Curtiss-Wright Corp. - Notification of Part 21 Report on Eaton/Cutler Hammer A200 Series Starters (and Contactors), Per North Anna, H.B. Robinson, Diablo Canyon, and Hatch
ML16020A476
Person / Time
Site: Hatch, North Anna, Diablo Canyon, Robinson  Duke Energy icon.png
Issue date: 12/18/2015
From: Troutner J
Curtiss-Wright Corp
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML16020A476 (3)


Text

CUR TISS "

VWRIGHT 1.2.01IF515539 4000 East Tech Dflw, Cincinnat, Oil 4,s.us December 1 8, 2015

Subject:

Notification of I0CFR Part 21 on Eaton/Cutler Hammer A200 series Starters (&

Contactors)

Pacific Gas and Electric (PGE) reported to QTNP that they have had eigbt Cutler Hammer A200 series starter failures since September 15, 2008. The failures would remain in the operated/energized contact state with power removed for some period of time. All starters impacted with this failure were continuously energized. The concern was that if tripped, that the main contacts would not open to protect the motor.

Testing was performed by Eaton Industrial Controls Division after receiving defective samples from PGE.

The Test Report from Eaton was received by QTNP for further review and evaluation. On October 6, 2015 QTNP determined that the Cutler Hammer A200 series starter failures may be reportable and an extent of condition review needed to be done.

The root cause was a silicon based mold release that remained on the molded parts and would come between the moving (magnet) & fixed armatures. When heated for an extended period of time, this material would become sticky causing anywhere from a minor delay in opening, up to a frozen closed condition.

Cutler Hammer has determined that the silicone mold release was first introduced into the manufacturing facility in May 2008 due to a shortage of the Zinc Stearate Mold release that was traditionally used. The silicon based mold release was periodically used until October 2012.

According to Cutler Hammer, anything made after January 1, 2013 should definitely be silicon mold release free.

Thus any starters/contactors of the CH A200 series manufactured between May 2008 &

December 31, 2012 could have this concern. This failure has only been reported for continuously energized applications. The end user should evaluate their applications for this potential failure mechanism.

Corrective Action to Prevent recurrence:

  • QualTech has notified all of the affected customers listed in the attached table regarding this issue.
  • QualTech will revise applicable dedication plans to add a caution that "Any starters/contactors of the CH A200 series manufactured between May 2008 &

December 31, 2012 may not be dedicated and are unacceptable". Or similar language and provide a reference to this notification or Corrective Action document that applies to this notification.

Page 1 of 2

/Jg

Should you have any questions, please contact me at 513-328-7900 or Tim Franchuk at 513-201 -2176 Sincerely, General Manager, Curtiss-Wright QualTech, NP

CURT/SS -

WRIGHT QuaTodNP P: 513 528.7900 I F: 513.528.929 Customer Plant Customer Year S/N / Date PO#:

sold/shipped

______/T#

Relay Qty Tag#

Code Dominion North Anna 4500033020 12/13/2012 CC 1995/CJ2385 A200MACAC 1

CJ238501 C121 119 Dominion North Anna 4500034851 1/11/2013 CC2019/CJ2415 A200MACAC 1

CJ241501 C121119 Dominion North Anna 45813045 2/10/2011 CC285/CJ361 A200MACAC 1

CJ36101 CIO1023 Dominion North Anna 45597232 7/18/2008 T8270.1 A200MACAC 1

T827001 C0801 18 Dominion North Anna 45619298 9/26/2008 T8446.1 A200MACAC 1

T844601 C0801 18 01..02:C120111 03: C1201 16 H.B.ROBI SON04:

C111230 Duke HPBLA BNT O 00607524 2/16/2012 CC 1262/CJI52I A201KICA 8

CJI52101 05:C110909 06: C110914 07: C1l1111 08: C1 11128 Duke PLANT RO SN00608576 3/26/2012 CC1293/CJ1555 A&201KICA 6

CJ155501 01-2: C110909 HP.

OBNT ON03-06:

CI10915 KRSKO Slovienia 10106/479 4/13/2010 T8610.1 A201KSCH 2

T861003 02: C090323

____________________03:

C100331 KRSKO Slovienia 10106/479 4/13/2010 T8610.1 A20IK4CH 1

T861004 C090115 PG&E DIABLO CANYON 3500947987 4/2/2013 CC1818/CJ2177 A200MI CACEJ4 6

CJ217701 01-06:C120928 01: C100603 02: C100617 PG&E DIABLO CANYON 3500889322 2/10/2011 CC298/CJ380 A201KOCA 9

CJ38001 03: C100701 04-07: C101208 08-09: CI 10111 PG&E DIABLO CANYON 3500902818 7/27/2011 CC658/CJ805 A200MOCACDEJ4 5

CJ80501 01-05: C110719 PG&E DIABLO CANYON 136862 6/16/2008 T8169.1 A200MI CACFJ4 6

T816901 01-06: C080429 PG&E Df*.lAC£ DIABLO CANYON 3500842462 "9/29/2009 T9421lEL A200MOCACDEJ4 2

6 T942 102 01: C090826 02: C090923 01-06: C090831!

C 120627 Date Code is:

YYMMDD Page 2 of 2

CUR TISS "

VWRIGHT 1.2.01IF515539 4000 East Tech Dflw, Cincinnat, Oil 4,s.us December 1 8, 2015

Subject:

Notification of I0CFR Part 21 on Eaton/Cutler Hammer A200 series Starters (&

Contactors)

Pacific Gas and Electric (PGE) reported to QTNP that they have had eigbt Cutler Hammer A200 series starter failures since September 15, 2008. The failures would remain in the operated/energized contact state with power removed for some period of time. All starters impacted with this failure were continuously energized. The concern was that if tripped, that the main contacts would not open to protect the motor.

Testing was performed by Eaton Industrial Controls Division after receiving defective samples from PGE.

The Test Report from Eaton was received by QTNP for further review and evaluation. On October 6, 2015 QTNP determined that the Cutler Hammer A200 series starter failures may be reportable and an extent of condition review needed to be done.

The root cause was a silicon based mold release that remained on the molded parts and would come between the moving (magnet) & fixed armatures. When heated for an extended period of time, this material would become sticky causing anywhere from a minor delay in opening, up to a frozen closed condition.

Cutler Hammer has determined that the silicone mold release was first introduced into the manufacturing facility in May 2008 due to a shortage of the Zinc Stearate Mold release that was traditionally used. The silicon based mold release was periodically used until October 2012.

According to Cutler Hammer, anything made after January 1, 2013 should definitely be silicon mold release free.

Thus any starters/contactors of the CH A200 series manufactured between May 2008 &

December 31, 2012 could have this concern. This failure has only been reported for continuously energized applications. The end user should evaluate their applications for this potential failure mechanism.

Corrective Action to Prevent recurrence:

  • QualTech has notified all of the affected customers listed in the attached table regarding this issue.
  • QualTech will revise applicable dedication plans to add a caution that "Any starters/contactors of the CH A200 series manufactured between May 2008 &

December 31, 2012 may not be dedicated and are unacceptable". Or similar language and provide a reference to this notification or Corrective Action document that applies to this notification.

Page 1 of 2

/Jg

Should you have any questions, please contact me at 513-328-7900 or Tim Franchuk at 513-201 -2176 Sincerely, General Manager, Curtiss-Wright QualTech, NP

CURT/SS -

WRIGHT QuaTodNP P: 513 528.7900 I F: 513.528.929 Customer Plant Customer Year S/N / Date PO#:

sold/shipped

______/T#

Relay Qty Tag#

Code Dominion North Anna 4500033020 12/13/2012 CC 1995/CJ2385 A200MACAC 1

CJ238501 C121 119 Dominion North Anna 4500034851 1/11/2013 CC2019/CJ2415 A200MACAC 1

CJ241501 C121119 Dominion North Anna 45813045 2/10/2011 CC285/CJ361 A200MACAC 1

CJ36101 CIO1023 Dominion North Anna 45597232 7/18/2008 T8270.1 A200MACAC 1

T827001 C0801 18 Dominion North Anna 45619298 9/26/2008 T8446.1 A200MACAC 1

T844601 C0801 18 01..02:C120111 03: C1201 16 H.B.ROBI SON04:

C111230 Duke HPBLA BNT O 00607524 2/16/2012 CC 1262/CJI52I A201KICA 8

CJI52101 05:C110909 06: C110914 07: C1l1111 08: C1 11128 Duke PLANT RO SN00608576 3/26/2012 CC1293/CJ1555 A&201KICA 6

CJ155501 01-2: C110909 HP.

OBNT ON03-06:

CI10915 KRSKO Slovienia 10106/479 4/13/2010 T8610.1 A201KSCH 2

T861003 02: C090323

____________________03:

C100331 KRSKO Slovienia 10106/479 4/13/2010 T8610.1 A20IK4CH 1

T861004 C090115 PG&E DIABLO CANYON 3500947987 4/2/2013 CC1818/CJ2177 A200MI CACEJ4 6

CJ217701 01-06:C120928 01: C100603 02: C100617 PG&E DIABLO CANYON 3500889322 2/10/2011 CC298/CJ380 A201KOCA 9

CJ38001 03: C100701 04-07: C101208 08-09: CI 10111 PG&E DIABLO CANYON 3500902818 7/27/2011 CC658/CJ805 A200MOCACDEJ4 5

CJ80501 01-05: C110719 PG&E DIABLO CANYON 136862 6/16/2008 T8169.1 A200MI CACFJ4 6

T816901 01-06: C080429 PG&E Df*.lAC£ DIABLO CANYON 3500842462 "9/29/2009 T9421lEL A200MOCACDEJ4 2

6 T942 102 01: C090826 02: C090923 01-06: C090831!

C 120627 Date Code is:

YYMMDD Page 2 of 2