1 NRR-PMDAPEm Resource From:

Saba, Farideh Sent:

Tuesday, July 21, 2015 4:54 PM To:

Williams, Gordon Robert (grwilliams1@tva.gov); Hammargren, Benjamin John Cc:

Schrull, Edward Dustin (edschrull@tva.gov); Chernoff, Margaret

Subject:

Request for Additional Information (RAI) for Browns Ferry Unit 1request to Adopt TSTF-460 (MF5827)

Importance:

High Ben/Gordon, By letter dated March 9, 2015, (Agencywide Documents Access and Management System Accession No. ML15111A396), Tennessee Valley Authority, (TVA, the licensee), submitted a license amendment request (LAR), regarding Browns Ferry Nuclear Plant, Unit 1, to modify Technical Specification 3.1.4, Control Rod Scram Times, to incorporate Technical Specifications Task Force Traveler (TSTF) 460, Revision 0. The request is submitted consistent with the guidance contained in Nuclear Regulatory Commission (NRC) approved TSTF-460. The proposed change would extend the frequency of verifying the scram time for a representative sample of control rods from 120 days of cumulative operation in Mode 1 to 200 days cumulative operation in Mode 1, along with a tighter acceptance criterion band. Integral to the NRC staffs approval of this change is the reliability of the scram rates. The NRC staff reviewed the licensees submittal and determined that the following information is needed to complete its review of this LAR.

RAI-1 The LAR provides information regarding test results, but does not provide any information regarding any significant changes in hardware or testing practices that could influence these test results. Provide a description and evaluation of the effects of any changes in hardware or testing practices that impact the test history data provided in the LAR.

As we agreed today, please provide your response to this RAI by August 20, 2015.

Thanks, Farideh Farideh E. Saba, P.E.

Senior Project Manager NRC/ADRO/NRR/DORL 301-415-1447 Mail Stop O-8G9A Farideh.Saba@NRC.GOV

Hearing Identifier:

NRR_PMDA Email Number:

2244 Mail Envelope Properties (Farideh.Saba@nrc.gov20150721165300)

Subject:

Request for Additional Information (RAI) for Browns Ferry Unit 1request to Adopt TSTF-460 (MF5827)

Sent Date:

7/21/2015 4:53:30 PM Received Date:

7/21/2015 4:53:00 PM From:

Saba, Farideh Created By:

Farideh.Saba@nrc.gov Recipients:

"Schrull, Edward Dustin (edschrull@tva.gov)" <edschrull@tva.gov>

Tracking Status: None "Chernoff, Margaret" <Margaret.Chernoff@nrc.gov>

Tracking Status: None "Williams, Gordon Robert (grwilliams1@tva.gov)" <grwilliams1@tva.gov>

Tracking Status: None "Hammargren, Benjamin John" <bjhammargren@tva.gov>

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 1669 7/21/2015 4:53:00 PM Options Priority:

High Return Notification:

No Reply Requested:

Yes Sensitivity:

Normal Expiration Date:

Recipients Received: