ML15261A209

From kanterella
Jump to navigation Jump to search
EN-98-056:on 980807,notice of Violation for Level II Violation Will Be Issued to Licensee,But NRC Will Exercise Enforcement Discretion Per Section VI.B.3 of Enforcement Policy & Not Issue Civil Penalty
ML15261A209
Person / Time
Site: Oconee  Duke Energy icon.png
Issue date: 07/31/1998
From: Satorius M, Westreich B
NRC OFFICE OF ENFORCEMENT (OE)
To:
References
EA-98-268, EN-98-056, EN-98-56, NUDOCS 9811170325
Download: ML15261A209 (2)


Text

CATEGORY 10 REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9811170325 DOC.DATE: 98/07/31 NOTARIZED: NO DOCKET #

FACIL:50-269 Oconee Nuclear Station, Unit 1, Duke Power Co.

05000269 50-270 Oconee Nuclear Station, Unit 2, Duke Power Co.

05000270 50-287 Oconee Nuclear Station, Unit 3, Duke Power Co.

05000287 AUTH.NAME AUTHOR AFFILIATION WESTREICH,B.

Ofc of Enforcement (Post 870413)

SATORIUS,M.

Ofc of Enforcement (Post 870413)

RECIP.NAME RECIPIENT AFFILIATION C

SUBJECT:

EN-98-056:on 980807,notice of violation for level II A

violation will be issued to licensee,but NRC will exercise enforcement discretion per section VI.B.3 of Enforcement T

Policy & not issue civil penalty.

DISTRIBUTION CODE: IE33F COPIES RECEIVED:LTR 0 ENCL SIZE:

E TITLE: Enforcement Notice (EN)

G NOTES:

O RECIPIENT COPIES RECIPIENT COPIES R

ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL y

INTERNAL: AEOD/SPD/RRAB 1

1 E

1 NRR/DRPM/PERB 1

NUDOCS FULL TXT 1

OE DIR 1

OE FILE 01 1

1 EXTERNAL: LITCO BRYCE,J H 1

NOAC 1

NRC PDR 1

D 0

C U

M E

T NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE.

TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD) ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED: LTTR ENCL 9

July 31, 1998 EN 98-056 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT -ACTION Lipensee Duke Energy Corporation EA 98-268 Oconee Nuclear Station, Units 1, 2 and 3 Docket Numbers: 50-269; 50-270; 50-287 Subiect:

EXERCISE OF ENFORCEMENT DISCRETION This is to inform the Commission that the staff intends to issue a Notice of Violation for a Severity Level II Violation to Duke Energy Corporation (DEC), but exercise enforcement discretion per Section VI.B.3 of the Enforcement Policy and not issue a Civil Penalty. This action is based on (1) the failure to implement the requirements of 10 CFR 50, Appendix B, Criterion Ill, to incorporate design basis requirements into drawings and procedures; and, (2) the failure to maintain Technical Specification (TS) equipment in an operable condition.

Specifically, DEC failed to ensure that the as-built height configuration of the boric water storage tank (BWST) level instrument taps were adequately incorporated into system design drawings and calibration procedures and failed to incorporate the reactor building (RB) wide range level instrument uncertainties into the emergency operating procedures (EOPs). As a result of this condition, resolution of a conflict between the EOP requirements for initiation of swapover to recirculation during accident scenarios and actual tank and sump level indications, depended heavily on the ability of operators, in a relatively short time period, to recognize the conflict and deviate from the EOP requirements to prevent air entrainment and damage to the high pressure injection (HPI), low pressure injection (LPI) and reactor building spray (BS) systems. The staff has determined that there was not reasonable assurance that the ECCS system could have fulfilled its intended safety function across the full spectrum of break sizes that could result in a loss of coolant accident.

The violation involved a past problem in design. The issues were licensee-identified a part of a self initiated audit, corrective actions were comprehensive and routine licensee efforts were not likely to have identified the deficiencies. Therefore, discretion in accordance with Section VII.B.3 of the Enforcement Policy to refrain from issuing a civil penalty for a Severity Level II violation involving a past problem was exercised.

It should be noted that the licensee has not been specifically informed of the enforcement action. The schedule of issuance and notification is:

Mailing of Notice August 7, 1998 Telephone Notification of Licensee August 7, 1998 The State of South Carolina will be notified.

The licensee has thirty days from the date of the Notice in which to respond.

Contacts: B. Westreich, OE, (301) 415-3456 M. Satorius, OE, (301) 415-2747 Distribution OWFN OWFN TWFN Regional Offices Chairman Jackson EDO OC RI o Comm.

DEDR AEOD RIl WCFO 0 Comm. Diaz DEDE OP CTR RIII Comm. McGaffigan OE NMSS RIV SECY OGC IRM MAIL nor OCA NRR OIG NUDOCS PA 01 RES PUBLIC IP SP ACRS PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION