ML15303A006
| ML15303A006 | |
| Person / Time | |
|---|---|
| Site: | Catawba |
| Issue date: | 10/26/2015 |
| From: | Swanson D Emerson Process Management |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| 51494 | |
| Download: ML15303A006 (6) | |
Text
10/26/2015 U.S. Nuclear Reeulatorv Commission Operations Center Event Report Pa*e I Part 21 (PAR)
Event #
51494
- Rep Org: EMERSON PROCESS MANAGEMENT Notification Date I Time: 10/23/2015 16:53 (EDT)
Supplier: FISHER CONTROLS INTERNATIONAL LLC Event Date /ITime: 09/02/2015 (CDT)
Last Modification: 10/23/2015 Region:
3 Docket #:
City:
MARSHALLTOWN Agreement State:
Yes County:
.License #:
State:
IA NRC Notified by: DENNIS SWANSON Notifications: ALAN BLAMEY R2DO HQ Ops Officer: DONG HWA PARK PART 21/50.55 REACTORS EMAIL Emergency Class: NON EMERGENCY 10 CFR Section:
21.21(d)(3)(i)
DEFECTS AND NONCOMPLIANCE 50.55(e)
CONSTRUCT DEFICIENCY PART-21 REPORT - CLOSED SWITCH NOT ACTUATING WHEN VALVE IS FULLY CLOSED The following is a summary of a submitted facsimile:
"Items subject to this Fisher Information Notice (FIN) were provided to Catawba Nuclear Station (CNS) per CNS Order 00178457 (Fisher Order Number 033-D800306145). Specifically, Fisher supplied an 8 inch Design All Butterfly Valve with a Type 1052 Actuator and Top Worx Switches, serial number F000458892 ('Equipment'). The issue is with the closed switch not actuating when the valve is fully closed.
"The purpose of this FIN is to alert CNS that as of 2 September 2015, Fisher Controls International LLC (Fisher) became aware of a situation which may affect the performance of the Equipment, including its safety-related function.
"If there are any technical questions or concerns, please contact: Ben Ahrens, Quality Manager, Emerson Process Management, Fisher Controls International LLC, 301 South 1st Avenue, Marshalltown, La 50158, Phone:
(641) 754-2249, benjamin~ahrens@emerson.com"
Oct. 23. 2315 3'05PM Jo353 P 1 N0,0540 P, 1 Process Maiiagernent:
Facsimile 301 South First Ave Marshalitown, IA 50166 T 641-754-3011 F 641-754-2830 To:
NRC Operations Center - Attn: Bill I-uffman Fax:
301-816-5161 From:
Dennis Swanson, Emerson Process Management Date:
1012312015 Pages:
5 (In c cover)
Attachment:
Fisher Information Notice - (FIN) 2015-03 For technical questions please contact George Baitinger at (641,) 754-2026.
Oct. 23. 2Q15 3'05PM040 P2 No, 0540 P, 2 EMERSON.
Process Management Fisher Controls International LOC 301 South First Ave.
P.O. Box 190 Marshalitowri, Iowa 50155-0190 USA T (641) 754-S011 F (641) 754-2830 October 23, 2015 To Whom It May Concern:
Attached is a Fisher information Notice, (FIN) 2015-03.
Emerson Process Management - Fisher Valves complies with the reporting requirements of 10 CFR Part 21 Section 21.21 (b) and 10 CFR Part 50.55 (e) by informing the U.S. Nuclear Regulatory Commission Licensees or Purchaser of deviations or failures to comply.
Please review the attached FIN notice for applicability to your facility.
George Baitinger Director, Quality Americas Attachments
Oct. 23. 2015 3:05PM EMERSON.
Process Management No. 0540 P. 3 Fisher Controls International LLC 301 South Firat Ave PD.O Box 190 Mershailtown, Iowa.501 58-0190 USA.
T (64-1) 754-3011 F (54i-) 754-,2.830 Fisher Information Notice: FIN 2015-03 22 October 2015
Subject:
t Safety Related Switch Misalignment From:"
(C)IA/\\<2 Chad Engle Nuclear Business Unit Direotor Fisher Controls International LLC 301 South First Avenue Marshalitown, IA 50156 Fax: (641) 754-2854 Equipment Affected by this Information Notice:
Items subject to this Fisher Information Notice (FIN) were provided to Catawba Nuclear Station (CA(S) per CNS Order 00178457 (Fisher Order Number 033 -D800206145J.
Specifically, Fisher supplied an 30 Design All Butterfly Valve with a Type 1052 Actuator and Top Worr Switches, serial number F:000458802 ("Equipment"j. The Issue Is with the closed switch not actuating when the valve is fully closed.
