UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Bryan C. Hanson President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Rd.
Warrenville, IL 60555 June 2, 2015
SUBJECT:
PEACH BOTTOM ATOMIC POWER STATION, UNIT 3 - INDIVIDUAL NOTICE OF CONSIDERATION OF ISSUANCE OF AMENDMENT TO FACILITY OPERATING LICENSE, PROPOSED NO SIGNIFICANT HAZARDS CONSIDERATION DETERMINATION, AND OPPORTUNITY FOR HEARING (TAC NO. MF6285)
Dear Mr. Hanson:
The U.S. Nuclear Regulatory Commission (NRC) has forwarded the enclosed "Notice of Consideration of Issuance of Amendment to Facility Operating License, Proposed No Significant Hazards Consideration Determination, and Opportunity for a Hearing," to the Office of the Federal Register for publication.
This notice relates to your application dated May 29, 2015, in which you requested a change to a license condition pertaining to the replacement steam dryer (RSD) for Peach Bottom Atomic Power Station (PBAPS), Unit 3. Currently, the license condition requires that revised analysis for the RSD be submitted to the NRC, as a report, at least 90 days prior to the start of the PBAPS, Unit 3 extended power uprate (EPU) outage. The proposed amendment would reduce the period before the outage by which the analysis is to be submitted from 90 days to 30 days.
The EPU outage is scheduled to start on September 14, 2015.
If you have any questions, please contact me at 301-415-1420 or Rick.Ennis@nrc.gov.
Docket No. 50-278
Enclosure:
Notice of Consideration cc w/enclosure: Distribution via Listserv Sincerely, Richard B. Ennis, Senior Project Manager Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
ENCLOSURE FEDERAL REGISTER NOTICE
NUCLEAR REGULATORY COMMISSION
[Docket No. 50-278; NRC-20YY-XXXX]
[7590-01-P]
Exelon Generation Company, LLC; Peach Bottom Atomic Power Station, Unit 3 AGENCY: Nuclear Regulatory Commission.
ACTION: License amendment application; opportunity to comment, request a hearing, and petition for leave to intervene.
SUMMARY
- The U.S. Nuclear Regulatory Commission (NRC) is considering issuance of an amendment to Renewed Facility Operating License No. DPR-56, issued to Exelon Generation Company, LLC (the licensee), for operation of the Peach Bottom Atomic Power Station (PBAPS), Unit 3. The proposed amendment would change a license condition pertaining to the PBAPS, Unit 3 replacement steam dryer (RSD). Currently, the license condition requires that a revised analysis for the RSD be submitted to the NRC, as a report, at least 90 days prior to the start of the Unit 3 extended power uprate (EPU) outage. The proposed amendment would reduce the period before the outage by which the analysis is to be submitted from 90 days to 30 days. The licensee indicated that the EPU outage is scheduled to start on September 14, 2015.
DATES: Submit comments by [INSERT DATE 30 DAYS FROM DATE OF PUBLICATION].
Requests for a hearing or petition for leave to intervene must be filed by [INSERT DATE 60 DAYS FROM DATE OF PUBLICATION].
ADDRESSES: You may submit comments by any of the following methods (unless this document describes a different method for submitting comments on a specific subject):
Federal Rulemaking Web Site: Go to http://www.regulations.gov and search for Docket ID: NRC-20YY-XXXX. Address questions about NRC dockets to Carol Gallagher; telephone: 301-415-3463; e-mail: Carol.Gallagher@nrc.gov. For technical questions, contact the individual listed in the FOR FURTHER INFORMATION CONTACT section of this document.
Mail comments to: Cindy Bladey, Office of Administration, Mail Stop: OWFN HOB, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001.
For additional direction on obtaining information and submitting comments, see "Obtaining Information and Submitting Comments" in the SUPPLEMENTARY INFORMATION section of this document.
FOR FURTHER INFORMATION CONTACT: Richard B. Ennis, Office of Nuclear Reactor Regulation, telephone: 301-415-1420, e-mail: Rick.Ennis@nrc.gov; U.S. Nuclear Regulatory Commission, Washington DC 20555-0001.
