dated August 27, 2015 (ML15243A033)
4) NRC Letter, "Duane Arnold Energy Center-Interim Staff Evaluation and Request For Additional Information Regarding the Overall Integrated Plan for Implementation of Order EA-12-051, Reliable Spent Fuel Pool Instrumentation,"

dated November 26, 2013 (ML13323B443)

5) NRC Letter, "Correction Letter-Duane Arnold Energy Center Regarding Interim Staff Evaluation and Request for Additional Information for Reliable Spent Fuel Pool Instrumentation (Order EA-12-051 )," dated January 17, 2014 (ML14007A215)
6) NRC Letter dated March 26, 2014, Nuclear Regulatory Commission Audits of Licensee Responses to Reliable Spent Fuel Pool Instrumentation Order EA-12-051 (ML14083A620)

Page 2 of 2