Purpose; The purpose of this FIN is to alert CNS that as of 2 September 2015, Fisher Controls International LLC (Fisher) became aware of a situation which may affect the performance of the Equipment, including its safety-related function.
Fisher is informing CNS of this circumstance in accordance with Section 21.21 (b) of 10 CFR 21.
FISHER Page I of 3
Oct. 23. 2015 3:05PM o050 P4 No, 0540 P, 4 Fisher Information Notice: FIN 2015-03 Applicability:
This FIN applies only to the subject Equipment supplied by Fisher Controls to ONS via the aforementioned order.
Discussion:
The switches are operated by Target Magnets on a bracket which is attached to a hub in the actuator housing. The hub rotates based on valve shaft rotation. The shaft and hub are indexed for proper disc positioning. For the subject valve, the proper alignment and indexing for disc/shaft pinning was incorrect. This misalignment resulted in a misalignment of the Target Magnets to the closed swItch, such that it would not actuate when the disc was fully closed.
The open switch was also mnisaligned, but not to an extent that prevents the switch from actuating.
This issue was discovered following receipt of the Equipment by CNS. Duke's diagnostic testing determined the closed limit switch was not actuating with the valve fully closed. Further examination was performed by Fisher Lifecycle Services Colombia, which confirmed this finding.
It is assumed that the ostensibly identical valve assembly provided on Order 033 -D800306145 (item CC2A) has successfully undergone functional testing and does not have the same defect.
Action Required:
Fisher will provide CNS with a properly pinned Disc/Shaft Assembly which will properly align Hub and Target Magnet Bracket allowing for proper switch actuation, in addition, a Corrective Action Request (CAR 1772) has been initiated by Fisher to prevent reoccurrence of this issue.
FISHER Page 2 of 3
Oct,23.
2615 3:66PMNo656 P5 No, 0540 P, 5 Fisher Information Notice: FIN 2015-03 1 0 CFR 21 Implications; Fisher requests that the recipient of this rnotice review it and take appropriate acton in accordance with 10 CFR 21. if there are any technical questions or concerns, please contact:
Ben Ahuens Quality Manager Emerson Process Management Fisher Controls International LLC 301,South 1st Avenue Marshalltowri, IA 50158 Phone: (641) 764-2249 beniarnin.ahrensc~ernerson~com Page 3 of 3
10/26/2015 U.S. Nuclear Reeulatorv Commission Operations Center Event Report Pa*e I Part 21 (PAR)
Event #
51494
- Rep Org: EMERSON PROCESS MANAGEMENT Notification Date I Time: 10/23/2015 16:53 (EDT)
Supplier: FISHER CONTROLS INTERNATIONAL LLC Event Date /ITime: 09/02/2015 (CDT)
Last Modification: 10/23/2015 Region:
3 Docket #:
City:
MARSHALLTOWN Agreement State:
Yes County:
.License #:
State:
IA NRC Notified by: DENNIS SWANSON Notifications: ALAN BLAMEY R2DO HQ Ops Officer: DONG HWA PARK PART 21/50.55 REACTORS EMAIL Emergency Class: NON EMERGENCY 10 CFR Section:
21.21(d)(3)(i)
DEFECTS AND NONCOMPLIANCE 50.55(e)
CONSTRUCT DEFICIENCY PART-21 REPORT - CLOSED SWITCH NOT ACTUATING WHEN VALVE IS FULLY CLOSED The following is a summary of a submitted facsimile:
"Items subject to this Fisher Information Notice (FIN) were provided to Catawba Nuclear Station (CNS) per CNS Order 00178457 (Fisher Order Number 033-D800306145). Specifically, Fisher supplied an 8 inch Design All Butterfly Valve with a Type 1052 Actuator and Top Worx Switches, serial number F000458892 ('Equipment'). The issue is with the closed switch not actuating when the valve is fully closed.
"The purpose of this FIN is to alert CNS that as of 2 September 2015, Fisher Controls International LLC (Fisher) became aware of a situation which may affect the performance of the Equipment, including its safety-related function.
"If there are any technical questions or concerns, please contact: Ben Ahrens, Quality Manager, Emerson Process Management, Fisher Controls International LLC, 301 South 1st Avenue, Marshalltown, La 50158, Phone:
(641) 754-2249, benjamin~ahrens@emerson.com"
Oct. 23. 2315 3'05PM Jo353 P 1 N0,0540 P, 1 Process Maiiagernent:
Facsimile 301 South First Ave Marshalitown, IA 50166 T 641-754-3011 F 641-754-2830 To:
NRC Operations Center - Attn: Bill I-uffman Fax:
301-816-5161 From:
Dennis Swanson, Emerson Process Management Date:
1012312015 Pages:
5 (In c cover)
Attachment:
Fisher Information Notice - (FIN) 2015-03 For technical questions please contact George Baitinger at (641,) 754-2026.