SUPPLEMENTARY INFORMATION:
I. Obtaining Information and Submitting Comments.
A. Obtaining Information.
Please refer to Docket ID NRC-20YY-XXXX when contacting the NRC about the availability of information for this action. You may obtain publicly-available information related to this action by any of the following methods:
Federal rulemaking Web Site: Go to http://www.regulations.gov and search for Docket ID NRC-20YY-XXXX.
NRC's Agencywide Documents Access and Management System (ADAMS):
You may obtain publicly-available documents online in the ADAMS Public Documents collection at http://www.nrc.gov/reading-rm/adams.html. To begin the search, select "ADAMS Public Documents" and then select "Begin Web-based ADAMS Search." For problems with ADAMS, please contact the NRC's Public Document Room (PDR) reference staff at 1-800-397-4209, 301-415-4737, or by e-mail to pdr.resource@nrc.gov. The Peach Bottom Atomic Power Station, Unit 3, license amendment application, "Exigent License Amendment Request - Change to Unit 3 License Condition 2.C(15)(a)1," dated May 29, 2015, is available in ADAMS under Accession No. ML15149A473.
NRC's PDR: You may examine and purchase copies of public documents at the NRC's PDR, Room 01-F21, One White Flint North, 11555 Rockville Pike, Rockville, Maryland 20852.
B. Submitting Comments.
Please include Docket ID NRC-20YY-XXXX in your comment submission.
The NRC cautions you not to include identifying or contact information that you do not want to be publicly disclosed in your comment submission. The NRC will post all comment submissions at http://www.regulations.gov as well as enter the comment submissions into ADAMS. The NRC does not routinely edit comment submissions to remove identifying or contact information.
If you are requesting or aggregating comments from other persons for submission to the NRC, then you should inform those persons not to include identifying or contact information that they do not want to be publicly disclosed in their comment submission. Your request should state that the NRC does not routinely edit comment submissions to remove such information before making the comment submissions available to the public or entering the comment into ADAMS.
II. Introduction.
The NRG is considering issuance of an amendment to Renewed Facility Operating License No. DPR-56, issued to Exelon Generation Company, LLC, for operation of PBAPS, Unit 3, located in York and Lancaster Counties, Pennsylvania.
The proposed amendment would change license condition 2.C(15)(a)1 pertaining to the PBAPS, Unit 3 RSD. Currently, the license condition requires that revised stress analysis for the RSD be submitted to the NRG, as a report, at least 90 days prior to the start of the Unit 3 EPU outage. The proposed amendment would reduce the period before the outage by which the analysis is to be submitted from 90 days to 30 days. The EPU outage is scheduled to start on September 14, 2015. The revised analysis is based on results of recent testing and analysis for the PBAPS, Unit 2 RSD. Due to delays in the Unit 2 RSD testing and analysis, the licensee is unable to complete the Unit 3 RSD analysis and submit it to the NRG 90 days prior to the Unit 3 outage, as currently required by license condition 2.C(15)(a)1, while still maintaining the currently planned outage schedule. As such, the licensee requested a change to the licensee condition to reduce the required time prior to the outage for submittal of the report.
The licensee has requested that the amendment be processed under exigent circumstances, in accordance with the provisions in § 50.91 (a)(6) of Title 1 O of the Code of Federal Regulations (1 O CFR). Processing an amendment under exigent circumstances allows a reduced period for public comment on the proposed no significant hazards consideration determination, other than the normal 30-day comment period. However, the NRG staff has determined that there is sufficient time to allow the full 30-day public comment period. As such, the amendment is not being processed as an exigent amendment.
Before any issuance of the proposed license amendment, the NRC will need to make the findings required by the Atomic Energy Act of 1954, as amended (the Act), and NRC's regulations.
The NRC has made a proposed determination that the license amendment request involves no significant hazards consideration. Under the NRC's regulations in 10 CFR 50.92, this means that operation of the facility in accordance with the proposed amendment would not (1) involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a new or different kind of accident from any accident previously evaluated; or (3) involve a significant reduction in a margin of safety. As required by 1 O CFR 50.91 (a), the licensee has provided its analysis of the issue of no significant hazards consideration, which is presented below:
- 1.
Does the proposed amendment involve a significant increase in the probability or consequences of an accident previously evaluated?
Response: No.