Oct. 23. 2Q15 3'05PM040 P2 No, 0540 P, 2 EMERSON.
Process Management Fisher Controls International LOC 301 South First Ave.
P.O. Box 190 Marshalitowri, Iowa 50155-0190 USA T (641) 754-S011 F (641) 754-2830 October 23, 2015 To Whom It May Concern:
Attached is a Fisher information Notice, (FIN) 2015-03.
Emerson Process Management - Fisher Valves complies with the reporting requirements of 10 CFR Part 21 Section 21.21 (b) and 10 CFR Part 50.55 (e) by informing the U.S. Nuclear Regulatory Commission Licensees or Purchaser of deviations or failures to comply.
Please review the attached FIN notice for applicability to your facility.
George Baitinger Director, Quality Americas Attachments
Oct. 23. 2015 3:05PM EMERSON.
Process Management No. 0540 P. 3 Fisher Controls International LLC 301 South Firat Ave PD.O Box 190 Mershailtown, Iowa.501 58-0190 USA.
T (64-1) 754-3011 F (54i-) 754-,2.830 Fisher Information Notice: FIN 2015-03 22 October 2015
Subject:
t Safety Related Switch Misalignment From:"
(C)IA/\\<2 Chad Engle Nuclear Business Unit Direotor Fisher Controls International LLC 301 South First Avenue Marshalitown, IA 50156 Fax: (641) 754-2854 Equipment Affected by this Information Notice:
Items subject to this Fisher Information Notice (FIN) were provided to Catawba Nuclear Station (CA(S) per CNS Order 00178457 (Fisher Order Number 033 -D800206145J.
Specifically, Fisher supplied an 30 Design All Butterfly Valve with a Type 1052 Actuator and Top Worr Switches, serial number F:000458802 ("Equipment"j. The Issue Is with the closed switch not actuating when the valve is fully closed.
Purpose; The purpose of this FIN is to alert CNS that as of 2 September 2015, Fisher Controls International LLC (Fisher) became aware of a situation which may affect the performance of the Equipment, including its safety-related function.
Fisher is informing CNS of this circumstance in accordance with Section 21.21 (b) of 10 CFR 21.
FISHER Page I of 3
Oct. 23. 2015 3:05PM o050 P4 No, 0540 P, 4 Fisher Information Notice: FIN 2015-03 Applicability:
This FIN applies only to the subject Equipment supplied by Fisher Controls to ONS via the aforementioned order.
Discussion:
The switches are operated by Target Magnets on a bracket which is attached to a hub in the actuator housing. The hub rotates based on valve shaft rotation. The shaft and hub are indexed for proper disc positioning. For the subject valve, the proper alignment and indexing for disc/shaft pinning was incorrect. This misalignment resulted in a misalignment of the Target Magnets to the closed swItch, such that it would not actuate when the disc was fully closed.
The open switch was also mnisaligned, but not to an extent that prevents the switch from actuating.
This issue was discovered following receipt of the Equipment by CNS. Duke's diagnostic testing determined the closed limit switch was not actuating with the valve fully closed. Further examination was performed by Fisher Lifecycle Services Colombia, which confirmed this finding.
It is assumed that the ostensibly identical valve assembly provided on Order 033 -D800306145 (item CC2A) has successfully undergone functional testing and does not have the same defect.
Action Required:
Fisher will provide CNS with a properly pinned Disc/Shaft Assembly which will properly align Hub and Target Magnet Bracket allowing for proper switch actuation, in addition, a Corrective Action Request (CAR 1772) has been initiated by Fisher to prevent reoccurrence of this issue.
FISHER Page 2 of 3
Oct,23.
2615 3:66PMNo656 P5 No, 0540 P, 5 Fisher Information Notice: FIN 2015-03 1 0 CFR 21 Implications; Fisher requests that the recipient of this rnotice review it and take appropriate acton in accordance with 10 CFR 21. if there are any technical questions or concerns, please contact:
Ben Ahuens Quality Manager Emerson Process Management Fisher Controls International LLC 301,South 1st Avenue Marshalltowri, IA 50158 Phone: (641) 764-2249 beniarnin.ahrensc~ernerson~com Page 3 of 3