The proposed exigent license amendment reduces the length of time prior to the outage by which a predictive summary stress analysis of the Peach Bottom Atomic Power Station (PBAPS), Unit 3 replacement steam dryer (RSD), performed using an NRG-approved methodology benchmarked on the PBAPS, Unit 2 RSD, must be submitted to the NRC for information. There is no required review or approval of the revised analysis needed to satisfy the license condition. The proposed change is an administrative change to the period before the outage and does not impact any system, structure or component in such a way as to affect the probability or consequences of an accident previously evaluated.
The proposed amendment is purely administrative and has no technical or safety aspects.
Therefore, the proposed change does not involve a significant increase in the probability or consequences of an accident previously evaluated.
- 2.
Does the proposed amendment create the possibility of a new or different kind of accident from any accident previously evaluated?
Response: No.
The proposed exigent license amendment reduces the length of time prior to the outage by which a revised stress analysis of the PBAPS, Unit 3 RSD must be submitted to the NRG for information. The proposed amendment is purely administrative and has no technical or safety aspects.
Therefore, the proposed change does not create the possibility of a new or different kind of accident from any accident previously evaluated.
- 3.
Does the proposed amendment involve a significant reduction in a margin of safety?
Response: No.
The proposed exigent license amendment reduces the length of time prior to the outage by which a revised stress analysis of the PBAPS, Unit 3 RSD must be submitted to the NRG for information. The proposed amendment is purely administrative and has no technical or safety aspects.
Therefore, the proposed change does not involve a significant reduction in a margin of safety.
The NRG staff has reviewed the licensee's analysis and, based on this review, it appears that the three standards of 1 O CFR 50.92(c) are satisfied. Therefore, the NRG staff proposes to determine that the license amendment request involves no significant hazards consideration.
The NRG is seeking public comments on this proposed determination that the license amendment request involves no significant hazards consideration. Any comments received within 30 days after the date of publication of this notice will be considered in making any final determination.
Normally, the Commission will not issue the amendment until the expiration of 60 days after the date of publication of this notice. The Commission may issue the license amendment before expiration of the 60-day notice period if the Commission concludes the amendment involves no significant hazards consideration. In addition, the Commission may issue the amendment prior to the expiration of the 30-day comment period should circumstances change during the 30-day comment period such that failure to act in a timely way would result, for example, in derating or shutdown of the facility. Should the Commission take action prior to the expiration of either the comment period or the notice period, it will publish in the Federal Register a notice of issuance. Should the Commission make a final no significant hazards consideration determination, any hearing will take place after issuance. The Commission expects that the need to take this action will occur very infrequently.
Ill. Opportunity to Request a Hearing and Petition for Leave to Intervene.
Within 60 days after the date of publication of this Federal Register notice, any person whose interest may be affected by this proceeding and who desires to participate as a party in the proceeding must file a written request for hearing or a petition for leave to intervene specifying the contentions which the person seeks to have litigated in the hearing with respect to the license amendment request. Requests for hearing and petitions for leave to intervene shall be filed in accordance with the NRC's "Agency Rules of Practice and Procedure" in 10 CFR part 2. Interested person(s) should consult a current copy of 1 O CFR 2.309, which is available at the NRC's PDR. The NRC's regulations are accessible electronically from the NRC Library on the NRC's Web site at http://www.nrc.gov/reading-rm/doc-collections/cfr/.
As required by 1 O CFR 2.309, a request for hearing or petition for leave to intervene must set forth with particularity the interest of the petitioner in the proceeding and how that interest may be affected by the results of the proceeding. The hearing request or petition must specifically explain the reasons why intervention should be permitted, with particular reference to the following general requirements: (1) the name, address, and telephone number of the requestor or petitioner; (2) the nature of the requestor's/petitioner's right under the Act to be made a party to the proceeding; (3) the nature and extent of the requester's/petitioner's property, financial, or other interest in the proceeding; and (4) the possible effect of any decision or order which may be entered in the proceeding on the requester's/petitioner's interest. The hearing request or petition must also include the specific contentions that the requester/petitioner seeks to have litigated at the proceeding.
For each contention, the requester/petitioner must provide a specific statement of the issue of law or fact to be raised or controverted, as well as a brief explanation of the basis for the contention. Additionally, the requester/petitioner must demonstrate that the issue raised by each contention is within the scope of the proceeding and is material to the findings that the NRG must make to support the granting of a license amendment in response to the application.
The hearing request or petition must also include a concise statement of the alleged facts or expert opinion that support the contention and on which the requester/petitioner intends to rely at the hearing, together with references to those specific sources and documents. The hearing request or petition must provide sufficient information to show that a genuine dispute exists with the applicant on a material issue of law or fact, including references to specific portions of the application for amendment that the petitioner disputes and the supporting reasons for each dispute. If the requester/petitioner believes that the application for amendment fails to contain information on a relevant matter as required by law, the requester/petitioner must identify each failure and the supporting reasons for the requester's/petitioner's belief. Each contention must be one which, if proven, would entitle the requester/petitioner to relief. A requester/petitioner who does not satisfy these requirements for at least one contention will not be permitted to participate as a party.
Those permitted to intervene become parties to the proceeding, subject to any limitations in the order granting leave to intervene, and have the opportunity to participate fully in the conduct of the hearing with respect to resolution of that person's admitted contentions, including the opportunity to present evidence and to submit a cross-examination plan for cross-examination of witnesses, consistent with NRG regulations, policies, and procedures. The Atomic Safety and Licensing Board will set the time and place for any prehearing conferences and evidentiary hearings, and the appropriate notices will be provided.
Hearing requests or petitions for leave to intervene must be filed no later than 60 days from the date of publication of this notice. Requests for hearing, petitions for leave to intervene, and motions for leave to file new or amended contentions that are filed after the 60-day deadline will not be entertained absent a determination by the presiding officer that the filing demonstrates good cause by satisfying the three factors in 1 O CFR 2.309(c)(1 )(i)-(iii).
If a hearing is requested, the Commission will make a final determination on the issue of no significant hazards consideration. The final determination will serve to decide when the hearing is held. If the final determination is that the amendment request involves no significant hazards consideration, the Commission may issue the amendment and make it immediately effective, notwithstanding the reqµest for a hearing. Any hearing held would take place after issuance of the amendment. If the final determination is that the amendment request involves a significant hazards consideration, then any hearing held would take place before the issuance of any amendment unless the Commission finds an imminent danger to the health or safety of the public, in which case it will issue an appropriate order or rule under 10 CFR part 2.
IV. Electronic Submissions (E-Filing).
All documents filed in NRG adjudicatory proceedings, including a request for hearing, a petition for leave to intervene, any motion or other document filed in the proceeding prior to the submission of a request for hearing or petition to intervene, and documents filed by interested governmental entities participating under 10 CFR 2.315(c), must be filed in accordance with the NRC's E-Filing rule (72 FR 49139; August 28, 2007). The E-Filing process requires participants to submit and serve all adjudicatory documents over the internet, or in some cases to mail copies on electronic storage media. Participants may not submit paper copies of their filings unless they seek an exemption in accordance with the procedures described below.
To comply with the procedural requirements of E-Filing, at least ten 10 days prior to the filing deadline, the participant should contact the Office of the Secretary by e-mail at hearing.docket@nrc.gov, or by telephone at 301-415-1677, to request (1) a digital identification (ID) certificate, which allows the participant (or its counsel or representative) to digitally sign documents and access the E-Submittal server for any proceeding in which it is participating; and (2) advise the Secretary that the participant will be submitting a request or petition for hearing (even in instances in which the participant, or its counsel or representative, already holds an NRG-issued digital ID certificate). Based upon this information, the Secretary will establish an electronic docket for the hearing in this proceeding if the Secretary has not already established an electronic docket.
Information about applying for a digital ID certificate is available on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals/getting-started.html. System requirements for accessing the E-Submittal server are detailed in the NRC's "Guidance for Electronic Submission," which is available on the agency's public Web site at http://www.nrc.gov/site-help/e-submittals.html.
Participants may attempt to use other software not listed on the Web site, but should note that the NRC's E-Filing system does not support unlisted software, and the NRC Meta System Help Desk will not be able to offer assistance in using unlisted software.
If a participant is electronically submitting a document to the NRC in accordance with the E-Filing rule, the participant must file the document using the NRC's online, Web-based submission form. In order to serve documents through the Electronic Information Exchange System, users will be required to install a Web browser plug-in from the NRC's Web site.
Further information on the Web-based submission form, including the installation of the Web browser plug-in, is available on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html.
Once a participant has obtained a digital ID certificate and a docket has been created, the participant can then submit a request for hearing or petition for leave to intervene.
Submissions should be in Portable Document Format (PDF) in accordance with NRC guidance available on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html. A filing is considered complete at the time the documents are submitted through the NRC's E-Filing system. To be timely, an electronic filing must be submitted to the E-Filing system no later than 11 :59 p.m. Eastern Time on the due date. Upon receipt of a transmission, the E Filing system time-stamps the document and sends the submitter an e-mail notice confirming receipt of the document. The E-Filing system also distributes an e-mail notice that provides access to the document to the NRC's Office of the General Counsel and any others who have advised the Office of the Secretary that they wish to participate in the proceeding, so that the filer need not serve the documents on those participants separately. Therefore, applicants and other participants (or their counsel or representative) must apply for and receive a digital ID certificate before a hearing requesVpetition to intervene is filed so that they can obtain access to the document via the E-Filing system.
A person filing electronically using the NRC's adjudicatory E-Filing system may seek assistance by contacting the NRC Meta System Help Desk through the "Contact Us" link located on the NRC's public Web site at http://www.nrc.gov/site-help/e-submittals.html, by e-mail to MSHD.Resource@nrc.gov, or by a toll-free call at 1-866-672-7640. The NRG Meta System Help Desk is available between 8:00 a.m. and 8:00 p.m., Eastern Time, Monday through Friday, excluding government holidays.
Participants who believe that they have a good cause for not submitting documents electronically must file an exemption request, in accordance with 10 CFR 2.302(g), with their initial paper filing requesting authorization to continue to submit documents in paper format.
Such filings must be submitted by: (1) first class mail addressed to the Office of the Secretary of the Commission, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, Attention: Rulemaking and Adjudications Staff; or (2) courier, express mail, or expedited delivery service to the Office of the Secretary, Sixteenth Floor, One White Flint North, 11555 Rockville Pike, Rockville, Maryland, 20852, Attention: Rulemaking and Adjudications Staff.
Participants filing a document in this manner are responsible for serving the document on all other participants. Filing is considered complete by first-class mail as of the time of deposit in the mail, or by courier, express mail, or expedited delivery service upon depositing the document with the provider of the service. A presiding officer, having granted an exemption request from using E-Filing, may require a participant or party to use E-Filing if the presiding officer subsequently determines that the reason for granting the exemption from use of E-Filing no longer exists.
Documents submitted in adjudicatory proceedings will appear in the NRC's electronic hearing docket which is available to the public athttp://ehd1.nrc.gov/ehd, unless excluded pursuant to an order of the Commission, or the presiding officer. Participants are requested not to include personal privacy information, such as social security numbers, home addresses, or home phone numbers in their filings, unless an NRG regulation or other law requires submission of such information. However, in some instances, a request to intervene will require including information on local residence in order to demonstrate a proximity assertion of interest in the proceeding. With respect to copyrighted works, except for limited excerpts that serve the purpose of the adjudicatory filings and would constitute a Fair Use application, participants are requested not to include copyrighted materials in their submission. For further details with respect to this action, see the application for license amendment dated May 29, 2015.
Attorney for licensee: J. Bradley Fewell, Esquire, Vice President and Deputy General Counsel, Exelon Generation Company, LLC, 4300 Winfield Rd., Warrenville, IL 60555.
NRG Branch Chief: Douglas A. Broaddus.
Dated at Rockville, Maryland, this 2nd day of June 2015.
For the Nuclear Regulatory Commission.
Richard B. Ennis, Senior Project Manager Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
LTR ML15152A442 OFFICE LPLl-2/PM LPLl-2/LA NAME REnnis LRonewicz DATE 06/02/15 06/02/15 Sincerely, IRA/
Richard B. Ennis, Senior Project Manager Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation LPLl-2 R/F RidsNrrPMPeachBottom Resource RidsRgn1 MailCenter Resource RidsNrrDorlDpr Resource FRN ML15152A450 LPLl-2/BC LPLl-2/PM DBroaddus REnnis 06/02/15 06/02/15